.1.3.6.1.4.1.318.1.1.1.2.2.12 · 1 row entry · 3 columns
A list of battery table entries. The number of battery
frames present in UPS.
upsAdvBatteryActualVoltageEntry entry .1.3.6.1.4.1.318.1.1.1.2.2.12.1
Information applicable to
each of the Battery frames.
Indexes
upsAdvBatteryActualVoltageTableIndex
Column Syntax OID
upsAdvBatteryActualVoltageTableIndex mandatory
The Battery Frame identifier. Battery Frame index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.2.12.1.1
upsAdvBatteryActualVoltagePolarity mandatory
The selected Battery Voltage Polarity.
0 indicates positive polarity.
1 indicates negative polarity.
Enumeration
Enumerated Values:
0positive
1negative
.1.3.6.1.4.1.318.1.1.1.2.2.12.1.2
upsAdvBatteryFrameActualVoltage mandatory
The actual battery bus voltage in Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.2.12.1.3
.1.3.6.1.4.1.318.1.1.1.2.2.13 · 1 row entry · 3 columns
A list of Battery Frame table entries.  The number of entries
is given by the value of Number of Battery Frames.
upsAdvTotalDCCurrentEntry entry .1.3.6.1.4.1.318.1.1.1.2.2.13.1
An entry containing information applicable to a
particular Battery Frame.
Indexes
upsAdvTotalDCCurrentTableIndex
Column Syntax OID
upsAdvTotalDCCurrentTableIndex mandatory
The Battery Frame identifier. Total DC Current
Table Index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.2.13.1.1
upsAdvTotalDCCurrentPolarity mandatory
The selected Battery Current Polarity.
0 indicates positive polarity.
1 indicates negative polarity.
Enumeration
Enumerated Values:
0positive
1negative
.1.3.6.1.4.1.318.1.1.1.2.2.13.1.2
upsAdvTotalFrameDCCurrent mandatory
The Total DC Current of battery in Amperes.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.2.13.1.3
.1.3.6.1.4.1.318.1.1.1.2.2.14 · 1 row entry · 4 columns
A list of Battery Frame table entries.  The number of entries
is given by number of Battery frames present.
upsAdvBatteryCurrentEntry entry .1.3.6.1.4.1.318.1.1.1.2.2.14.1
An entry containing information applicable to a
particular battery frame.
Indexes
upsAdvBatteryCurrentTableIndex upsAdvBatteryCurrentIndex
Column Syntax OID
upsAdvBatteryCurrentTableIndex mandatory
The Battery Frame identifier. Battery Current
Table Index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.2.14.1.1
upsAdvBatteryCurrentIndex mandatory
The battery frame identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.2.14.1.2
upsAdvBatteryCurrentPolarity mandatory
The selected Battery current polarity.
0 indicates positive polarity.
1 indicates negative polarity
Enumeration
Enumerated Values:
0positive
1negative
.1.3.6.1.4.1.318.1.1.1.2.2.14.1.3
upsAdvBatteryFrameCurrent mandatory
The Battery current measured in Amperes
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.2.14.1.4
.1.3.6.1.4.1.318.1.1.1.2.3.7 · 1 row entry · 3 columns
A list of Battery frame table entries.  The number of entries
is given by the number of Battery frames.
upsHighPrecBatteryActualVoltageEntry entry .1.3.6.1.4.1.318.1.1.1.2.3.7.1
An entry containing information applicable to a
particular battery frame.
Indexes
upsHighPrecBatteryActualVoltageTableIndex
Column Syntax OID
upsHighPrecBatteryActualVoltageTableIndex mandatory
The Battery Frame identifier. High Precision
Actual Voltage Table Index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.7.1.1
upsHighPrecBatteryActualVoltagePolarity mandatory
The selected Battery Voltage polarity.
0 indicates positive polarity.
1 indicates negative polarity.
Enumeration
Enumerated Values:
0positive
1negative
.1.3.6.1.4.1.318.1.1.1.2.3.7.1.2
upsHighPrecBatteryVoltage mandatory
The actual battery bus voltage expressed as tenths of Volts.
If not supported, return -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.7.1.3
.1.3.6.1.4.1.318.1.1.1.2.3.8 · 1 row entry · 3 columns
A list of Battery Frame table entries.  The number of entries
is given by the number of battery frames.
upsHighPrecTotalDCCurrentEntry entry .1.3.6.1.4.1.318.1.1.1.2.3.8.1
An entry containing information applicable to a
particular battery frame.
Indexes
upsHighPrecTotalDCCurrentTableIndex
Column Syntax OID
upsHighPrecTotalDCCurrentTableIndex mandatory
The Battery Frame identifier.
High precision Total DC Current index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.8.1.1
upsHighPrecTotalDCCurrentPolarity mandatory
The selected Battery Current polarity.
0 indicates positive polarity.
1 indicates negative polarity.
Enumeration
Enumerated Values:
0positive
1negative
.1.3.6.1.4.1.318.1.1.1.2.3.8.1.2
upsHighPrecTotalDCFrameCurrent mandatory
The total DC current in tenths of Amperes.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.8.1.3
.1.3.6.1.4.1.318.1.1.1.2.3.9 · 1 row entry · 4 columns
A list of Battery Frame table entries.  The number of entries
is given by the number of battery frames.
upsHighPrecBatteryCurrentEntry entry .1.3.6.1.4.1.318.1.1.1.2.3.9.1
An entry containing information applicable to a
particular battery frame.
Indexes
upsHighPrecBatteryCurrentTableIndex upsHighPrecBatteryCurrentIndex
Column Syntax OID
upsHighPrecBatteryCurrentTableIndex mandatory
The Battery frame identifier.
Battery Frame index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.9.1.1
upsHighPrecBatteryCurrentIndex mandatory
The Battery frame identifier.
Battery Index for each frame.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.9.1.2
upsHighPrecBatteryCurrentPolarity mandatory
The selected Battery Current polarity.
0 indicates positive polarity.
1 indicates negative polarity.
Enumeration
Enumerated Values:
0positive
1negative
.1.3.6.1.4.1.318.1.1.1.2.3.9.1.3
upsHighPrecBatteryFrameCurrent mandatory
The Battery current in tenths of Amperes.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.9.1.4
.1.3.6.1.4.1.318.1.1.1.2.3.10.2 · 1 row entry · 10 columns
A list of Battery Pack table entries.  The number of entries
is given by number of Battery Packs present.
upsHighPrecBatteryPackEntry entry .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1
An entry containing information applicable to a
particular battery pack.
Indexes
upsHighPrecBatteryPackIndex upsHighPrecBatteryCartridgeIndex
Column Syntax OID
upsHighPrecBatteryPackIndex mandatory
The battery pack identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1
upsHighPrecBatteryCartridgeIndex mandatory
The battery cartridge identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2
upsHighPrecBatteryPackFirmwareRevision mandatory
The battery pack firmware revision.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.3
upsHighPrecBatteryPackSerialNumber mandatory
The battery pack serial number.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4
upsHighPrecBatteryPackTemperature mandatory
The battery pack temperature measured in 10ths of degree Celcius
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5
upsHighPrecBatteryPackStatus mandatory
The battery status for the pack only.
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8…
OctetString .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.6
upsHighPrecBatteryPackCartridgeHealth mandatory
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order…
OctetString .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7
upsHighPrecBatteryPackCartridgeReplaceDate mandatory
The battery cartridge estimated battery replace date.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8
upsHighPrecBatteryPackCartridgeInstallDate mandatory
The battery cartridge install date.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.9
upsHighPrecBatteryPackCartridgeStatus mandatory
The battery cartridge status.
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 General…
OctetString .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10
.1.3.6.1.4.1.318.1.1.1.2.3.10.4 · 1 row entry · 10 columns
A list of Battery Pack table entries.  The number of entries
is given by number of Battery Packs present.
upsHighPrecBatteryPackOnlyEntry entry .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1
An entry containing information applicable to a
particular battery pack.
Indexes
upsHighPrecBatteryPackOnlyIndex
Column Syntax OID
upsHighPrecBatteryPackOnlyIndex mandatory
The battery pack identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.1
upsHighPrecBatteryPackOnlyFirmwareRevision mandatory
The battery pack firmware revision.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.2
upsHighPrecBatteryPackOnlySerialNumber mandatory
The battery pack serial number.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.3
upsHighPrecBatteryPackOnlyTemperature mandatory
The battery pack temperature measured in 10ths of degree Celcius
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.4
upsHighPrecBatteryPackOnlyStatus mandatory
The battery status for the pack only.
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8…
OctetString .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5
upsHighPrecBatteryPackOnlyHealth mandatory
The battery pack health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement pack
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replaceme…
OctetString .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.6
upsHighPrecBatteryPackOnlyReplaceDate mandatory
The battery pack estimated battery replace date.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.7
upsHighPrecBatteryPackOnlyInstallDate mandatory
The battery pack install date.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.8
upsHighPrecBatteryPackOnlyManufactureDate mandatory
The battery pack manufacture date.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.9
upsHighPrecBatteryPackOnlySKU mandatory
The battery pack SKU.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.10
.1.3.6.1.4.1.318.1.1.1.2.5 · 1 row entry · 16 columns
Table of battery cabinets
upsBatteryCabinetEntry entry .1.3.6.1.4.1.318.1.1.1.2.5.1
An entry containing information applicable to a
particular battery cabinet.
Indexes
upsBatteryCabinetIndex
Column Syntax OID
upsBatteryCabinetIndex optional
The Battery Cabinet identifier. Battery Cabinet
Table Index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.1
upsBatteryCabinetLocalIndex optional
The identification number for the actual battery cabinet in the system.
0 corresponds to the internal batteries
1 and higher corresponds to external battery cabinets
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.2
upsBatteryCabinetWiringConfiguration optional
The value indicates the wiring configuration, whether the battery is 2-wire or 3-wire.
If it's a 3-wire battery system, the system can have two voltages and currents per cabinet.
1 = 2-wire (a non-split battery)
2 = 3-w…
Enumeration
Enumerated Values:
1twoWire
2threeWire
.1.3.6.1.4.1.318.1.1.1.2.5.1.3
upsBatteryCabinetVoltagePolarity1 optional
The battery voltage. For a non-split battery, it is the full voltage.
For a split battery, the value is the voltage for one side/half of the battery
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.4
upsBatteryCabinetVoltagePolarity2 optional
The voltage for the second side/half of the battery in a split battery system.
If it is not a split battery, this reports -1
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.5
upsBatteryCabinetCurrentPolarity1 optional
The battery current. For a non-split battery, it is the full current.
For a split battery, the value is the current for one side/half of the battery
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.6
upsBatteryCabinetCurrentPolarity2 optional
The current for the second side/half of the battery in a split battery system.
If it is not a split battery, this reports -1
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.7
upsBatteryCabinetTemperature optional
The measured temperature of the battery cabinet in tenths of degrees Celcius
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.8
upsBatteryCabinetMaxTemperature optional
The highest temperature measured for the battery in the battery cabinet in tenths of degrees Celcius.
If there are multiple sensors in the battery cabinet, it is the selected highest actual value
of measured temperature…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.9
upsBatteryCabinetMinTemperature optional
The lowest temperature measured for the battery in the battery cabinet in tenths of degrees Celcius.
If there are multiple sensors in the battery cabinet, it is the selected lowest actual value
of measured temperatures.…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.10
upsBatteryCabinetAverageTemperature optional
The average temperature for all the battery sensors in the battery cabinet and
for the battery strings, if battery strings are present.
Measured in tenths of degrees Celcius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.11
upsBatteryCabinetFuse optional
If the battery cabinet has a common fuse, the status is given by this value.
1 = Fuse open
2 = Fuse OK
3 = Not present
Enumeration
Enumerated Values:
1fuseOpen
2fuseOk
3notPresent
.1.3.6.1.4.1.318.1.1.1.2.5.1.12
upsBatteryCabinetBreaker optional
The value indicates the battery cabinet breaker status. Reports 1 if no breaker is present.
1 = No breaker
2 = Unknown
3 = Breaker open
4 = Breaker closed
Enumeration
Enumerated Values:
1noBreaker
2unknown
3breakerOpen
4breakerClosed
.1.3.6.1.4.1.318.1.1.1.2.5.1.13
upsBatteryCabinetNumberOfStrings optional
The number of battery strings in the battery cabinet. The value can be 0,
meaning that no additional information on the battery string is available.
1 and higher means data in the table is provided.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.14
upsBatteryCabinetNumberOfVerticalPositions optional
The number of vertical levels or shelves for battery blocks/modules.
The levels are indexed from the bottom up
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.15
upsBatteryCabinetNumberOfHorizontalPositions optional
The number of horizontal positions for battery blocks/modules.
The levels are indexed from left to right
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.5.1.16
.1.3.6.1.4.1.318.1.1.1.2.6 · 1 row entry · 9 columns
Table of battery strings in the complete battery solution
upsBatteryCabStringEntry entry .1.3.6.1.4.1.318.1.1.1.2.6.1
An entry containing information applicable to a particular battery string
in the battery cabinet.
Indexes
upsBatteryCabStringIndex
Column Syntax OID
upsBatteryCabStringIndex optional
The battery cabinet string identifier. Battery cabinet string or halfstring
table index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.6.1.1
upsBatteryCabStringCabReference optional
Reference to the global battery cabinet index where the battery string is placed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.6.1.2
upsBatteryCabStringLocalIndex optional
Local battery string identification index in the actual battery cabinet (e.g. String 2 in cabinet)
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.6.1.3
upsBatteryCabStringCurrent optional
The current in a battery string or battery halfstring, in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.6.1.4
upsBatteryCabStringAverageTemperature optional
Temperature of the battery string or the average of the aggregated temperature of each
battery block/module (in tenths of degrees Celcius).
If not available, this variable is set to (-1999).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.6.1.5
upsBatteryCabStringMaxTemperature optional
The actual highest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.6.1.6
upsBatteryCabStringMinTemperature optional
The actual lowest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.6.1.7
upsBatteryCabStringFuseStatus optional
If the battery string has a common fuse, the status is given by this value.
1 = Fuse open
2 = Fuse OK
3 = Not present
Enumeration
Enumerated Values:
1fuseOpen
2fuseOk
3notPresent
.1.3.6.1.4.1.318.1.1.1.2.6.1.8
upsBatteryCabStringNumberOfBlocks optional
The number of battery blocks/modules in a battery string.
Can be 0, if no data is available in the table of individual battery blocks/cartridges
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.6.1.9
.1.3.6.1.4.1.318.1.1.1.2.7 · 1 row entry · 11 columns
Table of battery blocks/modules in the complete battery solution.
upsBatteryCabBlockEntry entry .1.3.6.1.4.1.318.1.1.1.2.7.1
An entry containing information applicable to a particular battery block
in the battery cabinet.
Indexes
upsBatteryCabBlockIndex
Column Syntax OID
upsBatteryCabBlockIndex optional
The battery cabinet block identifier. Global battery cabinet block
table index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.7.1.1
upsBatteryCabBlockStringReference optional
Reference to the specific global battery string index
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.7.1.2
upsBatteryCabBlockLocalIndex optional
Local battery block/module identification index in the actual battery string (e.g. Battery block 3 in the battery string)
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.7.1.3
upsBatteryCabBlockPresent optional
Value indicates if battery block/module is present in the system.
Typically battery modules are removable and battery blocks are static. Reports notAvailable(3) if data is not available
Enumeration
Enumerated Values:
1present
2notPresent
3notAvailable
.1.3.6.1.4.1.318.1.1.1.2.7.1.4
upsBatteryCabBlockType optional
Text string value, showing the vendor and model of the battery in the battery block/module
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.2.7.1.5
upsBatteryCabBlockTemperature optional
The temperature for the battery block/module in tenths of degrees Celcius.
If multiple sensors are available it is the highest temperature in the battery block/module
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.7.1.6
upsBatteryCabBlockFuseStatus optional
If the battery module has a fuse, the status is given by this value.
1 = Fuse open
2 = Fuse OK
3 = Not present
Enumeration
Enumerated Values:
1fuseOpen
2fuseOk
3notPresent
.1.3.6.1.4.1.318.1.1.1.2.7.1.7
upsBatteryCabBlockVoltage optional
The voltage of the battery block/module
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.7.1.8
upsBatteryCabBlockNumberOfCells optional
The number of cells in the battery block/module
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.7.1.9
upsBatteryCabBlockVerticalPosition optional
The vertical position of the battery block/module in the actual battery cabinet
(e.g. 4, if it is the 4th shelf counting from the bottom)
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.7.1.10
upsBatteryCabBlockHorizontalPosition optional
The horizontal position of the battery block/module in the actual battery cabinet
(e.g. 3, if it is the 3rd position counting from the left)
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.7.1.11
.1.3.6.1.4.1.318.1.1.1.2.8 · 1 row entry · 5 columns
Table of battery cells in a battery block/module in the complete battery solution
upsBatteryCabBlockCellEntry entry .1.3.6.1.4.1.318.1.1.1.2.8.1
An entry containing information applicable to a particular battery cell
inside the battery block.
Indexes
upsBatteryCabBlockCellIndex
Column Syntax OID
upsBatteryCabBlockCellIndex optional
The battery block cell identifier. Global battery block cell
table index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.8.1.1
upsBatteryCabBlockCellReference optional
Reference to the specific global battery block/module index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.8.1.2
upsBatteryCabBlockCellLocalIndex optional
Local battery block/module identification index in the actual battery block (e.g. battery cell 5 in the battery block)
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.8.1.3
upsBatteryCabBlockCellVoltage optional
The measured battery cell voltage
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.8.1.4
upsBatteryCabBlockCellTemperature optional
The temperature for the battery cell in tenths of degrees Celcius.
If there is not a temperature sensor for each battery cell, then report -1 for those, which are not present.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.2.8.1.5
.1.3.6.1.4.1.318.1.1.1.3.2.10 · 1 row entry · 7 columns
A list of input table entries.  The number of entries
is given by the value of upsPhaseNumInputs.
upsAdvInputStatisticsEntry entry .1.3.6.1.4.1.318.1.1.1.3.2.10.1
An entry containing information applicable to a
particular input.
Indexes
upsAdvInputStatisticsIndex
Column Syntax OID
upsAdvInputStatisticsIndex mandatory
The input identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.3.2.10.1.1
upsAdvInputApparentPower mandatory
The input apparent power(sum of all of the three phases) measured in kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.3.2.10.1.2
upsAdvInputVoltageTHD mandatory
The input voltage Total Harmonic Distortion in percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.3.2.10.1.3
upsAdvInputBypassVoltageTHD mandatory
The bypass input voltage Total Harmonic Distortion in percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.3.2.10.1.4
upsAdvInputPeakCurrent mandatory
The input peak current in Amperes.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.3.2.10.1.5
upsAdvInputBypassPeakCurrent mandatory
The bypass input peak current in Amperes.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.3.2.10.1.6
upsAdvInputActivePower mandatory
The input active power measured in kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.3.2.10.1.7
.1.3.6.1.4.1.318.1.1.1.4.2.10 · 1 row entry · 4 columns
A list of input table entries.  The number of entries
is given by the value of upsPhaseNumOutputs.
upsAdvOutputStatisticsEntry entry .1.3.6.1.4.1.318.1.1.1.4.2.10.1
An entry containing information applicable to a
particular output.
Indexes
upsAdvOutputStatisticsIndex
Column Syntax OID
upsAdvOutputStatisticsIndex mandatory
The output identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.4.2.10.1.1
upsAdvOutputPeakCurrent mandatory
The output peak current in Amperes.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.4.2.10.1.2
upsAdvOutputCurrentTHD mandatory
The output current Total Harmonic Distortion in percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.4.2.10.1.3
upsAdvOutputCrestFactor mandatory
The output current crest factor expressed in tenths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.4.2.10.1.4
.1.3.6.1.4.1.318.1.1.1.5.1.2 · 1 row entry · 4 columns
A list of devices that are plugged into the UPS.
The number of entries is given by the value of
upsBasicConfigNumDevices.
upsBasicConfigDeviceEntry entry .1.3.6.1.4.1.318.1.1.1.5.1.2.1
The devices plugged in to the UPS.
Indexes
deviceIndex
Column Syntax OID
deviceIndex mandatory
The index of the device that is plugged into the UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.5.1.2.1.1
deviceName mandatory
The name/description of the device plugged into the UPS.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.5.1.2.1.2
vaRating mandatory
The volt-amp rating of the device plugged into the UPS.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.5.1.2.1.3
acceptThisDevice mandatory
An entry is added if yes, the entry is deleted if no.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.1.1.5.1.2.1.4
.1.3.6.1.4.1.318.1.1.1.5.2.13 · 1 row entry · 2 columns
Current settings of UPS dip switches.
upsAdvConfigDipSwitchEntry entry .1.3.6.1.4.1.318.1.1.1.5.2.13.1
The current setting of one dip switch.
Indexes
dipSwitchIndex
Column Syntax OID
dipSwitchIndex mandatory
The index of a UPS dip switch.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.5.2.13.1.1
dipSwitchStatus mandatory
The setting of a UPS dip switch.
Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.318.1.1.1.5.2.13.1.2
.1.3.6.1.4.1.318.1.1.1.5.2.16 · 1 row entry · 3 columns
The table listing the allowed values for all discrete
configurable UPS variables.
upsAdvConfigAllowedSetEntry entry .1.3.6.1.4.1.318.1.1.1.5.2.16.1
The table entry for a configurable UPS variable.
Indexes
apcUpsConfigFieldIndex
Column Syntax OID
apcUpsConfigFieldIndex mandatory
The index to an eeprom field entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.5.2.16.1.1
apcUpsConfigFieldOID mandatory
The OID of the current configurable value.
ObjectIdentifier .1.3.6.1.4.1.318.1.1.1.5.2.16.1.2
apcUpsConfigFieldValueRange mandatory
The discrete set of allowed values of a configurable
register. Individual values are delimited by a comma.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.5.2.16.1.3

upsPhaseInputTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.9.2.2 · 1 row entry · 6 columns
A list of input table entries.  The number of entries
is given by the value of upsPhaseNumInputs.
upsPhaseInputEntry entry .1.3.6.1.4.1.318.1.1.1.9.2.2.1
An entry containing information applicable to a
particular input.
Indexes
upsPhaseInputTableIndex
Column Syntax OID
upsPhaseInputTableIndex mandatory
The input identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.2.1.1
upsPhaseNumInputPhases mandatory
The number of input phases utilized in this
device. The sum of all the upsPhaseNumInputPhases
variable indicates the number of rows in the
input phase table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.2.1.2
upsPhaseInputVoltageOrientation mandatory
The input voltage orientation:
1: unknown for this UPS
2: singlePhase - phase 1 voltage is between Phase 1
and Neutral.
3: splitPhase - phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Phase 2 …
Enumeration
Enumerated Values:
1unknown
2singlePhase
3splitPhase
4threePhasePhaseToNeutral
5threePhasePhaseToPhase
.1.3.6.1.4.1.318.1.1.1.9.2.2.1.3
upsPhaseInputFrequency mandatory
The input frequency in 0.1 Hertz, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.2.1.4
upsPhaseInputType mandatory
The input type.
Enumeration
Enumerated Values:
1unknown
2main
3bypass
.1.3.6.1.4.1.318.1.1.1.9.2.2.1.5
upsPhaseInputName mandatory
A name given to a particular input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.9.2.2.1.6
.1.3.6.1.4.1.318.1.1.1.9.2.3 · 1 row entry · 14 columns
A list of input table entries.  The number of entries
is given by the sum of the upsPhaseNumInputPhases.
upsPhaseInputPhaseEntry entry .1.3.6.1.4.1.318.1.1.1.9.2.3.1
An entry containing information applicable to a
particular input phase.
Indexes
upsPhaseInputPhaseTableIndex upsPhaseInputPhaseIndex
Column Syntax OID
upsPhaseInputPhaseTableIndex mandatory
The input identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.1
upsPhaseInputPhaseIndex mandatory
The input phase identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.2
upsPhaseInputVoltage mandatory
The input voltage in VAC, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.3
upsPhaseInputMaxVoltage mandatory
The maximum input voltage in VAC measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.4
upsPhaseInputMinVoltage mandatory
The minimum input voltage in VAC measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.5
upsPhaseInputCurrent mandatory
The input current in 0.1 amperes, or -1 if it's
unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.6
upsPhaseInputMaxCurrent mandatory
The maximum input current in 0.1 amperes measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.7
upsPhaseInputMinCurrent mandatory
The minimum input current in 0.1 amperes measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.8
upsPhaseInputPower mandatory
The input power in Watts, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.9
upsPhaseInputMaxPower mandatory
The maximum input power in Watts measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.10
upsPhaseInputMinPower mandatory
The minimum input power in Watts measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.11
upsPhaseInputApparentPower mandatory
The input apparent power of the UPS in kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.12
upsPhaseInputPowerFactor mandatory
The input power factor measured in hundredth.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.13
upsPhaseInputVoltagePN mandatory
The input voltage measured across Phase to Neutral in VAC, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.2.3.1.14

upsPhaseOutputTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.9.3.2 · 1 row entry · 4 columns
A list of output table entries.  The number of entries
is given by the value of upsOutputNumPhases.
upsPhaseOutputEntry entry .1.3.6.1.4.1.318.1.1.1.9.3.2.1
An entry containing information applicable to a
particular output.
Indexes
upsPhaseOutputTableIndex
Column Syntax OID
upsPhaseOutputTableIndex mandatory
The output identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.2.1.1
upsPhaseNumOutputPhases mandatory
The number of output phases utilized in this
device. The sum of all the upsPhaseNumOutputPhases
variable indicates the number of rows in the
output phase table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.2.1.2
upsPhaseOutputVoltageOrientation mandatory
The output voltage orientation:
1: unknown for this UPS
2: singlePhase - phase 1 voltage is between Phase 1
and Neutral.
3: splitPhase - phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Phase 2…
Enumeration
Enumerated Values:
1unknown
2singlePhase
3splitPhase
4threePhasePhaseToNeutral
5threePhasePhaseToPhase
.1.3.6.1.4.1.318.1.1.1.9.3.2.1.3
upsPhaseOutputFrequency mandatory
The output frequency in 0.1 Hertz, or -1 if it's
unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.2.1.4
.1.3.6.1.4.1.318.1.1.1.9.3.3 · 1 row entry · 23 columns
A list of output table entries.  The number of
entries is given by the sum of the upsPhaseNumOutputPhases.
upsPhaseOutputPhaseEntry entry .1.3.6.1.4.1.318.1.1.1.9.3.3.1
An entry containing information applicable to a
particular output phase.
Indexes
upsPhaseOutputPhaseTableIndex upsPhaseOutputPhaseIndex
Column Syntax OID
upsPhaseOutputPhaseTableIndex mandatory
The output identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.1
upsPhaseOutputPhaseIndex mandatory
The output phase identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.2
upsPhaseOutputVoltage mandatory
The output voltage in VAC, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.3
upsPhaseOutputCurrent mandatory
The output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.4
upsPhaseOutputMaxCurrent mandatory
The maximum output current in 0.1 amperes measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.5
upsPhaseOutputMinCurrent mandatory
The minimum output current in 0.1 amperes measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.6
upsPhaseOutputLoad mandatory
The output load in VA, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.7
upsPhaseOutputMaxLoad mandatory
The maximum output load in VA measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.8
upsPhaseOutputMinLoad mandatory
The minimum output load in VA measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.9
upsPhaseOutputPercentLoad mandatory
The percentage of the UPS load capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.10
upsPhaseOutputMaxPercentLoad mandatory
The maximum percentage of the UPS load capacity in
VA measured at redundancy @ (n + x) presently
being used on this output phase since the last reset
(upsPhaseResetMaxMinValues), or -1 if it's unsupported
by this UPS. S…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.11
upsPhaseOutputMinPercentLoad mandatory
The minimum percentage of the UPS load capacity in
VA measured at redundancy @ (n + x) presently
being used on this output phase since the last reset
(upsPhaseResetMaxMinValues), or -1 if it's unsupported
by this UPS. S…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.12
upsPhaseOutputPower mandatory
The output power in Watts, or -1 if it's
unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.13
upsPhaseOutputMaxPower mandatory
The maximum output power in Watts measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.14
upsPhaseOutputMinPower mandatory
The minimum output power in Watts measured
since the last reset (upsPhaseResetMaxMinValues), or
-1 if it's unsupported by this UPS.
Sampled every 30 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.15
upsPhaseOutputPercentPower mandatory
The percentage of the UPS power capacity in Watts at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.16
upsPhaseOutputMaxPercentPower mandatory
The maximum percentage of the UPS power capacity
in Watts measured at redundancy @ (n + x) presently
being used on this output phase since the last
reset (upsPhaseResetMaxMinValues), or -1 if it's
unsupported by this UP…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.17
upsPhaseOutputMinPercentPower mandatory
The maximum percentage of the UPS power capacity
in Watts measured at redundancy @ (n + x) presently
being used on this output phase since the last
reset (upsPhaseResetMaxMinValues), or -1 if it's
unsupported by this UP…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.18
upsPhaseOutputPowerFactor mandatory
The Output power factor of the UPS in hundredth.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.19
upsPhaseOutputApparentPower mandatory
Apparent power in kVA
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.20
upsPhaseOutputInverterVoltage mandatory
Output voltage in VAC measured at the output of inverter.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.21
upsPhaseOutputVoltagePN mandatory
The output voltage measured across Phase to Neutral in VAC, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.22
upsPhaseOutputEnergyUsage mandatory
The output energy usage of the phase in hundredths of kWh.
Unsigned32
Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32
.1.3.6.1.4.1.318.1.1.1.9.3.3.1.23

upsSCGStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.10.2.2 · 1 row entry · 4 columns
A list of SCG status table entries.  The number of entries
is given by the value of upsSCGNumOfGroupMembers.
upsSCGStatusEntry entry .1.3.6.1.4.1.318.1.1.1.10.2.2.1
An entry containing information applicable to a
particular SCG Member.
Indexes
upsSCGStatusTableIndex
Column Syntax OID
upsSCGStatusTableIndex mandatory
The index of a status entry for an active, communicating SCG member.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.10.2.2.1.1
upsSCGMemberIP mandatory
The IP address of an active, communicating SCG Member.
RFC1155-SMIIpAddress
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.1.1.10.2.2.1.2
upsSCGACInputStatus mandatory
This OID indicates the AC Input Status of the SCG Member.
acInGood(1) indicates the AC Input is within tolerance.
acInBad(2) indicates the AC Input is not within tolerance.
Enumeration
Enumerated Values:
1acInGood
2acInBad
.1.3.6.1.4.1.318.1.1.1.10.2.2.1.3
upsSCGACOutputStatus mandatory
This OID indicates the AC Output Status of the SCG Member.
acOutOn(1) indicates the UPS output is providing power to the load.
acOutOff(2) indicates the UPS output is not providing power to the load.
Enumeration
Enumerated Values:
1acOutOn
2acOutOff
.1.3.6.1.4.1.318.1.1.1.10.2.2.1.4
.1.3.6.1.4.1.318.1.1.1.12.1.2 · 1 row entry · 6 columns
Allows for getting status of the outlet groups. The number of
entries is contained in the upsOutletGroupStatusTableSize OID.
upsOutletGroupStatusEntry entry .1.3.6.1.4.1.318.1.1.1.12.1.2.1
The outlet group status to get.
Indexes
upsOutletGroupStatusIndex
Column Syntax OID
upsOutletGroupStatusIndex mandatory
The index to the outlet group entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.1.2.1.1
upsOutletGroupStatusName mandatory
The name of the outlet group. This OID is provided
for informational purposes only. This value is set
by the upsOutletGroupConfigName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.12.1.2.1.2
upsOutletGroupStatusGroupState mandatory
Getting this variable will return the outlet group state. If the outlet
group is on, the upsOutletGroupStatusOn (1) value will be returned. If
the outlet group is off, the upsOutletGroupStatusOff (2) value will be
retur…
Enumeration
Enumerated Values:
1upsOutletGroupStatusOn
2upsOutletGroupStatusOff
3upsOutletGroupStatusUnknown
.1.3.6.1.4.1.318.1.1.1.12.1.2.1.3
upsOutletGroupStatusCommandPending mandatory
Getting this variable will return the command pending
state of the outlet group. If a command is pending on the
outlet group, the upsOutletGroupCommandPending (1) value
will be returned. If there is not a command pendin…
Enumeration
Enumerated Values:
1upsOutletGroupCommandPending
2upsOutletGroupNoCommandPending
.1.3.6.1.4.1.318.1.1.1.12.1.2.1.4
upsOutletGroupStatusOutletType mandatory
Getting this variable will return the type of outlet group.
If present in the system, the main outlet group is
'unswitched' and must be on in order for any of the switched
outlet groups to be on. Conversely, if the main…
Enumeration
Enumerated Values:
1upsSwitchedOutletGroup
2upsMainOutletGroup
.1.3.6.1.4.1.318.1.1.1.12.1.2.1.5
upsOutletGroupStatusGroupFullState mandatory
An ASCII string containing the 32 flags representing the
current state(s) of the outlet group. If the Network Card
is unable to determine the state of the outlet group, this
variable is set to 'UNKNOWN'.

RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.12.1.2.1.6
.1.3.6.1.4.1.318.1.1.1.12.2.2 · 1 row entry · 14 columns
The list of outlet groups to configure. The number of entries
is defined by the upsOutletGroupConfigTableSize OID.
upsOutletGroupConfigEntry entry .1.3.6.1.4.1.318.1.1.1.12.2.2.1
The outlet groups to configure.
Indexes
upsOutletGroupConfigIndex
Column Syntax OID
upsOutletGroupConfigIndex mandatory
The index to the outlet group entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.1
upsOutletGroupConfigName mandatory
The name of the outlet group.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.2
upsOutletGroupConfigPowerOnDelay mandatory
The amount of time (seconds) the outlet group will delay
powering on when the delayed on, reboot, or shutdown command is
applied. Allowed values vary by UPS model. The value of -1 is
used for Never if supported by the U…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.3
upsOutletGroupConfigPowerOffDelay mandatory
The amount of time (seconds) the outlet group will delay
powering off when the delayed off, reboot, or shutdown command is
applied. Allowed values vary by UPS model. The value of -1 is
used for Never if supported by the…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.4
upsOutletGroupConfigRebootDuration mandatory
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait
(seconds) after turning the power off, at the start
of the sequence, before initiating the power on sequence.
A…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.5
upsOutletGroupConfigMinReturnRuntime mandatory
In an Outlet Group shutdown sequence, the Outlet Group cycles
power off then on. This OID defines the minimum amount of UPS
runtime (seconds) that is required in order to power the
Outlet Group on. Allowed values vary b…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.6
upsOutletGroupConfigOutletType mandatory
Getting this variable will return the type of outlet group.
If present in the system, the main outlet group is
'unswitched' and must be on in order for any of the switched
outlet groups to be on. Conversely, if the main…
Enumeration
Enumerated Values:
1upsSwitchedOutletGroup
2upsMainOutletGroup
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.7
upsOutletGroupConfigLoadShedControlSkipOffDelay mandatory
Configures whether the outlet group's off delay setting
(upsOutletGroupConfigPowerOffDelay) will be used in a load
shedding situation, where applicable.
Enumerationr/w
Enumerated Values:
1upsOutletGroupConfigSkipOffDelay
2upsOutletGroupConfigUseOffDelay
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.8
upsOutletGroupConfigLoadShedControlAutoRestart mandatory
Configures whether the outlet group will automatically restart
after a load shedding situation, where applicable.
Enumerationr/w
Enumerated Values:
1upsOutletGroupConfigAutoRestart
2upsOutletGroupConfigManualRestart
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.9
upsOutletGroupConfigLoadShedControlTimeOnBattery mandatory
Configures whether the outlet group will load shed (turn off)
after the UPS device's time on battery has exceeded the
upsOutletGroupConfigLoadShedTimeOnBattery OID setting. The
settings for upsOutletGroupConfigLoadShedC…
Enumerationr/w
Enumerated Values:
1upsOutletGroupConfigDisableTimeOnBatteryLoadShed
2upsOutletGroupConfigEnableTimeOnBatteryLoadShed
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.10
upsOutletGroupConfigLoadShedControlRuntimeRemaining mandatory
Configures whether the outlet group will load shed (turn off)
when the UPS is on battery and the remaining runtime is less
than the upsOutletGroupConfigLoadShedRuntimeRemaining OID
setting. The settings for
upsOutletGro…
Enumerationr/w
Enumerated Values:
1upsOutletGroupConfigDisableRuntimeRemainingLoadShed
2upsOutletGroupConfigEnableRuntimeRemainingLoadShed
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.11
upsOutletGroupConfigLoadShedControlInOverload mandatory
Configures whether the outlet group will load shed (turn off)
when the UPS is in an overload condition. The setting for
upsOutletGroupConfigLoadShedControlSkipOffDelay is valid for
this load shed condition. Returns -1 i…
Enumerationr/w
Enumerated Values:
1upsOutletGroupConfigDisableInOverloadLoadShed
2upsOutletGroupConfigEnableInOverloadLoadShed
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.12
upsOutletGroupConfigLoadShedTimeOnBattery mandatory
When the UPS has been on battery for more time than this
value, the outlet group will turn off if this condition is
enabled by the upsOutletGroupConfigLoadShedControlTimeOnBattery
OID. Allowed values vary by UPS model.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.13
upsOutletGroupConfigLoadShedRuntimeRemaining mandatory
When the runtime remaining is less than this value, the outlet
group will turn off if this condition is enabled by the
upsOutletGroupConfigLoadShedControlRuntimeRemaining OID.
Allowed values vary by UPS model.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.2.2.1.14
.1.3.6.1.4.1.318.1.1.1.12.3.2 · 1 row entry · 4 columns
Allows for control of individual outlet groups. The number of
entries is contained in the upsOutletGroupControlTableSize OID.
upsOutletGroupControlEntry entry .1.3.6.1.4.1.318.1.1.1.12.3.2.1
The outlet group to control.
Indexes
upsOutletGroupControlIndex
Column Syntax OID
upsOutletGroupControlIndex mandatory
The index to the outlet group entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.12.3.2.1.1
upsOutletGroupControlName mandatory
The name of the outlet group. This OID is provided
for informational purposes only. This value is set
by the upsOutletGroupConfigName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.12.3.2.1.2
upsOutletGroupControlCommand mandatory
Getting this variable will return the outlet group state. If the outlet
group is on, the upsOutletGroupImmediateOn (1) value will be returned. If
the outlet group is off, the upsOutletGroupImmediateOff (2) value will be…
Enumerationr/w
Enumerated Values:
1upsOutletGroupImmediateOn
2upsOutletGroupImmediateOff
3upsOutletGroupImmediateRebootWithOrWithoutAC
4upsOutletGroupDelayedOn
5upsOutletGroupDelayedOff
6upsOutletGroupDelayedRebootWithOrWithoutAC
7upsOutletGroupCancelPendingCommand
8upsOutletGroupControlUnknown
9upsOutletGroupImmediateRebootShutdown
10upsOutletGroupDelayedRebootShutdown
.1.3.6.1.4.1.318.1.1.1.12.3.2.1.3
upsOutletGroupControlOutletType mandatory
Getting this variable will return the type of outlet group.
If present in the system, the main outlet group is
'unswitched' and must be on in order for any of the switched
outlet groups to be on. Conversely, if the main…
Enumeration
Enumerated Values:
1upsSwitchedOutletGroup
2upsMainOutletGroup
.1.3.6.1.4.1.318.1.1.1.12.3.2.1.4

upsDiagIMTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.13.1.2 · 1 row entry · 10 columns
Allows for diagnostics of individual Intelligence Modules. The number of
entries is contained in the upsDiagIMTableSize OID.
upsDiagIMEntry entry .1.3.6.1.4.1.318.1.1.1.13.1.2.1
The diagnostics and information of an Intelligence Module.
Indexes
upsDiagIMIndex
Column Syntax OID
upsDiagIMIndex mandatory
The index to the Intelligence Module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.1
upsDiagIMType mandatory
The type of the Intelligence Module.
imUnknown(1) indicates the IM type is unknown.
imMIM(2) indicates the IM type is a Main Intelligence Module.
imRIM(3) indicates the IM type is Redundant Intelligence Module.
Enumeration
Enumerated Values:
1imUnknown
2imMIM
3imRIM
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.2
upsDiagIMStatus mandatory
The status of the Intelligence Module.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the …
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.3
upsDiagIMFirmwareRev mandatory
The firmware revision of the Intelligence Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.4
upsDiagIMSlaveFirmwareRev mandatory
The slave firmware revision of the Intelligence Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.5
upsDiagIMHardwareRev mandatory
The hardware revision of the Intelligence Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.6
upsDiagIMSerialNum mandatory
The serial number of the Intelligence Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.7
upsDiagIMManufactureDate mandatory
The manufacture date of the Intelligence Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.8
upsDiagIMInControl mandatory
The Intelligence Module state.
activeInControl(1) indicates the IM is active and in control.
passive(2) indicates the IM is in passive state.
unknown(3) indicates the IM is in unknown state.
fault(4) indicates the IM is…
Enumeration
Enumerated Values:
1activeInControl
2passive
3unknown
4fault
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.9
upsDiagIMSKU mandatory
The SKU of the Intelligence Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.1.2.1.10

upsDiagPMTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.13.2.2 · 1 row entry · 11 columns
Allows for diagnostics of Individual Power modules. The number of
entries is contained in the upsDiagPMTableSize OID.
upsDiagPMEntry entry .1.3.6.1.4.1.318.1.1.1.13.2.2.1
The diagnostics of a Power Module.
Indexes
upsDiagPMIndex
Column Syntax OID
upsDiagPMIndex mandatory
The index to the Power Module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.1
upsDiagPMStatus mandatory
The status of the Power Module.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the device …
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.2
upsDiagPMFirmwareRev mandatory
The firmware revision of the Power Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.3
upsDiagPMHardwareRev mandatory
The hardware revision of the Power Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.4
upsDiagPMSerialNum mandatory
The serial number of the Power Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.5
upsDiagPMManufactureDate mandatory
The manufacture date of the Power Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.6
upsDiagPMModelNum mandatory
The model number of the Power Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.7
upsDiagPMRating optional
The power rating (in kVA) of the Power Module
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.8
upsDiagPMSKU optional
The SKU of the Power Module
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.9
upsDiagPMAverageFanSpeed optional
The average fan speed of the working fans in the Power Module in revolutions per minute (RPM).
Returns (-1) if not set.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.10
upsDiagPMAmbientTemperature optional
The ambient temperature inside the Power Module in tenths of degrees celsius.
If not available, this variable is set to (-1999).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.2.1.11
.1.3.6.1.4.1.318.1.1.1.13.2.3 · 1 row entry · 7 columns
Allows for diagnostics of individual power module's lifetime information.
The number of entries is contained in the upsDiagPMTableSize OID.
upsDiagPMLifetimeInfoEntry entry .1.3.6.1.4.1.318.1.1.1.13.2.3.1
The diagnostics of a Power Module lifetime information.
Indexes
upsDiagPMLifetimeInfoIndex
Column Syntax OID
upsDiagPMLifetimeInfoIndex mandatory
The index to the Power Module lifetime information entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.3.1.1
upsDiagPMLifetimeStatus mandatory
The status of the Power Module lifetime information.
ok(1) indicates the device lifetime status is OK.
nearEnd(2) indicates the device lifetime status is near end.
exceeded(3) indicates the device lifetime status is exc…
Enumeration
Enumerated Values:
1ok
2nearEnd
3exceeded
4unknown
.1.3.6.1.4.1.318.1.1.1.13.2.3.1.2
upsDiagPMEstmtdLifetimeRmng mandatory
Displays the time remaining for the module before it should be replaced.
Measured in months. This value is set when you originally install the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.3.1.3
upsDiagPMEstmtdLifetimeRmngPct mandatory
Displays the percentage of the total lifetime remaining for the module
before it should be replaced.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.3.1.4
upsDiagPMFanLifetimeStatus mandatory
The status of the Power Module Fan lifetime information.
ok(1) indicates the device lifetime status is OK.
nearEnd(2) indicates the device lifetime status is near end.
exceeded(3) indicates the device lifetime status is…
Enumeration
Enumerated Values:
1ok
2nearEnd
3exceeded
4unknown
.1.3.6.1.4.1.318.1.1.1.13.2.3.1.5
upsDiagPMFanEstmtdLifetimeRmng mandatory
Displays the time remaining, measured in months, before the module's
fan should be replaced. It is reset by the field service engineer when
a new fan is installed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.3.1.6
upsDiagPMFanEstmtdLifetimeRmngPct mandatory
Displays the percentage of the total lifetime remaining
before the module's fan should be replaced.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.3.1.7
.1.3.6.1.4.1.318.1.1.1.13.2.5 · 1 row entry · 5 columns
Allows for the diagnostics of individual power module enclosure door filters.
The number of entries is contained in the upsDiagPMEnclDoorFltrTableSize OID.
upsDiagPMEnclDoorFltrEntry entry .1.3.6.1.4.1.318.1.1.1.13.2.5.1
Power module door filter diagnostics info.
Indexes
upsDiagPMEnclIndex
Column Syntax OID
upsDiagPMEnclIndex mandatory
The index to the power module enclosure entry.
Enclosure 0 indicates the Power enclosure 1.
Enclosure 1 indicates the Power enclosure 2.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.5.1.1
upsDiagPMEnclDoorFltrLifetime mandatory
Door filter replacement time interval, based on the installation enivironment.
heavyFiltration15days (1) indicates door filter needs to be replaced within 15 days.
normalFiltration30days (2) indicates door filter needs …
Enumeration
Enumerated Values:
1heavyFiltration15days
2normalFiltration30days
3lightFiltration60days
4notPresent
.1.3.6.1.4.1.318.1.1.1.13.2.5.1.2
upsDiagPMEnclDoorFltrStatus mandatory
Indicates the current status of the door filter.
ok(1) indicates the device lifetime status is OK.
nearEnd(2) indicates the device lifetime status is near end.
exceeded(3) indicates the device lifetime status is exceede…
Enumeration
Enumerated Values:
1ok
2nearEnd
3exceeded
4unknown
.1.3.6.1.4.1.318.1.1.1.13.2.5.1.3
upsDiagPMEnclDoorFltrEstmtdLifetimeRmng mandatory
Displays the time remaining, measured in days, before the module door filter should be replaced.
This value is set when you originally install the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.5.1.4
upsDiagPMEnclDoorFltrEstmtdLifetimeRmngPct mandatory
Displays the percentage of the total lifetime remaining for the module
door filter before it should be replaced.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.2.5.1.5

upsDiagBatteryTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.13.3.2 · 1 row entry · 11 columns
Allows for diagnostics of individual batteries. The number of
entries is contained in the upsDiagBattTableSize OID.
upsDiagBatteryEntry entry .1.3.6.1.4.1.318.1.1.1.13.3.2.1
The diagnostics of a battery.
Indexes
upsDiagBatteryIndex
Column Syntax OID
upsDiagBatteryFrameIndex mandatory
The index to the battery frame entry.
Frame 0 indicates the Main frame. Extended Run (XR) frames
start from index 1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.1
upsDiagBatteryIndex mandatory
The index to the battery entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.2
upsDiagBatteryStatus mandatory
The status of the battery.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
ok(3) indicates the battery status is OK.
failed(4) indicates the battery status is fa…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3ok
4failed
5highTemperature
6replaceImmediately
7lowCapacity
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.3
upsDiagBatterySerialNumber mandatory
The serial number of the battery.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.4
upsDiagBatteryFirmwareRev mandatory
The firmware revision of the battery.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.5
upsDiagBatteryManufactureDate mandatory
The manufacture date of the battery.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.6
upsDiagBatteryType mandatory
The battery type or rating for the battery.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.7
upsDiagBatteryFramePresent mandatory
The battery frame/cabinet status.
0 indicates frame/cabinet is not present.
1 indicates frame/cabinet is present.
Enumeration
Enumerated Values:
0notPresent
1present
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.8
upsDiagBatteryFrameTemperature mandatory
The battery frame/cabinet temperature in tenths of degrees celsius.
If the frame/cabinet is not present, this variable is set to (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.9
upsDiagBatterySKU mandatory
The SKU of the battery.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.10
upsDiagBatteryHealth mandatory
The battery health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement module
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement …
OctetString .1.3.6.1.4.1.318.1.1.1.13.3.2.1.11
.1.3.6.1.4.1.318.1.1.1.13.3.4 · 1 row entry · 5 columns
Allows for diagnostics of individual battery frame. The number of
entries is contained in the upsDiagBatteryFrameTableSize OID.
upsDiagBatteryFrameEntry entry .1.3.6.1.4.1.318.1.1.1.13.3.4.1
The diagnostics of a battery frame.
Indexes
upsDiagBatteryFrameTableIndex
Column Syntax OID
upsDiagBatteryFrameTableIndex mandatory
The index to the battery frame entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.3.4.1.1
upsDiagBatteryModuleStatusPerFrame mandatory
An ASCII string containing the 64 flags representing
the status of battery modules. 1 indicates battery module installed,
0 indicates battery module not installed.

The flags are numbered from 1 to 64, and…
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.3.4.1.2
upsDiagBatteryPositiveVoltage mandatory
The battery positive voltage, in Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.3.4.1.3
upsDiagBatteryNegativeVoltage mandatory
The battery negative voltage, in Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.3.4.1.4
upsDiagBatteryTemperature mandatory
The battery frame/cabinet temperature in tenths of degrees celsius.
If the frame/cabinet is not present, this variable is set to (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.3.4.1.5
.1.3.6.1.4.1.318.1.1.1.13.4.2 · 1 row entry · 7 columns
Allows for diagnostics of individual XR Frames.
upsDiagSubSysFrameEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.2.1
The diagnostics of an XR Frame.
Indexes
upsDiagSubSysFrameIndex
Column Syntax OID
upsDiagSubSysFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.2.1.1
upsDiagSubSysFrameType mandatory
The type of Frame.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
frameTypeMain(3) indicates the frame type is the Main Frame.
frameTypeXR(4) indicates the fram…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3frameTypeMain
4frameTypeXR
5frameTypeLXR
.1.3.6.1.4.1.318.1.1.1.13.4.2.1.2
upsDiagSubSysFrameFirmwareRev mandatory
The firmware revision of the frame.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.2.1.3
upsDiagSubSysFrameHardwareRev mandatory
The hardware revision of the frame.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.2.1.4
upsDiagSubSysFrameSerialNum mandatory
The serial number of the frame.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.2.1.5
upsDiagSubSysFrameManufactureDate mandatory
The manufacture date of the frame.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.2.1.6
upsDiagSubSysFrameSKU mandatory
The SKU of the frame.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.2.1.7
.1.3.6.1.4.1.318.1.1.1.13.4.4 · 1 row entry · 10 columns
Allows for diagnostics of the Internal Bypass Switch.
upsDiagSubSysIntBypSwitchEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.4.1
The diagnostics of the Internal Bypass Switch.
Indexes
upsDiagSubSysIntBypSwitchIndex
Column Syntax OID
upsDiagSubSysIntBypSwitchFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.1
upsDiagSubSysIntBypSwitchIndex mandatory
The Internal Bypass Switch index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.2
upsDiagSubSysIntBypSwitchStatus mandatory
The Internal Bypass Switch status.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the devi…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.3
upsDiagSubSysIntBypSwitchFirmwareRev mandatory
The firmware revision of the Internal Bypass Switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.4
upsDiagSubSysIntBypSwitchHardwareRev mandatory
The hardware revision of the Internal Bypass Switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.5
upsDiagSubSysIntBypSwitchSerialNum mandatory
The serial number of the Internal Bypass Switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.6
upsDiagSubSysIntBypSwitchManufactureDate mandatory
The manufacture date of the Internal Bypass Switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.7
upsDiagSubSysIntBypSwitchModelNum mandatory
The model number of the Internal Bypass Switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.8
upsDiagSubSysIntBypFanSpeed optional
The average fan speed of the working fans in the Internal Bypass Switch in revolutions per minute (RPM).
Returns (-1) if not set.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.9
upsDiagSubSysIntBypAmbientTemperature optional
The ambient temperature in tenths of degrees celcius inside the Internal Bypass Switch.
If not available, this variable is set to (-1999).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.4.1.10
.1.3.6.1.4.1.318.1.1.1.13.4.6 · 1 row entry · 7 columns
Allows for diagnostics of the Battery Monitor Board.
upsDiagSubSysBattMonitorEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.6.1
The diagnostics of the Battery Monitor Board.
Indexes
upsDiagSubSysBattMonitorIndex
Column Syntax OID
upsDiagSubSysBattMonitorFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.6.1.1
upsDiagSubSysBattMonitorIndex mandatory
The index of the Battery Monitor Board.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.6.1.2
upsDiagSubSysBattMonitorStatus mandatory
The status of the Battery Monitor Board.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates th…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.6.1.3
upsDiagSubSysBattMonitorFirmwareRev mandatory
The firmware revision of the Battery Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.6.1.4
upsDiagSubSysBattMonitorHardwareRev mandatory
The hardware revision of the Battery Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.6.1.5
upsDiagSubSysBattMonitorSerialNum mandatory
The serial number of the Battery Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.6.1.6
upsDiagSubSysBattMonitorManufactureDate mandatory
The date of the manufacture for the Battery Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.6.1.7
.1.3.6.1.4.1.318.1.1.1.13.4.8 · 1 row entry · 8 columns
Allows for diagnostics of the individual External Switch Gear.
upsDiagSubSysExternalSwitchGearEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.8.1
The diagnostics of an individual External Switch Gear.
Indexes
upsDiagSubSysExternalSwitchGearIndex
Column Syntax OID
upsDiagSubSysExternalSwitchGearFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.8.1.1
upsDiagSubSysExternalSwitchGearIndex mandatory
The index of the External Switch Gear.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.8.1.2
upsDiagSubSysExternalSwitchGearStatus mandatory
The status of the External Switch Gear.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.8.1.3
upsDiagSubSysExternalSwitchGearFirmwareRev mandatory
The firmware revision of the External Switch Gear monitor card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.8.1.4
upsDiagSubSysExternalSwitchGearHardwareRev mandatory
The hardware revision of the External Switch Gear monitor card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.8.1.5
upsDiagSubSysExternalSwitchGearSerialNum mandatory
The serial number of the External Switch Gear monitor card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.8.1.6
upsDiagSubSysExternalSwitchGearManufactureDate mandatory
The date of the manufacture for the External Switch Gear monitor card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.8.1.7
upsDiagSubSysExternalSwitchGearTemperature mandatory
The temperature of the air around the External Switch
Gear monitor card in tenths of degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.8.1.8
.1.3.6.1.4.1.318.1.1.1.13.4.10 · 1 row entry · 3 columns
Allows for diagnostics of individual Display Interface Cards.
upsDiagSubSysDisplayInterfaceCardEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.10.1
The diagnostics of a Display Interface Card.
Indexes
upsDiagSubSysDisplayInterfaceCardIndex
Column Syntax OID
upsDiagSubSysDisplayInterfaceCardFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.10.1.1
upsDiagSubSysDisplayInterfaceCardIndex mandatory
The index of the Display Interface Card.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.10.1.2
upsDiagSubSysDisplayInterfaceCardStatus mandatory
The status of the Display Interface Card.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates t…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.10.1.3
.1.3.6.1.4.1.318.1.1.1.13.4.12 · 1 row entry · 3 columns
Allows for diagnostics of individual DC Circuit Breakers.
upsDiagSubSysDCCircuitBreakerEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.12.1
The diagnostics of a DC Circuit Breaker.
Indexes
upsDiagSubSysDCCircuitBreakerIndex
Column Syntax OID
upsDiagSubSysDCCircuitBreakerFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.12.1.1
upsDiagSubSysDCCircuitBreakerIndex mandatory
The index of the DC Circuit Breaker.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.12.1.2
upsDiagSubSysDCCircuitBreakerStatus mandatory
The status of the DC Circuit Breaker.
unknown(1) indicates the circuit breaker status is unknown.
notInstalled(2) indicates the circuit breaker is not installed.
opened(3) indicates the circuit breaker is opened.
closed…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3opened
4closed
.1.3.6.1.4.1.318.1.1.1.13.4.12.1.3
.1.3.6.1.4.1.318.1.1.1.13.4.14 · 1 row entry · 7 columns
Allows for diagnostics of individual System Power Supplies.
upsDiagSubSysSystemPowerSupplyEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.14.1
The diagnostics of a System Power Supply.
Indexes
upsDiagSubSysSystemPowerSupplyIndex
Column Syntax OID
upsDiagSubSysSystemPowerSupplyFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.14.1.1
upsDiagSubSysSystemPowerSupplyIndex mandatory
The index of a System Power Supply.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.14.1.2
upsDiagSubSysSystemPowerSupplyStatus mandatory
The status of the System Power Supply.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the …
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.14.1.3
upsDiagSubSysSystemPowerSupplyFirmwareRev mandatory
The firmware revision of the System Power Supply monitor card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.14.1.4
upsDiagSubSysSystemPowerSupplyHardwareRev mandatory
The hardware revision of the System Power Supply monitor card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.14.1.5
upsDiagSubSysSystemPowerSupplySerialNum mandatory
The serial number of the System Power Supply monitor card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.14.1.6
upsDiagSubSysSystemPowerSupplyManufactureDate mandatory
The date of the manufacture for the System Power Supply monitor card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.14.1.7
.1.3.6.1.4.1.318.1.1.1.13.4.16 · 1 row entry · 5 columns
Allows for diagnostics of individual XR Communication Cards.
upsDiagSubSysXRCommunicationCardEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.16.1
The diagnostics of an XR Communication Card.
Indexes
upsDiagSubSysXRCommunicationCardIndex
Column Syntax OID
upsDiagSubSysXRCommunicationCardFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.16.1.1
upsDiagSubSysXRCommunicationCardIndex mandatory
The index of an XR Communication Card.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.16.1.2
upsDiagSubSysXRCommunicationCardStatus mandatory
The status of the XR Communication Card.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates th…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.16.1.3
upsDiagSubSysXRCommunicationCardFirmwareRev mandatory
The firmware revision of the XR Communication card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.16.1.4
upsDiagSubSysXRCommunicationCardSerialNum mandatory
The serial number of the XR Communication card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.16.1.5
.1.3.6.1.4.1.318.1.1.1.13.4.18 · 1 row entry · 3 columns
Allows for diagnostics of individual External Power Frame Boards.
upsDiagSubSysExternalPowerFrameBoardEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.18.1
The diagnostics of an External Power Frame Board.
Indexes
upsDiagSubSysExternalPowerFrameBoardIndex
Column Syntax OID
upsDiagSubSysExternalPowerFrameBoardFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.18.1.1
upsDiagSubSysExternalPowerFrameBoardIndex mandatory
The index of an External Power Frame Board.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.18.1.2
upsDiagSubSysExternalPowerFrameBoardStatus mandatory
The status of the External Power Frame Board.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicat…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.18.1.3
.1.3.6.1.4.1.318.1.1.1.13.4.20 · 1 row entry · 3 columns
Allows for diagnostics of individual chargers.
upsDiagSubSysChargerEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.20.1
The diagnostics of a charger.
Indexes
upsDiagSubSysChargerIndex
Column Syntax OID
upsDiagSubSysChargerFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.20.1.1
upsDiagSubSysChargerIndex mandatory
The index of a charger.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.20.1.2
upsDiagSubSysChargerStatus mandatory
The status of the Charger.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the device statu…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.20.1.3
.1.3.6.1.4.1.318.1.1.1.13.4.22 · 1 row entry · 7 columns
Allows for diagnostics of individual Inverters.
upsDiagSubSysInverterEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.22.1
The diagnostics of an Inverter.
Indexes
upsDiagSubSysInverterIndex
Column Syntax OID
upsDiagSubSysInverterFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.22.1.1
upsDiagSubSysInverterIndex mandatory
The index of an Inverter.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.22.1.2
upsDiagSubSysInverterStatus mandatory
The status of the Inverter.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the device stat…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.22.1.3
upsDiagSubSysInverterFirmwareRev mandatory
The firmware revision of the Inverter monitor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.22.1.4
upsDiagSubSysInverterHardwareRev mandatory
The hardware revision of the Inverter monitor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.22.1.5
upsDiagSubSysInverterSerialNum mandatory
The serial number of the Inverter monitor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.22.1.6
upsDiagSubSysInverterManufactureDate mandatory
The date of manufacture for the Inverter monitor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.22.1.7
.1.3.6.1.4.1.318.1.1.1.13.4.24 · 1 row entry · 7 columns
Allows for diagnostics of individual PowerFactorCorrections.
upsDiagSubSysPowerFactorCorrectionEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.24.1
The diagnostics of a Power Factor Correction.
Indexes
upsDiagSubSysPowerFactorCorrectionIndex
Column Syntax OID
upsDiagSubSysPowerFactorCorrectionFrameIndex mandatory
The frame index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.24.1.1
upsDiagSubSysPowerFactorCorrectionIndex mandatory
The index of a Power Factor Correction.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.24.1.2
upsDiagSubSysPowerFactorCorrectionStatus mandatory
The status of the Power Factor Correction.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates …
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.24.1.3
upsDiagSubSysPowerFactorCorrectionFirmwareRev mandatory
The firmware revision of the Power Factor Correction monitor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.24.1.4
upsDiagSubSysPowerFactorCorrectionHardwareRev mandatory
The hardware revision of the Power Factor Correction monitor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.24.1.5
upsDiagSubSysPowerFactorCorrectionSerialNum mandatory
The serial number of the Power Factor Correction monitor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.24.1.6
upsDiagSubSysPowerFactorCorrectionManufactureDate mandatory
The date of the manufacture for the Power Factor Correction monitor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.24.1.7
.1.3.6.1.4.1.318.1.1.1.13.4.26 · 1 row entry · 7 columns
Allows for getting diagnostics information of an individual Network Communication Card.
upsDiagSubSysNetworkComCardEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.26.1
The diagnostics of a Network Communication Card.
Indexes
upsDiagSubSysNetworkComCardIndex
Column Syntax OID
upsDiagSubSysNetworkComCardIndex mandatory
The UPS network and display interface communication card index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.26.1.1
upsDiagSubSysNetworkComCardModelNumber mandatory
A character string identifying the model number of the UPS network and display interface communication card.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.26.1.2
upsDiagSubSysNetworkComCardSerialNumber mandatory
A character string identifying the serial number of the UPS network and display interface communication card.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.26.1.3
upsDiagSubSysNetworkComCardDateOfManufacture mandatory
The date when the UPS network and display interface communication card was manufactured in mm/dd/yyyy format.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.26.1.4
upsDiagSubSysNetworkComCardHardwareRev mandatory
The hardware revision of the UPS network and display interface communication card.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.26.1.5
upsDiagSubSysNetworkComCardFirmwareAppRev mandatory
An ID string identifying the application firmware revision of the
UPS network and display interface communication card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.26.1.6
upsDiagSubSysNetworkComCardFirmwareAppOSRev mandatory
An ID string identifying the application operating system firmware revision of the
UPS network and display interface communication card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.26.1.7
.1.3.6.1.4.1.318.1.1.1.13.4.28 · 1 row entry · 6 columns
Allows for diagnostics of the user supplied Battery Monitor Board.
upsDiagSubSysUsrSuppBattMonitorEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.28.1
The diagnostics of the user supplied Battery Monitor Board.
Indexes
upsDiagSubSysUsrSuppBattMonitorIndex
Column Syntax OID
upsDiagSubSysUsrSuppBattMonitorIndex mandatory
The index of the user supplied Battery Monitor Board.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.28.1.1
upsDiagSubSysUsrSuppBattMonitorStatus mandatory
The status of the user supplied Battery Monitor Board.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.28.1.2
upsDiagSubSysUsrSuppBattMonitorFirmwareRev mandatory
The firmware revision of the user supplied Battery Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.28.1.3
upsDiagSubSysUsrSuppBattMonitorHardwareRev mandatory
The hardware revision of the user supplied
Battery Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.28.1.4
upsDiagSubSysUsrSuppBattMonitorSerialNum mandatory
The serial number of the user supplied
Battery Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.28.1.5
upsDiagSubSysUsrSuppBattMonitorTemperature mandatory
The temperature of the air around the user supplied
Battery Monitor Board in tenths of degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.28.1.6

upsDiagSubSysPSUTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.13.4.31 · 1 row entry · 2 columns
Allows for diagnostics of individual Power Supply Units. The number of
entries is contained in the upsDiagSubSysPSUTableSize OID.
upsDiagSubSysPSUEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.31.1
The diagnostics information of a Power Supply Unit.
Indexes
upsDiagSubSysPSUIndex
Column Syntax OID
upsDiagSubSysPSUIndex mandatory
The index to the Power Supply Unit entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.31.1.1
upsDiagSubSysPSUStatus mandatory
The status of the Power Supply Unit.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the de…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.31.1.2

upsDiagSubSysIDRCTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.13.4.33 · 1 row entry · 5 columns
Allows for diagnostics of the ID and Relay Controller Card.
upsDiagSubSysIDRCEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.33.1
The diagnostics of the ID and Relay Controller Card.
Indexes
upsDiagSubSysIDRCIndex
Column Syntax OID
upsDiagSubSysIDRCIndex mandatory
The index of the ID and Relay Controller Card.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.33.1.1
upsDiagSubSysIDRCStatus mandatory
The status of the ID and Relay Controller Card.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indic…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.4.33.1.2
upsDiagSubSysIDRCFirmwareRev mandatory
The firmware revision of the ID and Relay Controller Card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.33.1.3
upsDiagSubSysIDRCHardwareRev mandatory
The hardware revision of the ID and Relay Controller Card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.33.1.4
upsDiagSubSysIDRCSerialNum mandatory
The serial number of the ID
and Relay Controller Card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.33.1.5
.1.3.6.1.4.1.318.1.1.1.13.4.36 · 1 row entry · 4 columns
Backfeed protection contactor table.
upsDiagSubSysBackfeedContactorEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.36.1
A list of backfeed protection contactors.
Indexes
upsDiagSubSysbackfeedContactorIndex
Column Syntax OID
upsDiagSubSysbackfeedContactorIndex mandatory
The index of the backfeed protection contactor.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.36.1.1
upsDiagSubSysbackfeedContactorName mandatory
The name of the backfeed protection contactor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.4.36.1.2
upsDiagSubSysbackfeedContactorType mandatory
Indicates the backfeed protection contactor types available in the UPS system.
If the UPS is unable to find any attached contactors, this variable
is set to unknown(1).
Enumeration
Enumerated Values:
1unknown
2normalAC
3bypassAC
.1.3.6.1.4.1.318.1.1.1.13.4.36.1.3
upsDiagSubSysbackfeedContactorStatus mandatory
The status of backfeed protection contactor.
unknown(1) indicates the contactor status is unknown.
opened (2) indicates the contactor is opened.
closed (3) indicates the contactor is closed.
Enumeration
Enumerated Values:
1unknown
2opened
3closed
.1.3.6.1.4.1.318.1.1.1.13.4.36.1.4
.1.3.6.1.4.1.318.1.1.1.13.4.38 · 1 row entry · 4 columns
Allows for diagnostics of the Internal Bypass Switch life time infomation.
upsDiagSubSysIntBypSwitchFanLifetimeInfoEntry entry .1.3.6.1.4.1.318.1.1.1.13.4.38.1
The diagnostics of the Internal Bypass Switch.
Indexes
upsDiagSubSysIntBypSwitchFanLifetimeInfoIndex
Column Syntax OID
upsDiagSubSysIntBypSwitchFanLifetimeInfoIndex mandatory
The index to the Internal Bypass Switch Fan liftime information entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.38.1.1
upsDiagSubSysIntBypSwitchFanLifetimeStatus mandatory
The status of the Internal Bypass Switch Fan lifetime information.
ok(1) indicates the device lifetime status is OK.
nearEnd(2) indicates the device lifetime status is near end.
exceeded(3) indicates the device lifetime…
Enumeration
Enumerated Values:
1ok
2nearEnd
3exceeded
4unknown
.1.3.6.1.4.1.318.1.1.1.13.4.38.1.2
upsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmng mandatory
Displays the time remaining for the module before it should be replaced.
Measured in months. This value is set when you originally install the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.38.1.3
upsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmngPct mandatory
Displays the percentage of the total lifetime remaining for the module
before it should be replaced.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.4.38.1.4
.1.3.6.1.4.1.318.1.1.1.13.5.1.7 · 1 row entry · 5 columns
Switchgear breaker table.
upsDiagSwitchGearBreakerEntry entry .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1
A list of switchgear breakers.
Indexes
switchgearBreakerIndex
Column Syntax OID
switchgearBreakerIndex mandatory
The index of the switchgear breaker.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.1
switchgearBreakerPresent mandatory
Indicates if the switchgear breaker is present.
notPresent(1) indicates that the breaker is not present.
present(2) indicates that the breaker is present.
Enumeration
Enumerated Values:
1notPresent
2present
.1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.2
switchgearBreakerName mandatory
The name of the switchgear breaker.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.3
switchgearBreakerType mandatory
Indicates the switchgear breaker types available in the UPS system.
If the UPS is unable to find any attached breakers, this variable
is set to unknown(1). If the system has multiple breakers of the same
type (e.g. mul…
Enumeration
Enumerated Values:
1unknown
2unitInputBreaker
3staticSwitchInputBreaker
4maintenanceBypassBreaker
5unitOutputBreaker
6systemIsolationBreaker
7batteryBreaker
8bypassBackFeedBreaker
9internalMaintenanceBypassBreaker
10redundantInternalMaintenanceBypassBreaker
.1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.4
switchgearBreakerStatus mandatory
The status of switchgear breaker.
unknown(1) indicates the breaker status is unknown.
opened (2) indicates the breaker is opened.
closed (3) indicates the breaker is closed.
NOTE: If there are more than one breaker of t…
Enumeration
Enumerated Values:
1unknown
2opened
3closed
.1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.5
.1.3.6.1.4.1.318.1.1.1.13.5.1.9 · 1 row entry · 8 columns
Subfeed breaker table.
upsDiagSubFeedBreakerEntry entry .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1
A list of subfeed breakers.
Indexes
subfeedBreakerIndex
Column Syntax OID
subfeedBreakerIndex mandatory
The index of the subfeed breakers.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.1
subfeedBreakerPresent mandatory
Indicates if the subfeed breaker is present.
notPresent (1) indicates that the breaker is not present.
present (2) indicates that the breaker is present.
Enumeration
Enumerated Values:
1notPresent
2present
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.2
subfeedBreakerRating mandatory
The current rating of the installed subfeed breaker.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.3
subfeedBreakerUpperAcceptPowerWarning mandatory
The maximum acceptable load before warning is issued.
Expressed as percent of the subfeed breaker rating.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.4
subfeedBreakerUpperAcceptPowerCritical mandatory
The maximum load before a critical alarm occurs.
Expressed as percent of the subfeed breaker rating.
Integer32r/w
Constraints:
range: 0-125
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.5
subfeedBreakerStatus mandatory
The status of the Circuit Breaker.
unknown(1) indicates the circuit breaker status is unknown.
notInstalled(2) indicates the circuit breaker is not installed.
opened(3) indicates the circuit breaker is opened.
closed(4)…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3opened
4closed
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.6
subfeedBreakerName mandatory
The name of the subfeed breaker.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.7
subfeedBreakerCurrent mandatory
The subfeed current in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.8
.1.3.6.1.4.1.318.1.1.1.13.5.1.11 · 1 row entry · 4 columns
A list of subfeed phase table.
upsDiagSubFeedPhaseEntry entry .1.3.6.1.4.1.318.1.1.1.13.5.1.11.1
An entry containing information applicable to a
particular phase.
Indexes
upsDiagSubFeedPhaseIndex
Column Syntax OID
upsDiagSubFeedBreakerIndex mandatory
The subfeed breaker index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.1
upsDiagSubFeedPhaseIndex mandatory
The subfeed phase index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.2
upsDiagSubFeedPhaseCurrent mandatory
The subfeed phase current in Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.3
upsDiagSubFeedPhaseCurrentAlternate mandatory
The subfeed phase current in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.4
.1.3.6.1.4.1.318.1.1.1.13.5.1.15 · 1 row entry · 6 columns
Allows for diagnostics of the user supplied Switch Gear Monitor Board.
upsDiagUsrSuppSwitchgearMonitorEntry entry .1.3.6.1.4.1.318.1.1.1.13.5.1.15.1
The diagnostics of the user supplied Switch Gear Monitor Board.
Indexes
upsDiagUsrSuppSwitchgearMonitorIndex
Column Syntax OID
upsDiagUsrSuppSwitchgearMonitorIndex mandatory
The index of the user supplied Switch Gear Monitor Board.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.1
upsDiagUsrSuppSwitchgearMonitorStatus mandatory
The status of the user supplied Switch Gear Monitor Board.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
on…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.2
upsDiagUsrSuppSwitchgearMonitorFirmwareRev mandatory
The firmware revision of the user supplied Switch Gear Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.3
upsDiagUsrSuppSwitchgearMonitorHardwareRev mandatory
The hardware revision of the user supplied Switch Gear Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.4
upsDiagUsrSuppSwitchgearMonitorSerialNum mandatory
The serial number of the user supplied
Switch Gear Monitor Board.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.5
upsDiagUsrSuppSwitchgearMonitorTemperature mandatory
The temperature of the air around the user supplied
Switch Gear Monitor Board in tenths of degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.6
.1.3.6.1.4.1.318.1.1.1.13.7.2 · 1 row entry · 2 columns
Allows for diagnostics of individual Power Cabinets.
The number of entries is contained in the upsDiagnosticPowerCabinetTableSize OID.
upsDiagnosticPowerCabinetEntry entry .1.3.6.1.4.1.318.1.1.1.13.7.2.1
The diagnostics of a Power Cabinet.
Indexes
upsDiagnosticPowerCabinetIndex
Column Syntax OID
upsDiagnosticPowerCabinetIndex mandatory
The index to the Power Cabinet.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.7.2.1.1
upsDiagnosticPowerCabinetAmbientTemperature mandatory
The ambient temperature of Power Cabinet in tenths of degrees Celsius.
If the Power Cabinet is not present, this variable is set to (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.7.2.1.2
.1.3.6.1.4.1.318.1.1.1.13.9.2 · 1 row entry · 6 columns
Allows for diagnostics of individual Intelligence Modules. The number of
entries is contained in the upsDiagUnitControllerTableSize OID.
upsDiagUnitControllerEntry entry .1.3.6.1.4.1.318.1.1.1.13.9.2.1
The diagnostics and information of an Intelligence Module.
Indexes
upsDiagUnitControllerIndex
Column Syntax OID
upsDiagUnitControllerIndex mandatory
The index to the Unit Controller entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.13.9.2.1.1
upsDiagUnitControllerStatus mandatory
The status of the Unit Controller.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
offOk(3) indicates the device status is off and OK.
onOk(4) indicates the devi…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3offOk
4onOk
5offFail
6onFail
7lostComm
.1.3.6.1.4.1.318.1.1.1.13.9.2.1.2
upsDiagUnitControllerFirmwareRev mandatory
The firmware revision of the Unit Controller.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.9.2.1.3
upsDiagUnitControllerHardwareRev mandatory
The hardware revision of the Unit Controller.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.9.2.1.4
upsDiagUnitControllerSerialNum mandatory
The serial number of the Unit Controller.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.9.2.1.5
upsDiagUnitControllerModelNum mandatory
The model number of the Unit Controller.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.13.9.2.1.6
.1.3.6.1.4.1.318.1.1.1.14.7 · 1 row entry · 10 columns
A list of input table entries.
upsParallelInputPhaseEntry entry .1.3.6.1.4.1.318.1.1.1.14.7.1
An entry containing information applicable to a
particular input phase.
Indexes
upsParallelInputPhaseTableIndex upsParallelInputPhaseIndex
Column Syntax OID
upsParallelInputPhaseTableIndex mandatory
The parallel unit identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.1
upsParallelInputPhaseIndex mandatory
The input phase identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.2
upsParallelInputCurrent mandatory
The input current in amperes, or -1 if it's
unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.3
upsParallelInputActivePower mandatory
The input power in kW, or -1 if it's
unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.4
upsParallelInputApparentPower mandatory
The input apparent power in kVA, or -1 if it's
unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.5
upsParallelInputVoltage mandatory
The input voltage of UPS in volts, or -1 if it's
unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.6
upsParallelInputMaxVoltage mandatory
The peak input voltage in VAC measured since the last reset,
or -1 if it's unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.7
upsParallelInputMaxCurrent mandatory
The peak input current in amperes measured since last reset,
or -1 if it's unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.8
upsParallelInputTotalActivePower mandatory
Total active input power of the parallel system in kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.9
upsParallelInputTotalApparentPower mandatory
Total apparent input power of the parallel system in kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.7.1.10
.1.3.6.1.4.1.318.1.1.1.14.8 · 1 row entry · 6 columns
A list of output table entries.  The number of
entries is given by the sum of the upsPhaseNumOutputPhases.
upsParallelOutputPhaseEntry entry .1.3.6.1.4.1.318.1.1.1.14.8.1
An entry containing information applicable to a
particular output phase.
Indexes
upsParallelOutputPhaseTableIndex upsParallelOutputPhaseIndex
Column Syntax OID
upsParallelOutputPhaseTableIndex mandatory
The output identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.8.1.1
upsParallelOutputPhaseIndex mandatory
The output phase identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.8.1.2
upsParallelOutputCurrent mandatory
The output current in amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.8.1.3
upsParallelOutputLoad mandatory
The output load in VA, or -1 if it's unsupported
by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.8.1.4
upsParallelOutputPercentLoad mandatory
The percentage of the UPS load capacity in VA at
present redundancy being used on this output phase,
or -1 if it's unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.8.1.5
upsParallelOutputPower mandatory
The output power in Watts, or -1 if it's
unsupported by this UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.8.1.6
.1.3.6.1.4.1.318.1.1.1.14.9 · 1 row entry · 2 columns
A list of output table entries.  The number of entries
is given by the value of upsOutputNumPhases.
upsParallelOutputApparentPowerEntry entry .1.3.6.1.4.1.318.1.1.1.14.9.1
An entry containing information applicable to a
particular output.
Indexes
upsParallelOutputApparentPowerTableIndex
Column Syntax OID
upsParallelOutputApparentPowerTableIndex mandatory
The UPS parallel output identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.9.1.1
upsParallelOutputApparentPower mandatory
The apparent power of each of UPS in kVA
when UPS are configured in parallel.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.9.1.2
.1.3.6.1.4.1.318.1.1.1.14.10 · 1 row entry · 4 columns
Allows for diagnostics of parallel Circuit Breakers.
upsParallelDiagSubSysBreakerEntry entry .1.3.6.1.4.1.318.1.1.1.14.10.1
The diagnostics of Circuit Breaker.
Indexes
upsParallelDiagSubSysBreakerFrameIndex upsParallelDiagSubSysBreakerIndex
Column Syntax OID
upsParallelDiagSubSysBreakerFrameIndex mandatory
The Parallel UPS index entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.10.1.1
upsParallelDiagSubSysBreakerIndex mandatory
The index of the Circuit Breaker.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.10.1.2
upsParallelDiagSubSysBreakerStatus mandatory
The status of the Circuit Breaker.
unknown(1) indicates the circuit breaker status is unknown.
notInstalled(2) indicates the circuit breaker is not installed.
opened(3) indicates the circuit breaker is opened.
closed(4)…
Enumeration
Enumerated Values:
1unknown
2notInstalled
3opened
4closed
.1.3.6.1.4.1.318.1.1.1.14.10.1.3
upsParallelDiagSubSysBreakerName mandatory
The name of Circuit Breaker.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.14.10.1.4
.1.3.6.1.4.1.318.1.1.1.14.12 · 1 row entry · 2 columns
A list of output table entries.  The number of entries
is given by the value of upsParallelSysRemoteAddress.
upsParallelOutputActivePowerEntry entry .1.3.6.1.4.1.318.1.1.1.14.12.1
An entry containing information applicable to a
particular output.
Indexes
upsParallelOutputActivePowerTableIndex
Column Syntax OID
upsParallelOutputActivePowerTableIndex mandatory
The UPS parallel output identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.12.1.1
upsParallelOutputActivePower mandatory
The active power of each UPS in kW
when UPS devices are configured in parallel.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.12.1.2

upsParallelSysUpsTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.14.17 · 1 row entry · 5 columns
A list of UPS table entries.  The number of entries
is given by the value of upsParallelSysUpsTableize.
upsParallelSysUpsEntry entry .1.3.6.1.4.1.318.1.1.1.14.17.1
An entry containing information applicable to a
particular UPS in parallel.
Indexes
upsParallelSysUpsIndex
Column Syntax OID
upsParallelSysUpsIndex mandatory
The index to the Parallel System UPS table entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.14.17.1.1
upsParallelSysUpsName mandatory
The UPS id as assigned by the system.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.14.17.1.2
upsParallelSysUpsAlarmStatus mandatory
The alarm status of the UPS.
unknown(1) indicates the UPS status is unknown.
normal(2) indicates UPS is functioning normally.
informational(3) indicates informational alarm present in the UPS.
warning(4) indicates warni…
Enumeration
Enumerated Values:
1unknown
2normal
3informational
4warning
5critical
.1.3.6.1.4.1.318.1.1.1.14.17.1.3
upsParallelSysUpsMode mandatory
The current operating mode of the UPS. If the UPS is unable to
determine the state of the UPS, this variable is set
to unknown(1).
Enumeration
Enumerated Values:
1unknown
2onLine
3onBattery
4onBatteryTest
5requestedStaticBypass
6forcedBypass
7maintenanceBypass
8off
9ecoMode
10hotStandby
11inquiring
.1.3.6.1.4.1.318.1.1.1.14.17.1.4
upsParallelSysUpsSerialNumber mandatory
The Serial number of the UPS in parallel.
Equivalent to OID 1.3.6.1.4.1.318.1.1.1.1.2.3 (upsAdvIdentSerialNumber).
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.14.17.1.5
.1.3.6.1.4.1.318.1.1.1.15.5 · 1 row entry · 2 columns
Battery frame layout position ID table.
upsBatteryFrameLayoutEntry entry .1.3.6.1.4.1.318.1.1.1.15.5.1
A list of layout position IDs of battery frames.
Indexes
batteryFrameIndex
Column Syntax OID
batteryFrameIndex mandatory
The index of the battery frame.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.15.5.1.1
batteryFramePositionID mandatory
Defines the position ID of each of the battery frames in the row.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.15.5.1.2
.1.3.6.1.4.1.318.1.1.1.15.7 · 1 row entry · 2 columns
Sidecar frame layout position ID table.
upsSideCarFrameLayoutEntry entry .1.3.6.1.4.1.318.1.1.1.15.7.1
A list of sidecar frame layout position IDs.
Indexes
sideCarFrameIndex
Column Syntax OID
sideCarFrameIndex mandatory
The index of the sidecar frame.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.15.7.1.1
sideCarFramePositionID mandatory
Defines the position ID of each of the sidecar frames in the row.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.15.7.1.2
.1.3.6.1.4.1.318.1.1.1.15.9 · 1 row entry · 2 columns
Power frame layout position ID table.
upsPowerFrameLayoutEntry entry .1.3.6.1.4.1.318.1.1.1.15.9.1
A list of power frame layout position IDs.
Indexes
powerFrameIndex
Column Syntax OID
powerFrameIndex mandatory
The index of the power frame.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.15.9.1.1
powerFramePositionID mandatory
Defines the position ID of each of the power frames in the row.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.15.9.1.2
.1.3.6.1.4.1.318.1.1.1.16.5 · 1 row entry · 5 columns
Allows for getting status and settings for the ATS input sources.
The number of entries is contained in the upsIntegratedATSSourceTableSize OID.
upsIntegratedATSSourceEntry entry .1.3.6.1.4.1.318.1.1.1.16.5.1
The input source status to get.
Indexes
upsIntegratedATSSourceIndex
Column Syntax OID
upsIntegratedATSSourceIndex mandatory
The index to the input source entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.16.5.1.1
upsIntegratedATSSourceName mandatory
The name of the input source. This OID is provided
for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.16.5.1.2
upsIntegratedATSSourceStatus mandatory
Getting this variable will return the input source status.
Enumeration
Enumerated Values:
1upsIntegratedATSSourceGood
2upsIntegratedATSSourceBad
3upsIntegratedATSSourceUnknown
.1.3.6.1.4.1.318.1.1.1.16.5.1.3
upsIntegratedATSLineFailDelay mandatory
The delay between a selected input source becoming bad, and the ATS switching away from that source.
This delay is used to make sure that the line has truly failed before the ATS will be switched.
Specified in seconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.16.5.1.4
upsIntegratedATSLineStabilityDelay mandatory
The delay between an unselected input source becoming good, and the ATS switching to that source.
This delay is used to make sure that the line has truly returned before the ATS will be switched.
Specified in seconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.16.5.1.5

upsDCOutputStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.1.17.1.2 · 1 row entry · 6 columns
Provides status information on UPS DC outputs.
The number of entries is contained in the upsDCOutputStatusTableSize OID.
upsDCOutputStatusEntry entry .1.3.6.1.4.1.318.1.1.1.17.1.2.1
The DC output.
Indexes
upsDCOutputStatusTableIndex
Column Syntax OID
upsDCOutputStatusTableIndex mandatory
The index to the DC output status entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.17.1.2.1.1
upsDCOutputStatusVoltageNominal mandatory
The desired voltage for this output in tenths of VDC.
When the output is on and there are no fault conditions,
the actual voltage should be near the nominal.
If not supported, return -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.17.1.2.1.2
upsDCOutputStatusCurrentRating mandatory
The amount of current this output is able to supply in
tenths of amperes.
If not supported, return -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.17.1.2.1.3
upsDCOutputStatusVoltage mandatory
The voltage measured on this output in tenths of VDC.
If not supported, return -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.17.1.2.1.4
upsDCOutputStatusCurrent mandatory
The current drawn by the load measured on this output
in tenths of amperes.
If not supported, return -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.17.1.2.1.5
upsDCOutputStatusAbnormalConditions mandatory
An ASCII string containing flags representing active
output faults. If the Network Card is unable to determine
the state of the faults, this variable is set to 'UNKNOWN'.

The flags are numbered 1 onward, …
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.17.1.2.1.6
.1.3.6.1.4.1.318.1.1.1.18.1.2 · 1 row entry · 3 columns
Allows for access of individual relays.
upsOutputRelayStatusEntry entry .1.3.6.1.4.1.318.1.1.1.18.1.2.1
The output relays to access.
Indexes
upsOutputRelayIndex
Column Syntax OID
upsOutputRelayIndex mandatory
The index to the output relay entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.18.1.2.1.1
upsOutputRelayState mandatory
Getting this variable will return the output relay state.
1 - normal state
2 - abnormal state
Enumeration
Enumerated Values:
1outputRelayNormalState
2outputRelayAbnormalState
.1.3.6.1.4.1.318.1.1.1.18.1.2.1.2
upsOutputRelayDetailedStatus mandatory
An ASCII string containing the 16 flags representing
the status of the output relay.

The flags are numbered from 1 to 16, and read from left
to right. The bits are defined as follows:

Flag …
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.1.18.1.2.1.3
.1.3.6.1.4.1.318.1.1.1.18.1.4 · 1 row entry · 3 columns
Allows for access of individual relays.
upsOutputRelayConfigEntry entry .1.3.6.1.4.1.318.1.1.1.18.1.4.1
The output relays to access.
Indexes
upsOutputRelayConfigIndex
Column Syntax OID
upsOutputRelayConfigIndex mandatory
The index to the output relay entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.18.1.4.1.1
upsOutputRelayConfigDelay mandatory
Output relay delay 0 - 86400 seconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.18.1.4.1.2
upsOutputRelayConfigCause mandatory
This variable sets what causes the output relay state to change.
1 - none
2 - on battery power failure
3 - on battery power failure expect during peak period
4 - low battery while on battery
5 - alarm
6 - fault
7 - outp…
Enumerationr/w
Enumerated Values:
1outputRelayConfigCauseNone
2outputRelayConfigCauseOnBatPwrFail
3outputRelayConfigCauseOnBatPwrFailExceptPeakPeriod
4outputRelayConfigCauseLoBatWhileOnBat
5outputRelayConfigCauseAlarm
6outputRelayConfigCauseFault
7outputRelayConfigCauseOutputOn
8outputRelayConfigCauseOutputOff
9outputRelayConfigCauseOnline
10outputRelayConfigCauseInBypass
.1.3.6.1.4.1.318.1.1.1.18.1.4.1.3
.1.3.6.1.4.1.318.1.1.1.18.2.2 · 1 row entry · 2 columns
Allows for access of individual contacts.
upsInputContactStatusEntry entry .1.3.6.1.4.1.318.1.1.1.18.2.2.1
The input contacts to access.
Indexes
upsInputContactIndex
Column Syntax OID
upsInputContactIndex mandatory
The index to the input contact entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.18.2.2.1.1
upsInputContactState mandatory
Getting this variable will return the input contact state.
1 - normal state
2 - abnormal state
Enumeration
Enumerated Values:
1upsInputContactNormalState
2upsInputContactAbnormalState
.1.3.6.1.4.1.318.1.1.1.18.2.2.1.2
.1.3.6.1.4.1.318.1.1.1.18.2.4 · 1 row entry · 2 columns
Allows for access of individual contacts.
upsInputContactConfigEntry entry .1.3.6.1.4.1.318.1.1.1.18.2.4.1
The input contacts to access.
Indexes
upsInputContactConfigIndex
Column Syntax OID
upsInputContactConfigIndex mandatory
The index to the input contact entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.1.18.2.4.1.1
upsInputContactConfigAction mandatory
When the input contact changes state, this action occurs.
1 - none
2 - self test
3 - external alarm on
4 - external alarm off
5 - output off no delay
6 - output on
Enumerationr/w
Enumerated Values:
1upsInputContactConfigActionNone
2upsInputContactConfigActionSelfTest
3upsInputContactConfigActionExternalAlarmOn
4upsInputContactConfigActionExternalAlarmOff
5upsInputContactConfigActionOutputOffNoDelay
6upsInputContactConfigActionOutputOn
.1.3.6.1.4.1.318.1.1.1.18.2.4.1.2

mUpsContactTable

table mandatory
.1.3.6.1.4.1.318.1.1.2.2.2 · 1 row entry · 5 columns
A list of contacts supported by the Measure-UPS.
mUpsContactEntry entry .1.3.6.1.4.1.318.1.1.2.2.2.1
A contact entry containing information for a given contact.
Indexes
contactNumber
Column Syntax OID
contactNumber mandatory
An index identifying the contact on the Measure-UPS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.2.2.2.1.1
normalState mandatory
The normal operating position of the contact. If the normal
operating position cannot be set then it is controlled via the
dip switch on the Measure-UPS and is therefore read-only.
Enumerationr/w
Enumerated Values:
1unknown
2open
3closed
.1.3.6.1.4.1.318.1.1.2.2.2.1.2
description mandatory
The description of the purpose/use of the contact.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.2.2.2.1.3
monitoringStatus mandatory
A flag indicating whether this contact is
monitored, or not.
Enumerationr/w
Enumerated Values:
1unknown
2enabled
3disabled
.1.3.6.1.4.1.318.1.1.2.2.2.1.4
currentStatus mandatory
This value indicates the current state of the contact.
If the contact is not in its normal state. This value
is set to fault(2).
Enumeration
Enumerated Values:
1unknown
2noFault
3fault
.1.3.6.1.4.1.318.1.1.2.2.2.1.5

sPDUOutletControlTable

table mandatory
.1.3.6.1.4.1.318.1.1.4.4.2 · 1 row entry · 4 columns
Allows for control of individual outlet switches. The number of
entries is contained in the sPDUOutletControlTableSize OID.
sPDUOutletControlEntry entry .1.3.6.1.4.1.318.1.1.4.4.2.1
The outlets to control.
Indexes
sPDUOutletControlIndex
Column Syntax OID
sPDUOutletControlIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.4.4.2.1.1
sPDUOutletPending mandatory
Reports whether the current outlet has a pending command.

If the commandPendingUnknown (3) value is returned, all
devices powered by the PDU should be shut down. The PDU's
power should then be cycled to c…
Enumeration
Enumerated Values:
1commandPending
2noCommandPending
3commandPendingUnknown
.1.3.6.1.4.1.318.1.1.4.4.2.1.2
sPDUOutletCtl mandatory
Getting this variable will return the outlet state. If
the outlet is on, the outletOn (1) value will be returned.
If the outlet is off, the outletOff (2) value will be
returned.

If the state of the outlet…
Enumerationr/w
Enumerated Values:
1outletOn
2outletOff
3outletReboot
4outletUnknown
5outletOnWithDelay
6outletOffWithDelay
7outletRebootWithDelay
.1.3.6.1.4.1.318.1.1.4.4.2.1.3
sPDUOutletCtlName mandatory
The name of the outlet. Maximum size is 20 characters.
This OID is provided for informational purposes only.
This value is set by the sPDUOutletName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.4.4.2.1.4

sPDUOutletConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.4.5.2 · 1 row entry · 5 columns
The list of outlets to configure. The number of
entries is defined by the sPDUOutletConfigTableSize
OID.
sPDUOutletConfigEntry entry .1.3.6.1.4.1.318.1.1.4.5.2.1
The outlets to control.
Indexes
sPDUOutletConfigIndex
Column Syntax OID
sPDUOutletConfigIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.4.5.2.1.1
sPDUOutletPowerOnTime mandatory
The amount of time (in seconds) the outlet will delay
powering on when the MasterSwitch is powered on.

Allowed values are:

-1 never power on automatically.
0 power on with the Master Switc…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.4.5.2.1.2
sPDUOutletName mandatory
The name of the outlet. Maximum size is 20 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.4.5.2.1.3
sPDUOutletPowerOffTime mandatory
The amount of time (in seconds) the outlet will delay
powering off.

Allowed values are:

-1 never power off automatically.
0 power off with the MasterSwitch.
15 power off 15 seconds after b…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.4.5.2.1.4
sPDUOutletRebootDuration mandatory
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence, before turning power back on, at the
en…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.4.5.2.1.5

sPDUIdentVMTable

table mandatory
.1.3.6.1.4.1.318.1.1.5.1.2 · 1 row entry · 7 columns
Allows for query of the individual MasterSwitch VMs.
The number of entries is contained in the
sPDUIdentVMTableSize OID.
sPDUIdentVMEntry entry .1.3.6.1.4.1.318.1.1.5.1.2.1
The MasterSwitch VMs to query.
Indexes
sPDUIdentVMIndex
Column Syntax OID
sPDUIdentVMIndex mandatory
The index to the MasterSwitch VM entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.1.2.1.1
sPDUIdentNameVM mandatory
A 23-character string identifying the
MasterSwitch VM.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.1.2.1.2
sPDUIdentHardwareRevVM mandatory
The hardware version of the MasterSwitch VM.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.1.2.1.3
sPDUIdentFirmwareRevVM mandatory
An 6-character ID string identifying the MasterSwitch VM
firmware version. This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.1.2.1.4
sPDUIdentDateOfManufactureVM mandatory
The date when the MasterSwitch VM was manufactured in mm/dd/yyyy format.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.1.2.1.5
sPDUIdentModelNumberVM mandatory
A 17-character string identifying the model number of
the MasterSwitch VM. This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.1.2.1.6
sPDUIdentSerialNumberVM mandatory
A 17-character string identifying the serial number of
the MasterSwitch VM. This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.1.2.1.7
.1.3.6.1.4.1.318.1.1.5.2.2 · 1 row entry · 3 columns
Allows for control of the individual MasterSwitch VMs.
The number of entries is contained in the
sPDUMasterControlVMTableSize OID.
sPDUMasterControlVMEntry entry .1.3.6.1.4.1.318.1.1.5.2.2.1
The MasterSwitch VMs to control.
Indexes
sPDUMasterControlVMIndex
Column Syntax OID
sPDUMasterControlVMIndex mandatory
The index to the MasterSwitch VM entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.2.2.1.1
sPDUMasterControlVMName mandatory
The name of the MasterSwitch VM. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigVMName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.2.2.1.2
sPDUMasterControlVMCommand mandatory
Setting this OID to immediateAllOnVM (2) will turn all outlets
on immediately.

Setting this OID to immediateAllOffVM (3) will turn all outlets
off immediately.

Setting this OID to immediate…
Enumerationr/w
Enumerated Values:
1noCommandAllVM
2immediateAllOnVM
3immediateAllOffVM
4immediateAllRebootVM
5delayedAllOnVM
6delayedAllOffVM
7sequencedAllRebootVM
8delayedAllRebootVM
9delayedSequenceAllRebootVM
10cancelAllPendingCommandsVM
11audioAlarmMute
.1.3.6.1.4.1.318.1.1.5.2.2.1.3
.1.3.6.1.4.1.318.1.1.5.3.2 · 1 row entry · 7 columns
Allows for configuration of the individual MasterSwitch VMs.
The number of entries is contained in the
sPDUMasterConfigVMTableSize OID.
sPDUMasterConfigVMEntry entry .1.3.6.1.4.1.318.1.1.5.3.2.1
The MasterSwitch VMs to configure.
Indexes
sPDUMasterConfigVMIndex
Column Syntax OID
sPDUMasterConfigVMIndex mandatory
The index to the MasterSwitch VM entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.3.2.1.1
sPDUMasterConfigVMName mandatory
The name of the MasterSwitch VM. Maximum size is 23 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.3.2.1.2
sPDUMasterConfigVMColdstartDelay mandatory
The amount of delay, in seconds, between when
power is provided to the MasterSwitch VM and
when the MasterSwitch VM provides basic master
power to the outlets.

Allowed values are:

-1 never …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.3.2.1.3
sPDUMasterConfigVMAudioAlarmActivated mandatory
Setting this OID to audioAlarmActiveNever (1) will disable
the audio alarm on the MasterSwitch VM.

Setting this OID to audioAlarmActiveOnOverload (2) will
activate the audio alarm on the MasterSwitch VM w…
Enumerationr/w
Enumerated Values:
1audioAlarmActiveNever
2audioAlarmActiveOnOverload
3audioAlarmActiveOnOverloadImminent
.1.3.6.1.4.1.318.1.1.5.3.2.1.4
sPDUMasterConfigVMHighLoadWarningThreshold mandatory
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented as a percentage of full load.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.5.3.2.1.5
sPDUMasterConfigVMLowLoadWarningThreshold mandatory
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented as a percentage of full load.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.5.3.2.1.6
sPDUMasterConfigVMOverloadRestriction mandatory
This OID controls the behavior of the MasterSwitch VM
when an overload condition is possible and additional
outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will always all…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnWarning
3restrictOnOverload
.1.3.6.1.4.1.318.1.1.5.3.2.1.7
.1.3.6.1.4.1.318.1.1.5.4.2 · 1 row entry · 9 columns
Allows for gathering of status from the individual
MasterSwitch VMs. The number of entries is contained
in the sPDUMasterStatusVMTableSize OID.
sPDUMasterStatusVMEntry entry .1.3.6.1.4.1.318.1.1.5.4.2.1
The MasterSwitch VMs to gather status from.
Indexes
sPDUMasterStatusVMIndex
Column Syntax OID
sPDUMasterStatusVMIndex mandatory
The index to the MasterSwitch VM entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.4.2.1.1
sPDUMasterStatusVMName mandatory
The name of the MasterSwitch VM. Maximum size is 23 characters.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.4.2.1.2
sPDUMasterStatusVMCommandPending mandatory
Getting this OID will return commandPendingMasterTrueVM (1)
if the MasterSwitch VM has a pending command on any of its
outlets.

commandPendingMasterFalseVM (2) will be returned if there are
no pending com…
Enumeration
Enumerated Values:
1commandPendingMasterTrueVM
2commandPendingMasterFalseVM
.1.3.6.1.4.1.318.1.1.5.4.2.1.3
sPDUMasterStatusVMOverloadCondition mandatory
Getting this OID will return overloadConditionTrueVM (1)
if the sPDUMasterConfigVMHighLoadWarningThreshold OID is
violated.

overloadConditionFalseVM (2) will be returned if the
sPDUMasterConfigVMHighLoadW…
Enumeration
Enumerated Values:
1overloadConditionTrueVM
2overloadConditionFalseVM
.1.3.6.1.4.1.318.1.1.5.4.2.1.4
sPDUMasterStatusVMLowLoadCondition mandatory
Getting this OID will return lowLoadConditionTrueVM (1)
if the sPDUMasterConfigVMLowLoadWarningThreshold OID is
violated.

lowLoadConditionFalseVM (2) will be returned if the
sPDUMasterConfigVMHighLoadWarn…
Enumeration
Enumerated Values:
1lowLoadConditionTrueVM
2lowLoadConditionFalseVM
.1.3.6.1.4.1.318.1.1.5.4.2.1.5
sPDUMasterStatusVMCurrentLoad mandatory
Getting this OID will return the total amount of power
being consumed by the load. It is represented as a
percentage of full load.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.4.2.1.6
sPDUMasterStatusVMMaxLoad mandatory
Getting this OID will return the total amount of power
that this MasterSwitch VM can provide. It is represented
in Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.4.2.1.7
sPDUMasterStatusVMOutletCount mandatory
Getting this OID will return the number of controllable
outlets for this MasterSwitch VM.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.4.2.1.8
sPDUMasterStatusVMRebootDuration mandatory
Getting this OID will return the largest
sPDUOutletConfigVMRebootDuration OID time
for this MasterSwitch VM.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.4.2.1.9
.1.3.6.1.4.1.318.1.1.5.5.1 · 1 row entry · 5 columns
Allows for control of individual outlet switches. The number of
entries is contained in the sPDUMasterStatusOutletCount OID.
sPDUOutletControlVMEntry entry .1.3.6.1.4.1.318.1.1.5.5.1.1
The outlets to control.
Indexes
sPDUOutletControlVMIndex sPDUOutletControlVMOutletIndex
Column Syntax OID
sPDUOutletControlVMIndex mandatory
The index to the MasterSwitch VM.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.5.1.1.1
sPDUOutletControlVMName mandatory
The name of the MasterSwitch VM. Maximum size is 23 characters.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.5.1.1.2
sPDUOutletControlVMOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.5.1.1.3
sPDUOutletControlVMOutletName mandatory
The name of the outlet. Maximum size is 23 characters.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.5.1.1.4
sPDUOutletControlVMOutletCommand mandatory
Getting this variable will return the outlet state. If
the outlet is on, the immediateOnVM (1) value will be returned.
If the outlet is off, the immediateOffVM (2) value will be
returned.


S…
Enumerationr/w
Enumerated Values:
1immediateOnVM
2immediateOffVM
3immediateRebootVM
4delayedOnVM
5delayedOffVM
6delayedRebootVM
7cancelPendingCommandVM
.1.3.6.1.4.1.318.1.1.5.5.1.1.5
.1.3.6.1.4.1.318.1.1.5.6.1 · 1 row entry · 7 columns
Allows for configuration of individual outlets. The number of
entries is contained in the sPDUMasterStatusOutletCount OID.
sPDUOutletConfigVMEntry entry .1.3.6.1.4.1.318.1.1.5.6.1.1
The outlets to configure.
Indexes
sPDUOutletConfigVMIndex sPDUOutletConfigVMOutletIndex
Column Syntax OID
sPDUOutletConfigVMIndex mandatory
The index to the MasterSwitch VM.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.6.1.1.1
sPDUOutletConfigVMName mandatory
The name of the MasterSwitch VM. Maximum size is 23 characters.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.6.1.1.2
sPDUOutletConfigVMOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.6.1.1.3
sPDUOutletConfigVMOutletName mandatory
The name of the outlet. Maximum size is 23 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.6.1.1.4
sPDUOutletConfigVMPowerOnTime mandatory
The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.

Allowed values are:

-1 never power on.
0 power on …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.6.1.1.5
sPDUOutletConfigVMPowerOffTime mandatory
The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.


Allowed values are:

-1 never power off automatical…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.6.1.1.6
sPDUOutletConfigVMRebootDuration mandatory
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence, before turning power back on, at the
en…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.6.1.1.7
.1.3.6.1.4.1.318.1.1.5.7.1 · 1 row entry · 6 columns
Allows for getting of status of individual outlets. The number of
entries is contained in the sPDUMasterStatusOutletCount OID.
sPDUOutletStatusVMEntry entry .1.3.6.1.4.1.318.1.1.5.7.1.1
The outlets to gather status from.
Indexes
sPDUOutletStatusVMIndex sPDUOutletStatusVMOutletIndex
Column Syntax OID
sPDUOutletStatusVMIndex mandatory
The index to the MasterSwitch VM.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.7.1.1.1
sPDUOutletStatusVMName mandatory
The name of the MasterSwitch VM. Maximum size is 23 characters.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.7.1.1.2
sPDUOutletStatusVMOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.5.7.1.1.3
sPDUOutletStatusVMOutletName mandatory
The name of the outlet. Maximum size is 23 characters.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.5.7.1.1.4
sPDUOutletStatusVMOutletState mandatory
Getting this variable will return the outlet state. If
the outlet is on, the outletStatusOnVM (1) value will be returned.
If the outlet is off, the outletStatusOffVM (2) value will be
returned.
Enumeration
Enumerated Values:
1outletStatusVMOn
2outletStatusVMOff
.1.3.6.1.4.1.318.1.1.5.7.1.1.5
sPDUOutletStatusVMCommandPending mandatory
Getting this variable will return the command pending
state of the outlet. If a command is pending on the
outlet, the outletStatusVMCommandPending (1) value
will be returned. If there is not a command pending
on the out…
Enumeration
Enumerated Values:
1outletStatusVMCommandPending
2outletStatusVMNoCommandPending
.1.3.6.1.4.1.318.1.1.5.7.1.1.6

sPDUIdentMSPTable

table mandatory
.1.3.6.1.4.1.318.1.1.6.1.2 · 1 row entry · 7 columns
Allows for query of the individual MasterSwitch pluses.
The number of entries is contained in the
sPDUIdentMSPTableSize OID.
sPDUIdentMSPEntry entry .1.3.6.1.4.1.318.1.1.6.1.2.1
The MasterSwitch pluses to query.
Indexes
sPDUIdentMSPIndex
Column Syntax OID
sPDUIdentMSPIndex mandatory
The index to the MasterSwitch plus entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.1.2.1.1
sPDUIdentNameMSP mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.1.2.1.2
sPDUIdentHardwareRevMSP mandatory
The hardware version of the MasterSwitch plus.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.1.2.1.3
sPDUIdentFirmwareRevMSP mandatory
An 6-character ID string identifying the MasterSwitch plus
firmware version. This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.1.2.1.4
sPDUIdentDateOfManufactureMSP mandatory
The date when the MasterSwitch plus was manufactured in mm/dd/yyyy format.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.1.2.1.5
sPDUIdentModelNumberMSP mandatory
A 17-character string identifying the model number of
the MasterSwitch plus. This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.1.2.1.6
sPDUIdentSerialNumberMSP mandatory
A 17-character string identifying the serial number of
the MasterSwitch plus. This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.1.2.1.7
.1.3.6.1.4.1.318.1.1.6.2.2 · 1 row entry · 3 columns
Allows for control of the individual MasterSwitch pluses.
The number of entries is contained in the
sPDUMasterControlMSPTableSize OID.
sPDUMasterControlMSPEntry entry .1.3.6.1.4.1.318.1.1.6.2.2.1
The MasterSwitch pluses to control.
Indexes
sPDUMasterControlMSPIndex
Column Syntax OID
sPDUMasterControlMSPIndex mandatory
The index to the MasterSwitch plus entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.2.2.1.1
sPDUMasterControlMSPName mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.2.2.1.2
sPDUMasterControlMSPCommand mandatory
Setting this OID to immediateAllOnMSP (2) will turn all outlets
on immediately.

Setting this OID to sequencedAllOnMSP (3) will turn all outlets
on as defined by each outlet's sPDUOutletConfigMSPPowerOnDel…
Enumerationr/w
Enumerated Values:
1noCommandAllMSP
2immediateAllOnMSP
3sequencedAllOnMSP
4immediateAllOffMSP
5gracefulAllRebootMSP
6immediateAllRebootMSP
7gracefulAllShutdownMSP
8overrideAllBatCapThreshMSP
9cancelAllPendingCommandsMSP
10restoreFactoryDefaultsMSP
.1.3.6.1.4.1.318.1.1.6.2.2.1.3
.1.3.6.1.4.1.318.1.1.6.3.2 · 1 row entry · 4 columns
Allows for configuration of the individual MasterSwitch pluses.
The number of entries is contained in the
sPDUMasterConfigMSPTableSize OID.
sPDUMasterConfigMSPEntry entry .1.3.6.1.4.1.318.1.1.6.3.2.1
The MasterSwitch pluses to configure.
Indexes
sPDUMasterConfigMSPIndex
Column Syntax OID
sPDUMasterConfigMSPIndex mandatory
The index to the MasterSwitch plus entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.3.2.1.1
sPDUMasterConfigMSPName mandatory
The name of the MasterSwitch plus. Maximum size is 23 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.3.2.1.2
sPDUMasterConfigMSPPowerOnTimeDelay mandatory
The amount of delay, in seconds, between when
power is provided to the MasterSwitch plus and
when the MasterSwitch plus provides basic master
power to the outlets.

Allowed values are:

0 - 9…
Integer32r/w
Constraints:
range: 0-9999
.1.3.6.1.4.1.318.1.1.6.3.2.1.3
sPDUMasterConfigMSPManualButton mandatory
Setting this OID to manualButtonDisabled (1) will disable
the manual button on the MasterSwitch plus.

Setting this OID to manualButtonEnabled (2) will enable
the manual button on the MasterSwitch plus.
Enumerationr/w
Enumerated Values:
1manualButtonDisabled
2manualButtonEnabled
.1.3.6.1.4.1.318.1.1.6.3.2.1.4
.1.3.6.1.4.1.318.1.1.6.4.2 · 1 row entry · 3 columns
Allows for gathering of status from the individual
MasterSwitch pluses. The number of entries is contained
in the sPDUMasterStatusMSPTableSize OID.
sPDUMasterStatusMSPEntry entry .1.3.6.1.4.1.318.1.1.6.4.2.1
The MasterSwitch pluses to gather status from.
Indexes
sPDUMasterStatusMSPIndex
Column Syntax OID
sPDUMasterStatusMSPIndex mandatory
The index to the MasterSwitch plus entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.4.2.1.1
sPDUMasterStatusMSPName mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.4.2.1.2
sPDUMasterStatusMSPOutletCount mandatory
Getting this OID will return the number of controllable
outlets for this MasterSwitch plus.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.4.2.1.3
.1.3.6.1.4.1.318.1.1.6.5.1 · 1 row entry · 5 columns
Allows for control of individual outlet switches. The number of
entries is contained in the sPDUMasterStatusMSPOutletCount OID.
sPDUOutletControlMSPEntry entry .1.3.6.1.4.1.318.1.1.6.5.1.1
The outlets to control.
Indexes
sPDUOutletControlMSPIndex sPDUOutletControlMSPOutletIndex
Column Syntax OID
sPDUOutletControlMSPIndex mandatory
The index to the MasterSwitch plus.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.5.1.1.1
sPDUOutletControlMSPName mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.5.1.1.2
sPDUOutletControlMSPOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.5.1.1.3
sPDUOutletControlMSPOutletName mandatory
The name of the outlet. The maximum size is
23 characters. The name is set by using the
sPDUOutletConfigMSPallOutletName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.5.1.1.4
sPDUOutletControlMSPOutletCommand mandatory
Getting this variable will return the outlet state. If
the outlet is on, the immediateOnMSP (1) value will be returned.
If the outlet is off, the immediateOffMSP (3) value will be
returned.

Setting this v…
Enumerationr/w
Enumerated Values:
1immediateOnMSP
2delayedOnMSP
3immediateOffMSP
4gracefulRebootMSP
5immediateRebootMSP
6gracefulshutdownMSP
7overrideBatCapThreshMSP
8cancelPendingCommandMSP
.1.3.6.1.4.1.318.1.1.6.5.1.1.5
.1.3.6.1.4.1.318.1.1.6.6.1.1 · 1 row entry · 5 columns
Allows for configuration of individual outlets. The number of
entries is contained in the sPDUMasterStatusMSPOutletCount OID.
sPDUOutletConfigMSPallEntry entry .1.3.6.1.4.1.318.1.1.6.6.1.1.1
The outlets to configure.
Indexes
sPDUOutletConfigMSPallIndex sPDUOutletConfigMSPallOutletIndex
Column Syntax OID
sPDUOutletConfigMSPallIndex mandatory
The index to the MasterSwitch plus.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.6.1.1.1.1
sPDUOutletConfigMSPallName mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.6.1.1.1.2
sPDUOutletConfigMSPallOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.6.1.1.1.3
sPDUOutletConfigMSPallOutletName mandatory
The name of the outlet. Maximum size is 23 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.6.1.1.1.4
sPDUOutletConfigMSPallOutletCtrlMode mandatory
Setting this OID to modeGracefulShutdown (1) will put this
outlet into the Graceful Shutdown control mode.

Setting this OID to modeAnnunciator (2) will put this outlet
into the Annunciator control mode.
Enumerationr/w
Enumerated Values:
1modeGracefulShutdown
2modeAnnunciator
.1.3.6.1.4.1.318.1.1.6.6.1.1.1.5
.1.3.6.1.4.1.318.1.1.6.6.2.1 · 1 row entry · 13 columns
Allows for configuration of individual outlets. The number of
entries is contained in the sPDUMasterStatusMSPOutletCount OID.
sPDUOutletConfigMSPgsEntry entry .1.3.6.1.4.1.318.1.1.6.6.2.1.1
The outlets to configure.
Indexes
sPDUOutletConfigMSPgsIndex sPDUOutletConfigMSPgsOutletIndex
Column Syntax OID
sPDUOutletConfigMSPgsIndex mandatory
The index to the MasterSwitch plus.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.1
sPDUOutletConfigMSPgsName mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.2
sPDUOutletConfigMSPgsOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.3
sPDUOutletConfigMSPgsOutletName mandatory
The name of the outlet. The maximum size is
23 characters. The name is set by using the
sPDUOutletConfigMSPallOutletName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.4
sPDUOutletConfigMSPgsOutletCtrlMode mandatory
The Control Mode of the outlet.
This OID is provided for informational purposes only.
Enumeration
Enumerated Values:
1modeGracefulShutdown
2modeAnnunciator
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.5
sPDUOutletConfigMSPgsDeviceConfirm mandatory
Setting this OID to deviceConfirmNo (1) cause the outlet to
NOT wait for device confirmation while performing graceful
operations.

Setting this OID to deviceConfirmYes (2) cause the outlet to
wait for dev…
Enumerationr/w
Enumerated Values:
1deviceConfirmNo
2deviceConfirmYes
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.6
sPDUOutletConfigMSPgsLowBattWarning mandatory
The amount of delay, in 6 second intervals, between
when the UPS goes on battery and the power down sequence for
the outlet is initiated.

Allowed values are:

-2 - Never initiate the power d…
Integer32r/w
Constraints:
range: -2-9999
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.7
sPDUOutletConfigMSPgsLowBattMult mandatory
Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID is
set to -1 (On Runtime Remaining).

Allows you to set the value to stagger the shutdown sequence of the outlets.
1 provides the longest delay (t…
Integer32r/w
Constraints:
range: 1-7
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.8
sPDUOutletConfigMSPgsRestartDelay mandatory
The amount of delay, in 6 minute intervals, between
when the outlet is turned off and the outlet is turned back on
when performing a Graceful Shutdown.

Allowed values are:

-1 - Never turn o…
Integer32r/w
Constraints:
range: -1-9999
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.9
sPDUOutletConfigMSPgsPowerOnDelay mandatory
The amount of delay, in seconds, between the UPS entering
normal (on-line) state and the outlet being powered on.

Allowed values are:

-1 - Remain Off when the UPS enters the on-line state.
Integer32r/w
Constraints:
range: -1-9999
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.10
sPDUOutletConfigMSPgsPowerOffDelay mandatory
The amount of delay, in seconds, between when the server
shuts down and the outlet is powered off.

Allowed values are:

0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs).
Integer32r/w
Constraints:
range: 0-9999
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.11
sPDUOutletConfigMSPgsBattCapThresh mandatory
The minimum battery capacity, as a percent (0-100%), required
of the UPS before an outlet will be allowed to power on.

Allowed values are:

0 - 100 percent.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.12
sPDUOutletConfigMSPgsRebootDuration mandatory
The amount of delay, in seconds, from outlet off until
outlet on during a reboot.

Allowed values are:

0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs).
Integer32r/w
Constraints:
range: 0-9999
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.13
.1.3.6.1.4.1.318.1.1.6.6.3.1 · 1 row entry · 7 columns
Allows for configuration of individual outlets. The number of
entries is contained in the sPDUMasterStatusMSPOutletCount OID.
sPDUOutletConfigMSPannunEntry entry .1.3.6.1.4.1.318.1.1.6.6.3.1.1
The outlets to configure.
Indexes
sPDUOutletConfigMSPannunIndex sPDUOutletConfigMSPannunOutletIndex
Column Syntax OID
sPDUOutletConfigMSPannunIndex mandatory
The index to the MasterSwitch plus.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.6.3.1.1.1
sPDUOutletConfigMSPannunName mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.6.3.1.1.2
sPDUOutletConfigMSPannunOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.6.3.1.1.3
sPDUOutletConfigMSPannunOutletName mandatory
The name of the outlet. The maximum size is
23 characters. The name is set by using the
sPDUOutletConfigMSPallOutletName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.6.3.1.1.4
sPDUOutletConfigMSPannunOutletCtrlMode mandatory
The Control Mode of the outlet.
This OID is provided for informational purposes only.
Enumeration
Enumerated Values:
1modeGracefulShutdown
2modeAnnunciator
.1.3.6.1.4.1.318.1.1.6.6.3.1.1.5
sPDUOutletConfigMSPannunInitialState mandatory
Setting this OID to initialStateOff (1) causes the outlet
to default to off when in the non-alarmed condition.

Setting this OID to initialStateOn (2) causes the outlet
to default to on when in the non-ala…
Enumerationr/w
Enumerated Values:
1initialStateOff
2initialStateOn
.1.3.6.1.4.1.318.1.1.6.6.3.1.1.6
sPDUOutletConfigMSPannunAlarmActionDly mandatory
The amount of time, in seconds, that an enabled Measure-UPS
alarm must be asserted before an alarm condition is recognized.

Allowed values are:

0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs…
Integer32r/w
Constraints:
range: 0-9999
.1.3.6.1.4.1.318.1.1.6.6.3.1.1.7
.1.3.6.1.4.1.318.1.1.6.6.4.1 · 1 row entry · 16 columns
Allows for configuration of individual outlets. The number of
entries is contained in the sPDUMasterStatusMSPOutletCount OID.
sPDUOutletConfigMSPmupsEntry entry .1.3.6.1.4.1.318.1.1.6.6.4.1.1
The outlets to configure.
Indexes
sPDUOutletConfigMSPmupsIndex sPDUOutletConfigMSPmupsOutletIndex
Column Syntax OID
sPDUOutletConfigMSPmupsIndex mandatory
The index to the MasterSwitch plus.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.1
sPDUOutletConfigMSPmupsName mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.2
sPDUOutletConfigMSPmupsOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.3
sPDUOutletConfigMSPmupsOutletName mandatory
The name of the outlet. The maximum size is
23 characters. The name is set by using the
sPDUOutletConfigMSPallOutletName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.4
sPDUOutletConfigMSPmupsZone1 mandatory
Setting this OID to disableAlarm (1) disables the
Zone 1 alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Zone 1 alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.5
sPDUOutletConfigMSPmupsZone2 mandatory
Setting this OID to disableAlarm (1) disables the
Zone 2 alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Zone 2 alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.6
sPDUOutletConfigMSPmupsZone3 mandatory
Setting this OID to disableAlarm (1) disables the
Zone 3 alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Zone 3 alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.7
sPDUOutletConfigMSPmupsZone4 mandatory
Setting this OID to disableAlarm (1) disables the
Zone 4 alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Zone 4 alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.8
sPDUOutletConfigMSPmupsP1LowHum mandatory
Setting this OID to disableAlarm (1) disables the
Probe 1 low humidity alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Probe 1 low humidity alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.9
sPDUOutletConfigMSPmupsP1HiHum mandatory
Setting this OID to disableAlarm (1) disables the
Probe 1 high humidity alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Probe 1 high humidity alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.10
sPDUOutletConfigMSPmupsP1LowTemp mandatory
Setting this OID to disableAlarm (1) disables the
Probe 1 low temperature alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Probe 1 low temperature alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.11
sPDUOutletConfigMSPmupsP1HiTemp mandatory
Setting this OID to disableAlarm (1) disables the
Probe 1 high temperature alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Probe 1 high temperature alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.12
sPDUOutletConfigMSPmupsP2LowHum mandatory
Setting this OID to disableAlarm (1) disables the
Probe 2 low humidity alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Probe 2 low humidity alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.13
sPDUOutletConfigMSPmupsP2HiHum mandatory
Setting this OID to disableAlarm (1) disables the
Probe 2 high humidity alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Probe 2 high humidity alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.14
sPDUOutletConfigMSPmupsP2LowTemp mandatory
Setting this OID to disableAlarm (1) disables the
Probe 2 low temperature alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Probe 2 low temperature alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.15
sPDUOutletConfigMSPmupsP2HiTemp mandatory
Setting this OID to disableAlarm (1) disables the
Probe 2 high temperature alarm for this outlet.

Setting this OID to enableAlarm (2) enables the
Probe 2 high temperature alarm for this outlet.
Enumerationr/w
Enumerated Values:
1disableAlarm
2enableAlarm
.1.3.6.1.4.1.318.1.1.6.6.4.1.1.16
.1.3.6.1.4.1.318.1.1.6.7.1 · 1 row entry · 7 columns
Allows for getting of status of individual outlets. The number of
entries is contained in the sPDUMasterStatusOutletCount OID.
sPDUOutletStatusMSPEntry entry .1.3.6.1.4.1.318.1.1.6.7.1.1
The outlets to gather status from.
Indexes
sPDUOutletStatusMSPIndex sPDUOutletStatusMSPOutletIndex
Column Syntax OID
sPDUOutletStatusMSPIndex mandatory
The index to the MasterSwitch MSP.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.7.1.1.1
sPDUOutletStatusMSPName mandatory
The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.7.1.1.2
sPDUOutletStatusMSPOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.6.7.1.1.3
sPDUOutletStatusMSPOutletName mandatory
The name of the outlet. The maximum size is
23 characters. The name is set by using the
sPDUOutletConfigMSPallOutletName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.6.7.1.1.4
sPDUOutletStatusMSPOutletState mandatory
Getting this variable will return the outlet state. If
the outlet is on, the outletStatusMSPOn (1) value will be returned.
If the outlet is off, the outletStatusMSPOff (2) value will be
returned.
Enumeration
Enumerated Values:
1outletStatusMSPOn
2outletStatusMSPOff
.1.3.6.1.4.1.318.1.1.6.7.1.1.5
sPDUOutletStatusMSPCommandPending mandatory
Getting this variable will return the command pending
state of the outlet. If a command is pending on the
outlet, the outletStatusMSPCommandPending (1) value
will be returned. If there is not a command pending
on the ou…
Enumeration
Enumerated Values:
1outletStatusMSPCommandPending
2outletStatusMSPNoCommandPending
.1.3.6.1.4.1.318.1.1.6.7.1.1.6
sPDUOutletStatusMSPOutletCtrlMode mandatory
The Control Mode of the outlet.
This OID is provided for informational purposes only.
Enumeration
Enumerated Values:
1modeGracefulShutdown
2modeAnnunciator
.1.3.6.1.4.1.318.1.1.6.7.1.1.7
.1.3.6.1.4.1.318.1.1.7.1.1.2 · 1 row entry · 2 columns
Allows for accessing description records of the powerplant. The number of
entries is contained in the dm3IdentSysDescriptionTableSize OID.
dm3IdentSysDescriptionEntry entry .1.3.6.1.4.1.318.1.1.7.1.1.2.1
The powerplant description record to reference.
Indexes
dm3IdentSysDescriptionIndex
Column Syntax OID
dm3IdentSysDescriptionIndex mandatory
The index to the DC powerplant description record.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.1.1.2.1.1
dm3IdentSysDescriptionText mandatory
A 16 character text field describing the DC power plant device.
This field can be configured from the dm3ConfigSysDescriptionText OID.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.1.1.2.1.2
.1.3.6.1.4.1.318.1.1.7.2.1.2 · 1 row entry · 2 columns
Allows for accessing description records of the powerplant. The number of
entries is contained in the dm3ConfigSysDescriptionTableSize OID.
dm3ConfigSysDescriptionEntry entry .1.3.6.1.4.1.318.1.1.7.2.1.2.1
The powerplant description record to reference.
Indexes
dm3ConfigSysDescriptionIndex
Column Syntax OID
dm3ConfigSysDescriptionIndex mandatory
The index to the DC powerplant description record.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.1.2.1.1
dm3ConfigSysDescriptionText mandatory
16 character text field describing the DC power plant device.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.2.1.2.1.2

dm3ConfigLVDTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.2.2.2 · 1 row entry · 7 columns
Allows for accessing settings of the LVDs. The number of
entries is contained in the dm3ConfigLVDTableSize OID.
dm3ConfigLVDEntry entry .1.3.6.1.4.1.318.1.1.7.2.2.2.1
The LVD to configure.
Indexes
dm3ConfigLVDIndex
Column Syntax OID
dm3ConfigLVDIndex mandatory
The index to the DC powerplant LVD.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.2.2.1.1
dm3ConfigLVDName mandatory
The name of the LVD. The maximum value is 16 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.2.2.2.1.2
dm3ConfigLVDEnable mandatory
This OID is used to control and indicate if the LVD is on or off.
Setting this OID to enabledYes (1) will enable (turn on) the LVD.
Setting this OID to enabledNo (2) will disable (turn off) the LVD.
Enumerationr/w
Enumerated Values:
1enabledYes
2enabledNo
.1.3.6.1.4.1.318.1.1.7.2.2.2.1.3
dm3ConfigLVDTripThresh mandatory
LVD Trip threshold. If voltage exceeds threshold, the LVD will trip.

Values are represented in thousandths of Volts (mV).
Attempts to set the value above or below the acceptable range of the powerplant
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.2.2.1.4
dm3ConfigLVDResetThresh mandatory
LVD Reset threshold. If voltage exceeds threshold, the LVD will reset.

Values are represented in thousandths of Volts (mV).
Attempts to set the value above or below the acceptable range of the powerplant…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.2.2.1.5
dm3ConfigLVDOpenAlarm mandatory
For the LVD Open Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
alarm condition.
Setting this OID to al…
Enumerationr/w
Enumerated Values:
1alarmIgnore
2alarmRelay1
3alarmRelay2
4alarmRelay3
5alarmRelay4
6alarmRelay5
7alarmRelay6
8alarmMinor
9alarmMajor
.1.3.6.1.4.1.318.1.1.7.2.2.2.1.6
dm3ConfigLVDHWAlarm mandatory
For the LVD Hardware Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
alarm condition.
Setting this OID t…
Enumerationr/w
Enumerated Values:
1alarmIgnore
2alarmRelay1
3alarmRelay2
4alarmRelay3
5alarmRelay4
6alarmRelay5
7alarmRelay6
8alarmMinor
9alarmMajor
.1.3.6.1.4.1.318.1.1.7.2.2.2.1.7

dm3ConfigOutRlyTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.2.5.1.2 · 1 row entry · 4 columns
Allows for accessing settings of the Output Relays. The number of
entries is contained in the dm3ConfigOutRlyTableSize OID.
dm3ConfigOutRlyEntry entry .1.3.6.1.4.1.318.1.1.7.2.5.1.2.1
The output relay to configure.
Indexes
dm3ConfigOutRlyIndex
Column Syntax OID
dm3ConfigOutRlyIndex mandatory
The index to the DC powerplant output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.1
dm3ConfigOutRlyName mandatory
The name of the output relay. The maximum value is 16 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.2
dm3ConfigOutRlyDelay mandatory
Output Relay Delay. This OID represents the time delay from the initiation of an
output relay action to when the output relay action does occur. If the alarm condition
disappears before the end of the delay, no action…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.3
dm3ConfigOutRlyAlarm mandatory
Output Relay Alarm. This setting indicates what action to perform in the event of
an output relay alarm condition;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to a…
Enumerationr/w
Enumerated Values:
1alarmIgnore
2alarmRelay1
3alarmRelay2
4alarmRelay3
5alarmRelay4
6alarmRelay5
7alarmRelay6
8alarmMinor
9alarmMajor
.1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.4

dm3ConfigInRlyTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.2.5.2.2 · 1 row entry · 4 columns
Allows for accessing settings of the Input Relays. The number of
entries is contained in the dm3ConfigInRlyTableSize OID.
dm3ConfigInRlyEntry entry .1.3.6.1.4.1.318.1.1.7.2.5.2.2.1
The input relay to configure.
Indexes
dm3ConfigInRlyIndex
Column Syntax OID
dm3ConfigInRlyIndex mandatory
The index to the DC powerplant input relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.1
dm3ConfigInRlyName mandatory
The name of the input relay. The maximum value is 16 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.2
dm3ConfigInRlyDelay mandatory
Input Relay Delay. This OID represents the time delay from the initiation of an
input relay action to when the input relay action does occur. If the alarm condition
disappears before the end of the delay, no action w…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.3
dm3ConfigInRlyAlarm mandatory
Input Relay Alarm. This setting indicates what action to perform in the event of
an input relay alarm condition;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to ala…
Enumerationr/w
Enumerated Values:
1alarmIgnore
2alarmRelay1
3alarmRelay2
4alarmRelay3
5alarmRelay4
6alarmRelay5
7alarmRelay6
8alarmMinor
9alarmMajor
.1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.4

dm3ConfigBreakersTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.2.6.1.2 · 1 row entry · 3 columns
Allows for accessing settings of the circuit breakers. The number of
entries is contained in the dm3ConfigBreakersTableSize OID.
dm3ConfigBreakersEntry entry .1.3.6.1.4.1.318.1.1.7.2.6.1.2.1
The circuit breaker to configure.
Indexes
dm3ConfigBreakersIndex
Column Syntax OID
dm3ConfigBreakersIndex mandatory
The index to the DC powerplant circuit breaker.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.1
dm3ConfigBreakersName mandatory
The name of the circuit breaker. The maximum value is 16 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.2
dm3ConfigBreakersAlarm mandatory
Circuit Breaker Alarm. This setting indicates what action to perform in the event of
a circuit breaker alarm condition;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID…
Enumerationr/w
Enumerated Values:
1alarmIgnore
2alarmRelay1
3alarmRelay2
4alarmRelay3
5alarmRelay4
6alarmRelay5
7alarmRelay6
8alarmMinor
9alarmMajor
.1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.3

dm3ConfigFusesTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.2.6.2.2 · 1 row entry · 3 columns
Allows for accessing settings of the Fuses. The number of
entries is contained in the dm3ConfigFusesTableSize OID.
dm3ConfigFusesEntry entry .1.3.6.1.4.1.318.1.1.7.2.6.2.2.1
The fuse to configure.
Indexes
dm3ConfigFusesIndex
Column Syntax OID
dm3ConfigFusesIndex mandatory
The index to the DC powerplant fuse.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.1
dm3ConfigFusesName mandatory
The name of the fuse. The maximum value is 16 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.2
dm3ConfigFusesAlarm mandatory
Fuses Alarm. This setting indicates what action to perform in the event of
a Fuse alarm condition;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) c…
Enumerationr/w
Enumerated Values:
1alarmIgnore
2alarmRelay1
3alarmRelay2
4alarmRelay3
5alarmRelay4
6alarmRelay5
7alarmRelay6
8alarmMinor
9alarmMajor
.1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.3

dm3StatusAlarmsTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.3.2.2 · 1 row entry · 2 columns
Allows for accessing system alarms. The number of
entries is contained in the dm3StatusAlarmsTableSize OID.
dm3StatusAlarmsEntry entry .1.3.6.1.4.1.318.1.1.7.3.2.2.1
The alarm to display.
Indexes
dm3StatusAlarmsIndex
Column Syntax OID
dm3StatusAlarmsIndex mandatory
The index of the system alarm.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.2.2.1.1
dm3StatusAlarmsText mandatory
The 16 character text describing the active alarm condition.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.3.2.2.1.2

dm3StatusLVDTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.3.5.2 · 1 row entry · 4 columns
Allows for accessing settings of the LVDs. The number of
entries is contained in the dm3StatusLVDTableSize OID.
dm3StatusLVDEntry entry .1.3.6.1.4.1.318.1.1.7.3.5.2.1
The LVD to gather status from.
Indexes
dm3StatusLVDIndex
Column Syntax OID
dm3StatusLVDIndex mandatory
The index to the DC powerplant LVD.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.5.2.1.1
dm3StatusLVDName mandatory
The name of the LVD. The maximum size is
16 characters. The name is set by using the
dm3ConfigLVDName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.3.5.2.1.2
dm3StatusLVDState mandatory
Getting this OID will return statusClosed (1) if the LVD is closed.
statusOpened (2) will be returned if the LVD is opened.
Enumeration
Enumerated Values:
1statusClosed
2statusOpened
.1.3.6.1.4.1.318.1.1.7.3.5.2.1.3
dm3StatusLVDHwFault mandatory
Getting this OID will return statusFault (1) if the LVD is faulted.
statusNofault (2) will be returned if the LVD is not faulted.
Enumeration
Enumerated Values:
1statusFault
2statusNofault
.1.3.6.1.4.1.318.1.1.7.3.5.2.1.4

dm3StatusRectTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.3.6.1.2 · 1 row entry · 16 columns
Allows for accessing settings of the rectifiers. The number of
entries is contained in the dm3StatusRectTableSize OID.
dm3StatusRectEntry entry .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1
The rectifier to gather status from.
Indexes
dm3StatusRectIndex
Column Syntax OID
dm3StatusRectIndex mandatory
The index to the DC powerplant rectifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.1
dm3StatusRectID mandatory
This OID shows the rectifier ID. This enumerates the number of the rectifier within
a group of rectifiers.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.2
dm3StatusRectDesc mandatory
This OID shows the 16-character rectifier description.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.3
dm3StatusRectCurrent mandatory
This OID shows the rectifier current in thousandths of Amps (mA).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.4
dm3StatusRectCurrentLimit mandatory
Getting this OID will return statusTrue (1) if the rectifier is in the Current Limit state.
statusFalse (2) will be returned if the rectifier is not in the Current Limit state.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.5
dm3StatusRectStandby mandatory
Getting this OID will return statusTrue (1) if the rectifier is in the Standby state.
statusFalse (2) will be returned if the rectifier is not in the Standby state.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.6
dm3StatusRectFanFail mandatory
Getting this OID will return statusTrue (1) if the rectifier Fan has failed.
statusFalse (2) will be returned if the rectifier Fan has not failed.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.7
dm3StatusRectFail mandatory
Getting this OID will return statusTrue (1) if the rectifier has failed.
statusFalse (2) will be returned if the rectifier has not failed.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.8
dm3StatusRectDevType mandatory
This OID shows the rectifier device type.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.9
dm3StatusRectPhyAddr mandatory
This OID shows the rectifier physical address (the address on the bus).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.10
dm3StatusRectCfg mandatory
Getting this OID will return statusTrue (1) if the rectifier is present after
power-up or set-configuration.
statusFalse (2) will be returned if the rectifier is not configured.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.11
dm3StatusRectPcbRev mandatory
This OID shows the rectifier device PCB serial number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.12
dm3StatusRectFwVer mandatory
This OID shows the rectifier device firmware revision.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.13
dm3StatusRectPresent mandatory
Getting this OID will return statusTrue (1) if the rectifier is present.
statusFalse (2) will be returned if the rectifier is not present.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.14
dm3StatusRectDiagPass mandatory
Getting this OID will return statusTrue (1) if the rectifier diagnostics have passed.
statusFalse (2) will be returned if the rectifier diagnostics have not passed.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.15
dm3StatusRectState mandatory
This OID shows the rectifier device state as defined by the device status register.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.16

dm3StatusConvTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.3.6.2.2 · 1 row entry · 16 columns
Allows for viewing status of the converters. The number of
entries is contained in the dm3StatusConvTableSize OID.
dm3StatusConvEntry entry .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1
The converter to gather status from.
Indexes
dm3StatusConvIndex
Column Syntax OID
dm3StatusConvIndex mandatory
The index to the DC powerplant converter.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.1
dm3StatusConvID mandatory
This OID shows the converter ID. This enumerates the number of the converter within
a group of converters.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.2
dm3StatusConvDesc mandatory
This OID shows the 16 character converter description.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.3
dm3StatusConvCurrent mandatory
This OID shows the converter current in thousandths of Amps (mA).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.4
dm3StatusConvCurrentLimit mandatory
Getting this OID will return statusTrue (1) if the converter is in the Current Limit state.
statusFalse (2) will be returned if the converter is not in the Current Limit state.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.5
dm3StatusConvStandby mandatory
Getting this OID will return statusTrue (1) if the converter is in the Standby state.
statusFalse (2) will be returned if the converter is not in the Standby state.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.6
dm3StatusConvFanFail mandatory
Getting this OID will return statusTrue (1) if the converter Fan has failed.
statusFalse (2) will be returned if the converter Fan has not failed.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.7
dm3StatusConvFail mandatory
Getting this OID will return statusTrue (1) if the converter has failed.
statusFalse (2) will be returned if the converter has not failed.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.8
dm3StatusConvDevType mandatory
This OID shows the converter device type.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.9
dm3StatusConvPhyAddr mandatory
This OID shows the converter physical address (the address on the bus).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.10
dm3StatusConvCfg mandatory
Getting this OID will return statusTrue (1) if the converter is present after
power-up or set-configuration.
statusFalse (2) will be returned if the converter is not configured.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.11
dm3StatusConvPcbRev mandatory
This OID shows the converter device PCB serial number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.12
dm3StatusConvFwVer mandatory
This OID shows the converter device firmware version.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.13
dm3StatusConvPresent mandatory
Getting this OID will return statusTrue (1) if the converter is present.
statusFalse (2) will be returned if the converter is not present.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.14
dm3StatusConvDiagPass mandatory
Getting this OID will return statusTrue (1) if the converter diagnostics have passed.
statusFalse (2) will be returned if the converter diagnostics have not passed.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.15
dm3StatusConvState mandatory
This OID shows the converter state as defined by the device status register.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.16

dm3StatusOutRlyTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.3.7.1.2 · 1 row entry · 3 columns
Allows for viewing status of the output relays. The number of
entries is contained in the dm3StatusOutRlyTableSize OID.
dm3StatusOutRlyEntry entry .1.3.6.1.4.1.318.1.1.7.3.7.1.2.1
The output relay to gather status from.
Indexes
dm3StatusOutRlyIndex
Column Syntax OID
dm3StatusOutRlyIndex mandatory
The index to the DC powerplant output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.1
dm3StatusOutRlyName mandatory
The name of the output relay. The maximum size is
16 characters. The name is set by using the
dm3ConfigOutRlyName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.2
dm3StatusOutRlyStatus mandatory
Getting this OID will return statusOn (1) if the output relay is enabled/on.
statusOff (2) will be returned if the output relay is disabled/off.
Enumeration
Enumerated Values:
1statusOn
2statusOff
.1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.3

dm3StatusInRlyTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.3.7.2.2 · 1 row entry · 3 columns
Allows for viewing status of the input relays. The number of
entries is contained in the dm3StatusInRlyTableSize OID.
dm3StatusInRlyEntry entry .1.3.6.1.4.1.318.1.1.7.3.7.2.2.1
The input relays to gather status from.
Indexes
dm3StatusInRlyIndex
Column Syntax OID
dm3StatusInRlyIndex mandatory
The index to the DC powerplant input relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.1
dm3StatusInRlyName mandatory
The name of the input relay. The maximum size is
16 characters. The name is set by using the
dm3ConfigInRlyName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.2
dm3StatusInRlyStatus mandatory
Getting this OID will return statusOn (1) if the input relay is enabled/on.
statusOff (2) will be returned if the input relay is disabled/off.
Enumeration
Enumerated Values:
1statusOn
2statusOff
.1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.3

dm3StatusBreakersTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.3.8.1.2 · 1 row entry · 3 columns
Allows for viewing status of the circuit breakers. The number of
entries is contained in the dm3StatusBreakersTableSize OID.
dm3StatusBreakersEntry entry .1.3.6.1.4.1.318.1.1.7.3.8.1.2.1
The circuit breaker to gather status from.
Indexes
dm3StatusBreakersIndex
Column Syntax OID
dm3StatusBreakersIndex mandatory
The index to the DC powerplant circuit breaker.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.1
dm3StatusBreakersName mandatory
The name of the circuit breaker. The maximum size is
16 characters. The name is set by using the
dm3ConfigBreakersName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.2
dm3StatusBreakersStatus mandatory
Getting this OID will return statusClosed (1) if the circuit breaker is closed.
statusOpen (2) will be returned if the circuit breaker is open.
Enumeration
Enumerated Values:
1statusClosed
2statusOpen
.1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.3

dm3StatusFusesTable

table mandatory
.1.3.6.1.4.1.318.1.1.7.3.8.2.2 · 1 row entry · 3 columns
Allows for viewing status of the fuses. The number of
entries is contained in the dm3StatusFusesTableSize OID.
dm3StatusFusesEntry entry .1.3.6.1.4.1.318.1.1.7.3.8.2.2.1
The fuse to gather status from.
Indexes
dm3StatusFusesIndex
Column Syntax OID
dm3StatusFusesIndex mandatory
The index to the DC powerplant fuse.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.1
dm3StatusFusesName mandatory
The name of the fuse. The maximum size is
16 characters. The name is set by using the
dm3ConfigFuseName OID.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.2
dm3StatusFusesStatus mandatory
Getting this OID will return statusClosed (1) if the fuse is closed.
statusOpen (2) will be returned if the fuse is open.
Enumeration
Enumerated Values:
1statusClosed
2statusOpen
.1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.3
.1.3.6.1.4.1.318.1.1.8.2.1.3 · 1 row entry · 3 columns
The number of phases per input line to this device.
It is not applicable to AP44xxA units or newer.
atsCalibrationInputPhaseEntry entry .1.3.6.1.4.1.318.1.1.8.2.1.3.1
An entry containing calibration information applicable to a
particular input phase. It is not applicable to AP44xxA units or newer.
Indexes
atsCalibrationInputTableIndex atsCalibrationInputPhaseTableIndex
Column Syntax OID
atsCalibrationInputTableIndex mandatory
The input identifier. It is not applicable to AP44xxA units or newer.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.1.3.1.1
atsCalibrationInputPhaseTableIndex mandatory
The input phase identifier. It is not applicable to AP44xxA units or newer.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.1.3.1.2
atsLineVoltageCalibrationFactor mandatory
The Line Voltage Calibration factor. This value is set at the factory.
It is not applicable to AP44xxA units or newer.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.1.3.1.3
.1.3.6.1.4.1.318.1.1.8.2.2.2 · 1 row entry · 3 columns
A list of Power Supply table entries. It is not applicable to AP44xxA units or newer.
atsCalibrationPowerSupplyVoltageEntry entry .1.3.6.1.4.1.318.1.1.8.2.2.2.1
An entry containing information applicable to a particular
Power Supply Voltage. It is not applicable to AP44xxA units or newer.
Indexes
atsCalibrationPowerSupplyVoltageTableIndex
Column Syntax OID
atsCalibrationPowerSupplyVoltageTableIndex mandatory
The power supply voltage identifier. It is not applicable to AP44xxA units or newer.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.2.2.1.1
atsCalibrationPowerSupplyVoltage mandatory
This value describes the power supply voltage of
24V Source A, 24V Source B, +12V, -12V and 5V.
It is not applicable to AP44xxA units or newer.
Enumeration
Enumerated Values:
1powerSupply24V
2powerSupply12V
3powerSupply
4powerSupply24VSourceB
5powerSupplyMinus12V
.1.3.6.1.4.1.318.1.1.8.2.2.2.1.2
atsPowerSupplyVoltageCalibrationFactor mandatory
The Line Voltage Calibration factor. This value is set at the factory.
It is not applicable to AP44xxA units or newer.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.2.2.1.3
.1.3.6.1.4.1.318.1.1.8.2.2.3 · 1 row entry · 3 columns
A list of Power Supply table entries. It is applicable only to AP44xx units.
ats4gCalibrationPowerSupplyVoltageEntry entry .1.3.6.1.4.1.318.1.1.8.2.2.3.1
An entry containing information applicable to a particular
Power Supply Voltage. It is applicable only to AP44xx ATS units.
Indexes
ats4gCalibrationPowerSupplyVoltageTableIndex
Column Syntax OID
ats4gCalibrationPowerSupplyVoltageTableIndex mandatory
The power supply voltage identifier. It is applicable only to AP44xx ATS units.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.2.3.1.1
ats4gCalibrationPowerSupplyVoltage mandatory
This value describes the power supply voltage of
24V Source A, 24V Source B, VBoost Source A, VBoost Source B, 3.3V, 1.0V.
It is applicable only to AP44xx units.
Enumeration
Enumerated Values:
1powerSupply24VA
2powerSupply24VB
3powerSupplyVBoostA
4powerSupplyVBoostB
5powerSupply3Dot3V
6powerSupply1Dot0V
.1.3.6.1.4.1.318.1.1.8.2.2.3.1.2
ats4gPowerSupplyVoltageCalibrationFactor mandatory
The Line Voltage Calibration factor. This value is set at the factory.
It is applicable only to AP44xx units.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.2.3.1.3
.1.3.6.1.4.1.318.1.1.8.2.3.3 · 1 row entry · 3 columns
A list of output table entries. It is not applicable to AP44xxA units or newer.
atsCalibrationOutputEntry entry .1.3.6.1.4.1.318.1.1.8.2.3.3.1
An entry containing information applicable to a particular output.
It is not applicable to AP44xxA units or newer.
Indexes
atsCalibrationOutputTableIndex atsCalibrationOutputPhasesTableIndex
Column Syntax OID
atsCalibrationOutputTableIndex mandatory
The output identifier. It is not applicable to AP44xxA units or newer.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.3.3.1.1
atsCalibrationOutputPhasesTableIndex mandatory
Description of each calibration factor for each
output phase utilized in this device and one for neutral.
It is not applicable to AP44xxA units or newer.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4neutral
.1.3.6.1.4.1.318.1.1.8.2.3.3.1.2
atsOutputCurrentCalibrationFactor mandatory
The output current calibration factor. It is not applicable to AP44xxA units or newer.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.2.3.3.1.3

atsConfigBankTable

table mandatory
.1.3.6.1.4.1.318.1.1.8.4.14 · 1 row entry · 5 columns
Allows for configuration of each ATS bank.
atsConfigBankEntry entry .1.3.6.1.4.1.318.1.1.8.4.14.1
This gives access to bank current threshold
Indexes
atsConfigBankTableIndex
Column Syntax OID
atsConfigBankTableIndex mandatory
An index to the bank table entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.4.14.1.1
atsConfigBank mandatory
The bank number of an ATS
Enumeration
Enumerated Values:
1total
2bank1
3bank2
.1.3.6.1.4.1.318.1.1.8.4.14.1.2
atsConfigBankLowLoadThreshold mandatory
A threshold that indicates the current drawn is nearing
a low consumption condition. It is represented in Amps.
A warning will be issued when the load is less than the
threshold value.

A threshold value o…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.4.14.1.3
atsConfigBankNearOverLoadThreshold mandatory
A threshold that indicates the current drawn is nearing
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than
or equal to the threshold value.

Minimum va…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.4.14.1.4
atsConfigBankOverLoadThreshold mandatory
A threshold that indicates the current drawn has entered
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than or
equal to the threshold value.

Minimum v…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.4.14.1.5

atsConfigPhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.8.4.16 · 1 row entry · 5 columns
Allows for configuration of each ATS phase.
atsConfigPhaseEntry entry .1.3.6.1.4.1.318.1.1.8.4.16.1
This gives access to phase threshold
Indexes
atsConfigPhaseTableIndex
Column Syntax OID
atsConfigPhaseTableIndex mandatory
The index to the phase table entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.4.16.1.1
atsConfigPhase mandatory
The phase number of an ATS
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.8.4.16.1.2
atsConfigPhaseLowLoadThreshold mandatory
A threshold that indicates the current drawn is nearing
a low consumption condition. It is represented in Amps.
A warning will be issued when the load is less than the
threshold value.

A threshold value o…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.4.16.1.3
atsConfigPhaseNearOverLoadThreshold mandatory
A threshold that indicates the current drawn is nearing
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than
or equal to the threshold value.

Minimum va…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.4.16.1.4
atsConfigPhaseOverLoadThreshold mandatory
A threshold that indicates the current drawn has entered
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than or
equal to the threshold value.

Minimum v…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.4.16.1.5

atsInputTable

table mandatory
.1.3.6.1.4.1.318.1.1.8.5.3.2 · 1 row entry · 6 columns
A list of input table entries.  The number of entries
is given by the value of atsNumInputs.
atsInputEntry entry .1.3.6.1.4.1.318.1.1.8.5.3.2.1
An entry containing information applicable to a
particular input.
Indexes
atsInputTableIndex
Column Syntax OID
atsInputTableIndex mandatory
The input identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.2.1.1
atsNumInputPhases mandatory
The number of input phases utilized in this
device. The sum of all the atsNumInputPhases
variable indicates the number of rows in the
input phase table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.2.1.2
atsInputVoltageOrientation mandatory
The input voltage orientation:
1: unknown for this Source
2: singlePhase - phase 1 voltage is between Phase 1
and Neutral.
3: splitPhase - phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Phase…
Enumeration
Enumerated Values:
1unknown
2singlePhase
3splitPhase
4threePhasePhaseToNeutral
5threePhasePhaseToPhase
.1.3.6.1.4.1.318.1.1.8.5.3.2.1.3
atsInputFrequency mandatory
The input frequency in Hertz, or -1 if it's unsupported
by this Source.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.2.1.4
atsInputType mandatory
The input type.
Enumeration
Enumerated Values:
1unknown
2main
3bypass
.1.3.6.1.4.1.318.1.1.8.5.3.2.1.5
atsInputName mandatory
A name given to a particular input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.8.5.3.2.1.6

atsInputPhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.8.5.3.3 · 1 row entry · 11 columns
A list of input table entries.  The number of entries
is given by the sum of the atsNumInputPhases.
atsInputPhaseEntry entry .1.3.6.1.4.1.318.1.1.8.5.3.3.1
An entry containing information applicable to a
particular input phase.
Indexes
atsInputPhaseTableIndex atsInputPhaseIndex
Column Syntax OID
atsInputPhaseTableIndex mandatory
The input identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.1
atsInputPhaseIndex mandatory
The input phase identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.2
atsInputVoltage mandatory
The input voltage in VAC, or -1 if it's unsupported
by this Source.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.3
atsInputMaxVoltage mandatory
The maximum input voltage in VAC measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.4
atsInputMinVoltage mandatory
The minimum input voltage in VAC measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.5
atsInputCurrent mandatory
The input current in amperes, or -1 if it's
unsupported by this Source.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.6
atsInputMaxCurrent mandatory
The maximum input current in amperes measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.7
atsInputMinCurrent mandatory
The minimum input current in amperes measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.8
atsInputPower mandatory
The input power in Watts, or -1 if it's unsupported
by this Source.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.9
atsInputMaxPower mandatory
The maximum input power in Watts measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.10
atsInputMinPower mandatory
The minimum input power in Watts measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.3.3.1.11

atsOutputTable

table mandatory
.1.3.6.1.4.1.318.1.1.8.5.4.2 · 1 row entry · 4 columns
A list of output table entries.  The number of entries
is given by the value of atsOutputNumPhases.
atsOutputEntry entry .1.3.6.1.4.1.318.1.1.8.5.4.2.1
An entry containing information applicable to a
particular output.
Indexes
atsOutputTableIndex
Column Syntax OID
atsOutputTableIndex mandatory
The output identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.2.1.1
atsNumOutputPhases mandatory
The number of output phases utilized in this
device. The sum of all the atsNumOutputPhases
variable indicates the number of rows in the
output phase table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.2.1.2
atsOutputVoltageOrientation mandatory
The output voltage orientation:
1: unknown for this ATS
2: singlePhase - phase 1 voltage is between Phase 1
and Neutral.
3: splitPhase - phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Phase 2…
Enumeration
Enumerated Values:
1unknown
2singlePhase
3splitPhase
4threePhasePhaseToNeutral
5threePhasePhaseToPhase
.1.3.6.1.4.1.318.1.1.8.5.4.2.1.3
atsOutputFrequency mandatory
The output frequency in Hertz, or -1 if it's
unsupported by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.2.1.4

atsOutputPhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.8.5.4.3 · 1 row entry · 19 columns
A list of output table entries.  The number of
entries is given by the sum of the atsNumOutputPhases.
atsOutputPhaseEntry entry .1.3.6.1.4.1.318.1.1.8.5.4.3.1
An entry containing information applicable to a
particular output phase.
Indexes
atsOutputPhaseTableIndex atsOutputPhaseIndex
Column Syntax OID
atsOutputPhaseTableIndex mandatory
The output identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.1
atsOutputPhaseIndex mandatory
Description of each output phase utilized in
this device and one for neutral.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4neutral
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.2
atsOutputVoltage mandatory
The output voltage in VAC, or -1 if it's unsupported
by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.3
atsOutputCurrent mandatory
The output current in 0.1 amperes drawn
by the load on the ATS, or -1 if it's unsupported
by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.4
atsOutputMaxCurrent mandatory
The maximum output current in 0.1 amperes measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.5
atsOutputMinCurrent mandatory
The minimum output current in 0.1 amperes measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.6
atsOutputLoad mandatory
The output load in VA, or -1 if it's unsupported
by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.7
atsOutputMaxLoad mandatory
The maximum output load in VA measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.8
atsOutputMinLoad mandatory
The minimum output load in VA measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.9
atsOutputPercentLoad mandatory
The percentage of the ATS load capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.10
atsOutputMaxPercentLoad mandatory
The maximum percentage of the ATS load capacity in
VA measured at redundancy @ (n + x) presently
being used on this output phase since the last time
this variable was read or reset (atsStatusResetMaxMinValues).
Returns …
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.11
atsOutputMinPercentLoad mandatory
The minimum percentage of the ATS load capacity in
VA measured at redundancy @ (n + x) presently
being used on this output phase since the last time
this variable was read or reset (atsStatusResetMaxMinValues).
Returns …
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.12
atsOutputPower mandatory
The output apparent power in VA, or
-1 if it's unsupported by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.13
atsOutputMaxPower mandatory
The maximum output power in VAs measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.14
atsOutputMinPower mandatory
The minimum output power in VA measured
since the last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.15
atsOutputPercentPower mandatory
The percentage of the ATSpower capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.16
atsOutputMaxPercentPower mandatory
The maximum percentage of the ATSpower capacity
in VA measured at redundancy @ (n + x) presently
being used on this output phase since the last time
this variable was read or reset (atsStatusResetMaxMinValues).
Returns …
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.17
atsOutputMinPercentPower mandatory
The minimum percentage of the ATSpower capacity
in VA measured at redundancy @ (n + x) presently
being used on this output phase since the last time
this variable was read or reset (atsStatusResetMaxMinValues).
Returns …
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.18
atsOutputPhaseState mandatory
Getting this OID will return the phase load state.

normal(1) indicates that the bank is operating properly
within the atsConfigPhaseLowLoadThreshold and
atsConfigPhaseNearOverLoadThreshold OID values.
Enumeration
Enumerated Values:
1normal
2lowload
3nearoverload
4overload
.1.3.6.1.4.1.318.1.1.8.5.4.3.1.19

atsOutputBankTable

table mandatory
.1.3.6.1.4.1.318.1.1.8.5.4.5 · 1 row entry · 20 columns
Allows for getting table entries.
atsOutputBankEntry entry .1.3.6.1.4.1.318.1.1.8.5.4.5.1
This gives access to bank table entries
Indexes
atsOutputBankTableIndex
Column Syntax OID
atsOutputBankTableIndex mandatory
The index to the bank table entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.1
atsOutputPhase mandatory
The phase number of an ATS
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.2
atsOutputBank mandatory
The bank number of an ATS
Enumeration
Enumerated Values:
1total
2bank1
3bank2
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.3
atsOutputBankCurrent mandatory
Getting this OID will return the bank current measured
in tenths of Amps.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.4
atsOutputBankState mandatory
Getting this OID will return the bank load state.

normal(1) indicates that the bank is
operating properly within the atsConfigBankLowLoadThreshold
and atsConfigBankNearOverLoadThreshold OID values.
Enumeration
Enumerated Values:
1normal
2lowload
3nearoverload
4overload
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.5
atsOutputBankOutputVoltage mandatory
The output voltage in VAC, or -1 if it's unsupported
by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.6
atsOutputBankMaxCurrent mandatory
The maximum output current, on the bank represented by
OID atsOutputBank, in 0.1 amperes measured since the
last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.7
atsOutputBankMinCurrent mandatory
The minimum output current, on the bank represented by
OID atsOutputBank, in 0.1 amperes measured since the
last time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.8
atsOutputBankLoad mandatory
The output load, on the bank represented by
OID atsOutputBank, in VA, or -1 if it's
unsupported by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.9
atsOutputBankMaxLoad mandatory
The maximum output load, on the bank represented by
OID atsOutputBank, in VA measured since the last
time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.10
atsOutputBankMinLoad mandatory
The minimum output load, on the bank represented by
OID atsOutputBank, in VA measured since the last
time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.11
atsOutputBankPercentLoad mandatory
The percentage of the ATS load capacity in VA at
redundancy @ (n + x) presently being used on this
bank, represented by OID atsOutputBank.
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.12
atsOutputBankMaxPercentLoad mandatory
The maximum percentage of the ATS load capacity in
VA measured at redundancy @ (n + x) presently
being used on this bank, represented by OID atsOutputBank,
since the last time this variable was read or
reset (atsStatusR…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.13
atsOutputBankMinPercentLoad mandatory
The minimum percentage of the ATS load capacity in
VA measured at redundancy @ (n + x) presently
being used on this bank, represented by OID
atsOutputBank, since the last time this variable was
read or reset (atsStatusR…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.14
atsOutputBankPower mandatory
The output apparent power in VA on the bank represented by
OID atsOutputBank or -1 if it's unsupported by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.15
atsOutputBankMaxPower mandatory
The maximum output power in VA measured on the bank
represented by OID atsOutputBank since the last
time this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.16
atsOutputBankMinPower mandatory
The minimum output power in VA measured on the bank
represented by OID atsOutputBank since the last time
this variable was read
or reset (atsStatusResetMaxMinValues).
Returns (-1) if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.17
atsOutputBankPercentPower mandatory
The percentage of the ATSpower capacity in Watts at
redundancy @ (n + x) presently being used on this
bank, represented by OID atsOutputBank, or
-1 if it's unsupported by this ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.18
atsOutputBankMaxPercentPower mandatory
The maximum percentage of the ATSpower capacity
in VA measured at redundancy @ (n + x) presently
being used on this bank, represented by OID
atsOutputBank, since the last time this variable
was read or reset (atsStatusR…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.19
atsOutputBankMinPercentPower mandatory
The minimum percentage of the ATSpower capacity
in VA measured at redundancy @ (n + x) presently
being used on this bank, represented by OID atsOutputBank
since the last time this variable was read or
reset (atsStatusRe…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.8.5.4.5.1.20

dcmim2ConfigLVDTable

table mandatory
.1.3.6.1.4.1.318.1.1.9.3.3.2 · 1 row entry · 4 columns
Allows for accessing settings of the LVDs. The number of
entries is contained in the dcmim2ConfigLVDTableSize OID.
dcmim2ConfigLVDEntry entry .1.3.6.1.4.1.318.1.1.9.3.3.2.1
The LVD to configure.
Indexes
dcmim2ConfigLVDIndex
Column Syntax OID
dcmim2ConfigLVDIndex mandatory
The index to the DC powerplant LVD.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.3.3.2.1.1
dcmim2ConfigLVDTrip mandatory
LVD Trip threshold. System bus voltage at which LVD will trip (open)
during a battery backup operation.

Values are represented in thousandths of Volts (mV).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.3.3.2.1.2
dcmim2ConfigLVDReset mandatory
LVD Reset threshold. System bus voltage at which LVD will reset (close)
after AC power has been restored.

Values are represented in thousandths of Volts (mV).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.3.3.2.1.3
dcmim2ConfigLVDState mandatory
Getting this OID will return statusClosed (1) if the LVD is closed.
statusOpened (2) will be returned if the LVD is opened.
Enumeration
Enumerated Values:
1statusClosed
2statusOpened
.1.3.6.1.4.1.318.1.1.9.3.3.2.1.4

dcmim2StatusRectTable

table mandatory
.1.3.6.1.4.1.318.1.1.9.4.2.2 · 1 row entry · 6 columns
Allows for accessing settings of the rectifiers. The number of
entries is contained in the dcmim2StatusRectTableSize OID.
dcmim2StatusRectEntry entry .1.3.6.1.4.1.318.1.1.9.4.2.2.1
The rectifier to gather status from.
Indexes
dcmim2StatusRectIndex
Column Syntax OID
dcmim2StatusRectIndex mandatory
The index to the DC powerplant rectifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.4.2.2.1.1
dcmim2StatusRectDevType mandatory
This OID shows the rectifier device type.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.4.2.2.1.2
dcmim2StatusRectID mandatory
This OID shows the rectifier ID. This enumerates the number of the rectifier within
a group of rectifiers.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.4.2.2.1.3
dcmim2StatusRectPhyAddr mandatory
This OID shows the rectifier physical address (the address on the bus).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.4.2.2.1.4
dcmim2StatusRectFail mandatory
Getting this OID will return statusTrue (1) if the rectifier has failed.
statusFalse (2) will be returned if the rectifier has not failed.
Enumeration
Enumerated Values:
1statusTrue
2statusFalse
.1.3.6.1.4.1.318.1.1.9.4.2.2.1.5
dcmim2StatusRectCurrent mandatory
This OID shows the individual rectifier current in thousandths of Amps (mA).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.4.2.2.1.6

dcmim2StatusLVDTable

table mandatory
.1.3.6.1.4.1.318.1.1.9.4.4.2 · 1 row entry · 2 columns
Allows for accessing the LVDs. The number of
entries is contained in the dcmim2StatusLVDTableSize OID.
dcmim2StatusLVDEntry entry .1.3.6.1.4.1.318.1.1.9.4.4.2.1
The LVD to access.
Indexes
dcmim2StatusLVDIndex
Column Syntax OID
dcmim2StatusLVDIndex mandatory
The index to the DC powerplant LVD.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.4.4.2.1.1
dcmim2StatusLVDState mandatory
Getting this OID will return statusClosed (1) if the LVD is closed.
statusOpened (2) will be returned if the LVD is opened.
Enumeration
Enumerated Values:
1statusClosed
2statusOpened
.1.3.6.1.4.1.318.1.1.9.4.4.2.1.2
.1.3.6.1.4.1.318.1.1.9.4.5.2 · 1 row entry · 2 columns
Allows for accessing system alarms. The number of
entries is contained in the dcmim2StatusAlarmsTableSize OID.
dcmim2StatusAlarmsEntry entry .1.3.6.1.4.1.318.1.1.9.4.5.2.1
The alarm to display.
Indexes
dcmim2StatusAlarmsIndex
Column Syntax OID
dcmim2StatusAlarmsIndex mandatory
The index of the system alarm.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.9.4.5.2.1.1
dcmim2StatusAlarmsText mandatory
The 16 character text describing the active alarm condition.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.9.4.5.2.1.2

emConfigProbesTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.1.2.2 · 1 row entry · 22 columns
A list of probes supported by the Environmental Monitor
and their configurations.
emConfigProbesEntry entry .1.3.6.1.4.1.318.1.1.10.1.2.2.1
The Environmental Monitor probe configurations.
Indexes
emConfigProbeNumber
Column Syntax OID
emConfigProbeNumber mandatory
The index into an Environmental Monitor probe entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.1
emConfigProbeName mandatory
A descriptive name of the probe set by the user,
possibly denoting its location or purpose.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.2
emConfigProbeHighTempThreshold mandatory
The high temperature alarm threshold for the probe.
Units are displayed in the scale selected in
the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.3
emConfigProbeLowTempThreshold mandatory
The low temperature alarm threshold for the probe.
Units are displayed in the scale selected in
the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.4
emConfigProbeTempUnits mandatory
The temperature scale used to display the temperature
thresholds of the probe, Celsius(1) or Fahrenheit(2).
This setting is based on the system preferences
configuration in the agent.
Enumeration
Enumerated Values:
1celsius
2fahrenheit
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.5
emConfigProbeHighHumidThreshold mandatory
The high humidity alarm threshold for the probe in
percent relative humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.6
emConfigProbeLowHumidThreshold mandatory
The low humidity alarm threshold for the probe in
percent relative humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.7
emConfigProbeHighTempEnable mandatory
The high temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.8
emConfigProbeLowTempEnable mandatory
The low temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.9
emConfigProbeHighHumidEnable mandatory
The high humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.10
emConfigProbeLowHumidEnable mandatory
The low humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.11
emConfigProbeMaxTempThreshold mandatory
The maximum temperature alarm threshold for the probe.
Units are displayed in the scale selected in
the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.12
emConfigProbeMinTempThreshold mandatory
The minimum temperature alarm threshold for the probe.
Units are displayed in the scale selected in
the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.13
emConfigProbeMaxHumidThreshold mandatory
The maximun humidity alarm threshold for the probe in
percent relative humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.14
emConfigProbeMinHumidThreshold mandatory
The minimum humidity alarm threshold for the probe in
percent relative humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.15
emConfigProbeMaxTempEnable mandatory
The maximum temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been viola…
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.16
emConfigProbeMinTempEnable mandatory
The minimum temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been viola…
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.17
emConfigProbeMaxHumidEnable mandatory
The maximum humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.18
emConfigProbeMinHumidEnable mandatory
The minimum humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.19
emConfigProbeTempHysteresis mandatory
The number of degrees beyond the temperature thresholds
at which an active temperature alarm will be cleared.
This configuration setting applies to all temperature
thresholds.
Units are displayed in the scale selected i…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.20
emConfigProbeHumidHysteresis mandatory
The number of percent RH points beyond the humidity
thresholds at which an active humidity alarm will be
cleared. This configuration setting applies to all
humidity thresholds.
Units are displayed in the scale selected …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.21
emConfigProbeLocation mandatory
A string describing the location of the probe.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.1.2.2.1.22

emConfigContactsTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.1.2.4 · 1 row entry · 6 columns
A list of contacts supported by the Environmental Monitor
and their configurations.
emConfigContactsEntry entry .1.3.6.1.4.1.318.1.1.10.1.2.4.1
The Environmental Monitor contact configurations.
Indexes
emConfigContactNumber
Column Syntax OID
emConfigContactNumber mandatory
The index of an Environmental Monitor contact.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.2.4.1.1
emConfigContactName mandatory
A descriptive name for an Environmental Monitor
contact set by the user, possibly denoting its
location or purpose.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.1.2.4.1.2
emConfigContactEnable mandatory
An Environmental Monitor contact alarm enable/disable.
No alarm will be generated if the contact is disabled(1).
An alarm will be generated if the contact is enabled(2)
and the contact has been faulted.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.1.2.4.1.3
emConfigContactSeverity mandatory
The severity of the alarm that will be triggered when
the input contact is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.1.2.4.1.4
emConfigContactNormalState mandatory
The contact state that will be considered normal, i.e.
will not trigger an alarm. The states are open(1) or
closed(2).
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.10.1.2.4.1.5
emConfigContactLocation mandatory
A descriptive label for the contact denoting its
location or purpose.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.1.2.4.1.6

emStatusProbesTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.1.3.3 · 1 row entry · 14 columns
A list of probes supported by the Environmental Monitor
and their status.
emStatusProbesEntry entry .1.3.6.1.4.1.318.1.1.10.1.3.3.1
The status of the probe.
Indexes
emStatusProbeNumber
Column Syntax OID
emStatusProbeNumber mandatory
The index of the probe.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.1
emStatusProbeName mandatory
A descriptive name for the probe set by the user,
possibly denoting its location or purpose.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.2
emStatusProbeStatus mandatory
The connected status of the probe, either
disconnected(1) or connected(2).
Enumeration
Enumerated Values:
1disconnected
2connected
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.3
emStatusProbeCurrentTemp mandatory
The current temperature reading from the probe displayed
in the units shown in the 'emStatusProbeTempUnits' OID
(Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.4
emStatusProbeTempUnits mandatory
The temperature scale used to display the temperature
thresholds of the probe, Celsius(1) or Fahrenheit(2).
This setting is based on the system preferences
configuration in the agent.
Enumeration
Enumerated Values:
1celsius
2fahrenheit
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.5
emStatusProbeCurrentHumid mandatory
The current humidity reading from the probe in
percent relative humidity.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.6
emStatusProbeHighTempViolation mandatory
The high temperature violation status of the probe
temperature reading. This OID will show a highTempViolation(2)
if the current temperature reading shown in the
'emStatusProbeCurrentTemp' OID is greater than or equal t…
Enumeration
Enumerated Values:
1noViolation
2highTempViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.7
emStatusProbeLowTempViolation mandatory
The high temperature violation status of the probe
temperature reading. This OID will show a lowTempViolation(2)
if the current temperature reading shown in the
'emStatusProbeCurrentTemp' OID is less than or equal to
th…
Enumeration
Enumerated Values:
1noViolation
2lowTempViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.8
emStatusProbeHighHumidViolation mandatory
The high humidity violation status of the probe humidity
reading. This OID will show a highTempViolation(2)
if the current humidity reading shown in the
'emStatusProbeCurrentHumid' OID is greater than or equal to
the hi…
Enumeration
Enumerated Values:
1noViolation
2highHumidViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.9
emStatusProbeLowHumidViolation mandatory
The low humidity violation status of the probe humidity
reading. This OID will show a lowTempViolation(2)
if the current humidity reading shown in the
'emStatusProbeCurrentHumid' OID is less than or equal to
the low hum…
Enumeration
Enumerated Values:
1noViolation
2lowHumidViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.10
emStatusProbeMaxTempViolation mandatory
The max temperature violation status of the probe
temperature reading. This OID will show a maxTempViolation(2)
if the current temperature reading shown in the
'emStatusProbeCurrentTemp' OID is greater than or equal to
Enumeration
Enumerated Values:
1noViolation
2maxTempViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.11
emStatusProbeMinTempViolation mandatory
The minimum temperature violation status of the probe
temperature reading. This OID will show a minTempViolation(2)
if the current temperature reading shown in the
'emStatusProbeCurrentTemp' OID is less than or equal to…
Enumeration
Enumerated Values:
1noViolation
2minTempViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.12
emStatusProbeMaxHumidViolation mandatory
The maximum humidity violation status of the probe humidity
reading. This OID will show a maxTempViolation(2)
if the current humidity reading shown in the
'emStatusProbeCurrentHumid' OID is greater than or equal to
the …
Enumeration
Enumerated Values:
1noViolation
2maxHumidViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.13
emStatusProbeMinHumidViolation mandatory
The minimum humidity violation status of the probe humidity
reading. This OID will show a minTempViolation(2)
if the current humidity reading shown in the
'emStatusProbeCurrentHumid' OID is less than or equal to
the min…
Enumeration
Enumerated Values:
1noViolation
2minHumidViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.3.1.14

emStatusContactsTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.1.3.5 · 1 row entry · 3 columns
A list of contacts supported by the Environmental Monitor
and their status.
emStatusContactsEntry entry .1.3.6.1.4.1.318.1.1.10.1.3.5.1
The status of the contact.
Indexes
emStatusContactNumber
Column Syntax OID
emStatusContactNumber mandatory
The index of the Environmental Monitor contact.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.1.3.5.1.1
emStatusContactName mandatory
A descriptive name for the Environmental Monitor contact
set by the user, possibly denoting its location or purpose.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.1.3.5.1.2
emStatusContactStatus mandatory
The status of the Environmental Monitor contact. The status
will show noFault(1) if the contact is in the normal state
and the 'emConfigContactEnable' OID is enabled. The status will
show a fault(2) if the contact is fa…
Enumeration
Enumerated Values:
1noFault
2fault
3disabled
.1.3.6.1.4.1.318.1.1.10.1.3.5.1.3

iemConfigProbesTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.2.2.2 · 1 row entry · 22 columns
A list of probes supported by the Environmental Monitor
and their configurations.
iemConfigProbesEntry entry .1.3.6.1.4.1.318.1.1.10.2.2.2.1
The Environmental Monitor probe configurations.
Indexes
iemConfigProbeNumber
Column Syntax OID
iemConfigProbeNumber mandatory
The index to a Environmental Monitor probe entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.1
iemConfigProbeName mandatory
A descriptive name for the probe set by the user,
possibly denoting its location or purpose.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.2
iemConfigProbeHighTempThreshold mandatory
The high temperature alarm threshold for the probe.
Units are displayed in the scale selected in the
'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.3
iemConfigProbeLowTempThreshold mandatory
The low temperature alarm threshold for the probe.
Units are displayed in the scale selected in the
'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.4
iemConfigProbeTempUnits mandatory
The temperature scale used to display the temperature
thresholds of the probe, Celsius(1) or Fahrenheit(2).
This setting is based on the system preferences
configuration in the agent.
Enumeration
Enumerated Values:
1celsius
2fahrenheit
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.5
iemConfigProbeHighHumidThreshold mandatory
The high humidity alarm threshold for the probe in
percent relative humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.6
iemConfigProbeLowHumidThreshold mandatory
The low humidity alarm threshold for the probe in
percent relative humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.7
iemConfigProbeHighTempEnable mandatory
The high temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.8
iemConfigProbeLowTempEnable mandatory
The low temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.9
iemConfigProbeHighHumidEnable mandatory
The high humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.10
iemConfigProbeLowHumidEnable mandatory
The low humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.11
iemConfigProbeMaxTempThreshold mandatory
The maximun temperature alarm threshold for the probe.
Units are displayed in the scale selected in the
'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.12
iemConfigProbeMinTempThreshold mandatory
The minimun temperature alarm threshold for the probe.
Units are displayed in the scale selected in the
'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.13
iemConfigProbeMaxHumidThreshold mandatory
The maximum humidity alarm threshold for the probe in
percent relative humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.14
iemConfigProbeMinHumidThreshold mandatory
The minimum humidity alarm threshold for the probe in
percent relative humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.15
iemConfigProbeMaxTempEnable mandatory
The maximum temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been viola…
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.16
iemConfigProbeMinTempEnable mandatory
The low temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.17
iemConfigProbeMaxHumidEnable mandatory
The maximum humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.18
iemConfigProbeMinHumidEnable mandatory
The minimum humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2) and
the threshold has been violated.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.19
iemConfigProbeTempHysteresis mandatory
The number of degrees beyond the temperature thresholds
at which an active temperature alarm will be cleared.
This configuration setting applies to all temperature
thresholds.
Units are displayed in the scale selected i…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.20
iemConfigProbeHumidHysteresis mandatory
The number of percent RH points beyond the humidity
thresholds at which an active humidity alarm will be
cleared. This configuration setting applies to all
humidity thresholds.
Units are displayed in the scale selected …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.21
iemConfigProbeLocation mandatory
A string describing the location of the probe.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.22

iemConfigContactsTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.2.2.4 · 1 row entry · 6 columns
A list of contacts supported by the Environmental Monitor
and their configurations.
iemConfigContactsEntry entry .1.3.6.1.4.1.318.1.1.10.2.2.4.1
The Environmental Monitor contact configurations.
Indexes
iemConfigContactNumber
Column Syntax OID
iemConfigContactNumber mandatory
The index of an Environmental Monitor contact.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.4.1.1
iemConfigContactName mandatory
A descriptive name for the Environmental Monitor contact
set by the user, possibly denoting its location or purpose.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.2.4.1.2
iemConfigContactEnable mandatory
An Environmental Monitor contact alarm enable/disable.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.2.2.4.1.3
iemConfigContactSeverity mandatory
The severtity of the alarm that will be triggered when
the input contact is activated. The alarms can be
critical(1), warning(2) or informational(3).
NOTE: informational(3) is deprecated (and no longer valid) for this O…
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.2.2.4.1.4
iemConfigContactNormalState mandatory
The contact state that will be considered normal, i.e.
will not trigger an alarm. The states are open(1) or
closed(2).
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.10.2.2.4.1.5
iemConfigContactLocation mandatory
A descriptive label for the contact denoting its
location or purpose.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.2.4.1.6

iemConfigRelaysTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.2.2.6 · 1 row entry · 4 columns
A list of output relays supported by the Environmental Monitor
and their configurations.
iemConfigRelaysEntry entry .1.3.6.1.4.1.318.1.1.10.2.2.6.1
The Environmental Monitor output relay configurations.
Indexes
iemConfigRelayNumber
Column Syntax OID
iemConfigRelayNumber mandatory
The index of an Environmental Monitor output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.6.1.1
iemConfigRelayName mandatory
A descriptive name of an Environmental Monitor output relay,
set by the user, describing its location or purpose.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.2.6.1.2
iemConfigRelayNormalState mandatory
The normal state (non-fault state) of an Environmental
Monitor output relay, either open(1) or closed(2).
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.10.2.2.6.1.3
iemConfigRelayFaultCondition mandatory
The fault condition used to activate the output relay.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.2.6.1.4

iemStatusProbesTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.2.3.2 · 1 row entry · 15 columns
A list of probes supported by the Environmental Monitor
and their status.
iemStatusProbesEntry entry .1.3.6.1.4.1.318.1.1.10.2.3.2.1
The status of the probe.
Indexes
iemStatusProbeNumber
Column Syntax OID
iemStatusProbeNumber mandatory
The index of the probe.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.1
iemStatusProbeName mandatory
A descriptive name for the probe set by the user.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.2
iemStatusProbeStatus mandatory
The connected status of the probe, either
disconnected(1) or connected(2).
Enumeration
Enumerated Values:
1disconnected
2connected
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.3
iemStatusProbeCurrentTemp mandatory
The current temperature reading from the probe displayed
in the units shown in the 'iemStatusProbeTempUnits' OID
(Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.4
iemStatusProbeTempUnits mandatory
The temperature scale used to display the temperature
thresholds of the probe, Celsius(1) or Fahrenheit(2).
This setting is based on the system preferences
configuration in the agent.
Enumeration
Enumerated Values:
1celsius
2fahrenheit
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.5
iemStatusProbeCurrentHumid mandatory
The current humidity reading from the probe in percent
relative humidity.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.6
iemStatusProbeHighTempViolation mandatory
The high temperature violation status of the probe
temperature reading. This OID will show a highTempViolation(2)
if the current temperature reading shown in the
'iemStatusProbeCurrentTemp' OID is greater than or equal …
Enumeration
Enumerated Values:
1noViolation
2highTempViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.7
iemStatusProbeLowTempViolation mandatory
The high temperature violation status of the probe
temperature reading. This OID will show a lowTempViolation(2)
if the current temperature reading shown in the
'iemStatusProbeCurrentTemp' OID is less than or equal to
t…
Enumeration
Enumerated Values:
1noViolation
2lowTempViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.8
iemStatusProbeHighHumidViolation mandatory
The high humidity violation status of the probe humidity
reading. This OID will show a highTempViolation(2)
if the current humidity reading shown in the
'iemStatusProbeCurrentHumid' OID is greater than or equal to
the h…
Enumeration
Enumerated Values:
1noViolation
2highHumidViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.9
iemStatusProbeLowHumidViolation mandatory
The low humidity violation status of the probe humidity
reading. This OID will show a lowTempViolation(2)
if the current humidity reading shown in the
'iemStatusProbeCurrentHumid' OID is less than or equal to
the low hu…
Enumeration
Enumerated Values:
1noViolation
2lowHumidViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.10
iemStatusProbeMaxTempViolation mandatory
The max temperature violation status of the probe
temperature reading. This OID will show a maxTempViolation(2)
if the current temperature reading shown in the
'iemStatusProbeCurrentTemp' OID is greater than or equal to…
Enumeration
Enumerated Values:
1noViolation
2maxTempViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.11
iemStatusProbeMinTempViolation mandatory
The minimum temperature violation status of the probe
temperature reading. This OID will show a minTempViolation(2)
if the current temperature reading shown in the
'iemStatusProbeCurrentTemp' OID is less than or equal t…
Enumeration
Enumerated Values:
1noViolation
2minTempViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.12
iemStatusProbeMaxHumidViolation mandatory
The maximum humidity violation status of the probe humidity
reading. This OID will show a maxTempViolation(2)
if the current humidity reading shown in the
'iemStatusProbeCurrentHumid' OID is greater than or equal to
the…
Enumeration
Enumerated Values:
1noViolation
2maxHumidViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.13
iemStatusProbeMinHumidViolation mandatory
The minimum humidity violation status of the probe humidity
reading. This OID will show a minTempViolation(2)
if the current humidity reading shown in the
'iemStatusProbeCurrentHumid' OID is less than or equal to
the mi…
Enumeration
Enumerated Values:
1noViolation
2minHumidViolation
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.14
iemStatusProbeLocation mandatory
A descriptive location for the probe set by the user.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.15

iemStatusContactsTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.2.3.4 · 1 row entry · 3 columns
A list of contacts supported by the Environmental Monitor
and their status.
iemStatusContactsEntry entry .1.3.6.1.4.1.318.1.1.10.2.3.4.1
The status of the contact.
Indexes
iemStatusContactNumber
Column Syntax OID
iemStatusContactNumber mandatory
The index of the Environmental Monitor contact.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.3.4.1.1
iemStatusContactName mandatory
A descriptive name for the Environmental Monitor contact
set by the user, denoting its location or purpose.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.3.4.1.2
iemStatusContactStatus mandatory
The status of the Environmental Monitor contact. The status
will show noFault(1) if the contact is in the normal state
and the 'iemConfigContactEnable' OID is enabled. The status will
show a fault(2) if the contact is f…
Enumeration
Enumerated Values:
1noFault
2fault
3disabled
.1.3.6.1.4.1.318.1.1.10.2.3.4.1.3

iemStatusRelaysTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.2.3.7 · 1 row entry · 3 columns
A list of output relays supported by the
Environmental Monitor and their status.
iemStatusRelaysEntry entry .1.3.6.1.4.1.318.1.1.10.2.3.7.1
The status of the relay.
Indexes
iemStatusRelayNumber
Column Syntax OID
iemStatusRelayNumber mandatory
The index of the output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.2.3.7.1.1
iemStatusRelayName mandatory
A descriptive name for the output relay set by the
user, denoting its location or purpose.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.2.3.7.1.2
iemStatusRelayStatus mandatory
The status of the output relay, either faultState(1) or
normalState(2).
Enumeration
Enumerated Values:
1faultState
2normalState
.1.3.6.1.4.1.318.1.1.10.2.3.7.1.3
.1.3.6.1.4.1.318.1.1.10.3.2.1 · 1 row entry · 3 columns
Allows for control of individual output relays. The number of
entries is contained in the emsStatusOutputRelayCount OID.
emsOutputRelayControlEntry entry .1.3.6.1.4.1.318.1.1.10.3.2.1.1
The output relays to control.
Indexes
emsOutputRelayControlOutputRelayIndex
Column Syntax OID
emsOutputRelayControlOutputRelayIndex mandatory
The index to the output relay entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.2.1.1.1
emsOutputRelayControlOutputRelayName mandatory
The name of the output relay.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.2.1.1.2
emsOutputRelayControlOutputRelayCommand mandatory
Getting this variable will return the output relay state. If
the output relay is closed, the immediateCloseEMS (1) value will be returned.
If the output relay is open, the immediateOpenEMS (2) value will be
returned.
Enumerationr/w
Enumerated Values:
1immediateCloseEMS
2immediateOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.2.1.1.3

emsOutletControlTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.3.1 · 1 row entry · 3 columns
Allows for control of individual outlet switches. The number of
entries is contained in the emsStatusOutletCount OID.
emsOutletControlEntry entry .1.3.6.1.4.1.318.1.1.10.3.3.1.1
The outlets to control.
Indexes
emsOutletControlOutletIndex
Column Syntax OID
emsOutletControlOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.3.1.1.1
emsOutletControlOutletName mandatory
The name of the outlet.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.3.1.1.2
emsOutletControlOutletCommand mandatory
Getting this variable will return the outlet state. If
the outlet is on, the immediateOnEMS (1) value will be returned.
If the outlet is off, the immediateOffEMS (2) value will be
returned.

Setting this v…
Enumerationr/w
Enumerated Values:
1immediateOnEMS
2immediateOffEMS
.1.3.6.1.4.1.318.1.1.10.3.3.1.1.3

emsSensorControlTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.4.1 · 1 row entry · 4 columns
Allows for control/reset of individual sensors. The number of
entries is contained in the emsStatusSensorCount OID.
emsSensorControlEntry entry .1.3.6.1.4.1.318.1.1.10.3.4.1.1
The sensors to control/reset.
Indexes
emsSensorControlSensorIndex
Column Syntax OID
emsSensorControlSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.4.1.1.1
emsSensorControlSensorSystemName mandatory
The system name of the sensor. This describes the hardware system
intent of this sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.4.1.1.2
emsSensorControlSensorUserName mandatory
The name of the sensor as given by the system user.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.4.1.1.3
emsSensorControlSensorCommand mandatory
Getting this variable will return noCommandEMS(1).

Setting this variable to resetCommandEMS(2) will issue a reset command to the
sensor. Some sensors cannot be manually reset and will not be affected
by …
Enumerationr/w
Enumerated Values:
1noCommandEMS
2resetCommandEMS
.1.3.6.1.4.1.318.1.1.10.3.4.1.1.4
.1.3.6.1.4.1.318.1.1.10.3.5.1 · 1 row entry · 3 columns
Allows for control of individual alarm devices.
Note: Some alarm devices are not controllable.  The number of
entries is contained in the emsStatusAlarmDeviceCount OID.
emsAlarmDeviceControlEntry entry .1.3.6.1.4.1.318.1.1.10.3.5.1.1
The alarm devices to control.
Indexes
emsAlarmDeviceControlDeviceIndex
Column Syntax OID
emsAlarmDeviceControlDeviceIndex mandatory
The index to the alarm device entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.5.1.1.1
emsAlarmDeviceControlDeviceName mandatory
The name of the alarm device.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.5.1.1.2
emsAlarmDeviceControlDeviceCommand mandatory
Getting this variable will return the device state. If
the device is active, the alarmDeviceOnEMS (1) value will be returned.
If the device is inactive, the alarmDeviceOffEMS (2) value will be
returned. If the device is…
Enumerationr/w
Enumerated Values:
1alarmDeviceOnEMS
2alarmDeviceOffEMS
3alarmDeviceNotInstalledEMS
.1.3.6.1.4.1.318.1.1.10.3.5.1.1.3

emsProbeConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.7.1 · 1 row entry · 22 columns
Allows for configuration of individual probes. The number of
entries is contained in the emsStatusProbeCount OID.
emsProbeConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.7.1.1
The probes to configure.
Indexes
emsProbeConfigProbeIndex
Column Syntax OID
emsProbeConfigProbeIndex mandatory
The index to the probe entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.1
emsProbeConfigProbeName mandatory
The name of the probe.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.2
emsProbeConfigProbeHighTempThresh mandatory
Probe high temperature threshold.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.3
emsProbeConfigProbeLowTempThresh mandatory
Probe low temperature threshold.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.4
emsProbeConfigProbeHighHumidityThresh mandatory
Probe high humidity threshold.

Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.5
emsProbeConfigProbeLowHumidityThresh mandatory
Probe low humidity threshold.

Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.6
emsProbeConfigProbeMaxTempThresh mandatory
Probe maximum temperature threshold.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.7
emsProbeConfigProbeMinTempThresh mandatory
Probe minimum temperature threshold.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.8
emsProbeConfigProbeDeltaTemp mandatory
Probe delta temperature.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.9
emsProbeConfigProbeMaxHumidityThresh mandatory
Probe maximum humidity threshold.

Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.10
emsProbeConfigProbeMinHumidityThresh mandatory
Probe minimum humidity threshold.

Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.11
emsProbeConfigProbeDeltaHumidity mandatory
Probe delta humidity.

Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.12
emsProbeConfigProbeSTIncTempVariance mandatory
Probe short-term increasing temperature variance used for rate of change alarms.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Ce…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.13
emsProbeConfigProbeSTIncTempTime mandatory
Probe short-term increasing temperature time used for rate of change alarms.

Values are represented in whole number minutes.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.14
emsProbeConfigProbeSTDecTempVariance mandatory
Probe short-term decreasing temperature variance used for rate of change alarms.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Ce…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.15
emsProbeConfigProbeSTDecTempTime mandatory
Probe short-term decreasing temperature time used for rate of change alarms.

Values are represented in whole number minutes.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.16
emsProbeConfigProbeLTIncTempVariance mandatory
Probe long-term increasing temperature variance used for rate of change alarms.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Cel…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.17
emsProbeConfigProbeLTIncTempTime mandatory
Probe long-term increasing temperature time used for rate of change alarms.

Values are represented in whole number hours.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.18
emsProbeConfigProbeLTDecTempVariance mandatory
Probe long-term decreasing temperature variance used for rate of change alarms.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Cel…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.19
emsProbeConfigProbeLTDecTempTime mandatory
Probe long-term decreasing temperature time used for rate of change alarms.

Values are represented in whole number hours.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.20
emsProbeConfigProbeMaxVoltThresh mandatory
Probe maximum voltage threshold in tenths of Volts.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.21
emsProbeConfigProbeMinVoltThresh mandatory
Probe minimum voltage threshold in tenths of Volts.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.7.1.1.22
.1.3.6.1.4.1.318.1.1.10.3.8.1 · 1 row entry · 3 columns
Allows for configuration of individual input contacts. The number of
entries is contained in the emsStatusInputContactCount OID.
emsInputContactConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.8.1.1
The input contacts to configure.
Indexes
emsInputContactConfigInputContactIndex
Column Syntax OID
emsInputContactConfigInputContactIndex mandatory
The index to the input contact entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.8.1.1.1
emsInputContactConfigInputContactName mandatory
The name of the input contact.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.8.1.1.2
emsInputContactConfigInputContactNormalState mandatory
Getting this variable will return the normal state of the input contact. If
the normal state is closed, the normallyClosedEMS (1) value will be returned.
If the normal state is closed, the normallyOpenEMS (2) value will…
Enumerationr/w
Enumerated Values:
1normallyClosedEMS
2normallyOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.8.1.1.3
.1.3.6.1.4.1.318.1.1.10.3.9.1 · 1 row entry · 3 columns
Allows for configuration of individual output relays. The number of
entries is contained in the emsStatusOutputRelayCount OID.
emsOutputRelayConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.9.1.1
The output relays to configure.
Indexes
emsOutputRelayConfigOutputRelayIndex
Column Syntax OID
emsOutputRelayConfigOutputRelayIndex mandatory
The index to the output relay entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.9.1.1.1
emsOutputRelayConfigOutputRelayName mandatory
The name of the output relay.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.9.1.1.2
emsOutputRelayConfigOutputRelayNormalState mandatory
Getting this variable will return the normal state of the output relay. If
the normal state is closed, the normallyClosedEMS (1) value will be returned.
If the normal state is closed, the normallyOpenEMS (2) value will …
Enumerationr/w
Enumerated Values:
1normallyClosedEMS
2normallyOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.9.1.1.3

emsOutletConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.10.1 · 1 row entry · 3 columns
Allows for configuration of individual outlets. The number of
entries is contained in the emsStatusOutletCount OID.
emsOutletConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.10.1.1
The outlets to configure.
Indexes
emsOutletConfigOutletIndex
Column Syntax OID
emsOutletConfigOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.10.1.1.1
emsOutletConfigOutletName mandatory
The name of the outlet.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.10.1.1.2
emsOutletConfigOutletNormalState mandatory
Getting this variable will return the normal state of the outlet. If
the normal state is on, the normallyOnEMS (1) value will be returned.
If the normal state is off, the normallyOffEMS (2) value will be
returned.
Enumerationr/w
Enumerated Values:
1normallyOnEMS
2normallyOffEMS
.1.3.6.1.4.1.318.1.1.10.3.10.1.1.3

emsSensorConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.11.1 · 1 row entry · 5 columns
Allows for configuration of individual sensors. The number of
entries is contained in the emsStatusSensorCount OID.
emsSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.11.1.1
The sensors to configure.
Indexes
emsSensorConfigSensorIndex
Column Syntax OID
emsSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.11.1.1.1
emsSensorConfigSensorSystemName mandatory
The system name of the sensor. This describes the hardware system
intent of this sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.11.1.1.2
emsSensorConfigSensorUserName mandatory
The name of the sensor as given by the system user.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.11.1.1.3
emsSensorConfigSensorNormalState mandatory
Getting this variable will return the normal state of the sensor. If
the normal state is closed, the normallyClosedEMS (1) value will be returned.
If the normal state is closed, the normallyOpenEMS (2) value will be
ret…
Enumerationr/w
Enumerated Values:
1normallyClosedEMS
2normallyOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.11.1.1.4
emsSensorConfigSensorAlarmDelay mandatory
The delay (in seconds) after a sensor detects an alarm condition before the
condition is reported.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.11.1.1.5

emsProbeStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.13.1 · 1 row entry · 18 columns
Allows for access of individual probes. The number of
entries is contained in the emsStatusProbeCount OID.
emsProbeStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.13.1.1
The probes to access.
Indexes
emsProbeStatusProbeIndex
Column Syntax OID
emsProbeStatusProbeIndex mandatory
The index to the probe entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.1
emsProbeStatusProbeName mandatory
The name of the probe.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.2
emsProbeStatusProbeTemperature mandatory
Probe temperature reading.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.3
emsProbeStatusProbeHighTempThresh mandatory
Probe high temperature threshold.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.4
emsProbeStatusProbeLowTempThresh mandatory
Probe low temperature threshold.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.5
emsProbeStatusProbeHumidity mandatory
Probe humidity reading.

Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.6
emsProbeStatusProbeHighHumidityThresh mandatory
Probe high humidity threshold.

Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.7
emsProbeStatusProbeLowHumidityThresh mandatory
Probe low humidity threshold.

Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.8
emsProbeStatusProbeSerialNumber mandatory
A label indicating the type (Local[L] or Remote[R]) and Number
of the probe. For example, the first local probe would be L1 and
the third remote probe would be R3.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.9
emsProbeStatusProbeCommStatus mandatory
The state of communications to the probe.
commNeverDiscovered(1) indicates there has never been communications with this device.
commsEstablished(2) indicates communication is normal and active with this device.
commsLo…
Enumeration
Enumerated Values:
1commsNeverDiscovered
2commsEstablished
3commsLost
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.10
emsProbeStatusProbeAlarmStatus mandatory
The alarm status of the probe. This integer should be interpreted
as a bit map, with each bit representing the presence or absence of
the specific alarm conditions listed below. The bit will be '1' if
the condition is…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.11
emsProbeStatusProbeMaxTempThresh mandatory
Probe maximum temperature threshold.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.12
emsProbeStatusProbeMinTempThresh mandatory
Probe minimum temperature threshold.

Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.13
emsProbeStatusProbeMaxHumidityThresh mandatory
Probe maximum humidity threshold.

Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.14
emsProbeStatusProbeMinHumidityThresh mandatory
Probe minimum humidity threshold.

Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.15
emsProbeStatusProbeVoltage mandatory
Probe voltage reading.

Values are displayed in tenths of Volts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.16
emsProbeStatusProbeMaxVoltThresh mandatory
Probe maximum voltage threshold in Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.17
emsProbeStatusProbeMinVoltThresh mandatory
Probe minimum voltage threshold in Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.18
.1.3.6.1.4.1.318.1.1.10.3.14.1 · 1 row entry · 4 columns
Allows for access of individual input contacts. The number of
entries is contained in the emsStatusInputContactCount OID.
emsInputContactStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.14.1.1
The input contacts to access.
Indexes
emsInputContactStatusInputContactIndex
Column Syntax OID
emsInputContactStatusInputContactIndex mandatory
The index to the input contact entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.14.1.1.1
emsInputContactStatusInputContactName mandatory
The name of the input contact.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.14.1.1.2
emsInputContactStatusInputContactState mandatory
Getting this variable will return the state of the input contact. If
the input contact is closed, the contactClosedEMS (1) value will be returned.
If the input contact state is open, the contactOpenEMS (2) value will be…
Enumeration
Enumerated Values:
1contactClosedEMS
2contactOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.14.1.1.3
emsInputContactStatusInputContactNormalState mandatory
Getting this variable will return the normal state of the input contact. If
the normal state is closed, the normallyClosedEMS (1) value will be returned.
If the normal state is open, the normallyOpenEMS (2) value will b…
Enumeration
Enumerated Values:
1normallyClosedEMS
2normallyOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.14.1.1.4
.1.3.6.1.4.1.318.1.1.10.3.15.1 · 1 row entry · 4 columns
Allows for access of individual output relays. The number of
entries is contained in the emsStatusOutputRelayCount OID.
emsOutputRelayStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.15.1.1
The output relays to access.
Indexes
emsOutputRelayStatusOutputRelayIndex
Column Syntax OID
emsOutputRelayStatusOutputRelayIndex mandatory
The index to the output relay entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.15.1.1.1
emsOutputRelayStatusOutputRelayName mandatory
The name of the output relay.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.15.1.1.2
emsOutputRelayStatusOutputRelayState mandatory
Getting this variable will return the state of the output relay. If
the output relay is closed, the relayClosedEMS (1) value will be returned.
If the output relay is open, the relayOpenEMS (2) value will be
returned.
Enumeration
Enumerated Values:
1relayClosedEMS
2relayOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.15.1.1.3
emsOutputRelayStatusOutputRelayNormalState mandatory
Getting this variable will return the normal state of the output relay. If
the normal state is closed, the normallyClosedEMS (1) value will be returned.
If the normal state is open, the normallyOpenEMS (2) value will be…
Enumeration
Enumerated Values:
1normallyClosedEMS
2normallyOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.15.1.1.4

emsOutletStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.16.1 · 1 row entry · 4 columns
Allows for access of individual outlets. The number of
entries is contained in the emsStatusOutletCount OID.
emsOutletStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.16.1.1
The outlets to access.
Indexes
emsOutletStatusOutletIndex
Column Syntax OID
emsOutletStatusOutletIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.16.1.1.1
emsOutletStatusOutletName mandatory
The name of the outlet.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.16.1.1.2
emsOutletStatusOutletState mandatory
Getting this variable will return the state of the outlet. If
the outlet is on, the outletOnEMS (1) value will be returned.
If the outlet is off, the outletOffEMS (2) value will be
returned.
Enumeration
Enumerated Values:
1outletOnEMS
2outletOffEMS
.1.3.6.1.4.1.318.1.1.10.3.16.1.1.3
emsOutletStatusOutletNormalState mandatory
Getting this variable will return the normal state of the outlet. If
the normal state is on, the normallyOnEMS (1) value will be returned.
If the normal state is off, the normallyOffEMS (2) value will be
returned.
Enumeration
Enumerated Values:
1normallyOnEMS
2normallyOffEMS
.1.3.6.1.4.1.318.1.1.10.3.16.1.1.4
.1.3.6.1.4.1.318.1.1.10.3.17.1 · 1 row entry · 3 columns
Allows for access of individual alarm devices. The number of
entries is contained in the emsStatusAlarmDeviceCount OID.
emsAlarmDeviceStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.17.1.1
The alarm devices to access.
Indexes
emsAlarmDeviceStatusDeviceIndex
Column Syntax OID
emsAlarmDeviceStatusDeviceIndex mandatory
The index to the alarm device entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.17.1.1.1
emsAlarmDeviceStatusDeviceName mandatory
The name of the alarm device.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.17.1.1.2
emsAlarmDeviceStatusDeviceState mandatory
Getting this variable will return the device state. If
the device is active, the alarmDeviceOnEMS (1) value will be returned.
If the device is inactive, the alarmDeviceOffEMS (2) value will be
returned. If the device i…
Enumeration
Enumerated Values:
1alarmDeviceOnEMS
2alarmDeviceOffEMS
3alarmDeviceNotInstalledEMS
.1.3.6.1.4.1.318.1.1.10.3.17.1.1.3

emsSensorStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.18.1 · 1 row entry · 6 columns
Allows for access of individual sensors. The number of
entries is contained in the emsStatusSensorCount OID.
emsSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.18.1.1
The sensors to access.
Indexes
emsSensorStatusSensorIndex
Column Syntax OID
emsSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.18.1.1.1
emsSensorStatusSensorSystemName mandatory
The system name of the sensor. This describes the hardware system
intent of this sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.18.1.1.2
emsSensorStatusSensorName mandatory
The name of the sensor as given by the system user.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.18.1.1.3
emsSensorStatusSensorState mandatory
Getting this variable will return the sensor state. If the sensor is faulted,
the sensorFaultedEMS (1) value will be returned.
If the sensor is not faulted, the sensorOKEMS (2) value will be
returned. If the sensor is n…
Enumeration
Enumerated Values:
1sensorFaultedEMS
2sensorOKEMS
3sensorNotInstalledEMS
.1.3.6.1.4.1.318.1.1.10.3.18.1.1.4
emsSensorStatusSensorNormalState mandatory
Getting this variable will return the normal state of the sensor. If
the normal state is closed, the normallyClosedEMS (1) value will be returned.
If the normal state is closed, the normallyOpenEMS (2) value will be
ret…
Enumeration
Enumerated Values:
1normallyClosedEMS
2normallyOpenEMS
.1.3.6.1.4.1.318.1.1.10.3.18.1.1.5
emsSensorStatusSensorAlarmDelay mandatory
The delay (in seconds) after a sensor detects an alarm condition before the
condition is reported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.18.1.1.6
.1.3.6.1.4.1.318.1.1.10.3.19.1 · 1 row entry · 4 columns
Allows for the configuration of individual sensors.
emsSmokeSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.19.1.1
The sensors to configure.
Indexes
emsSmokeSensorConfigSensorIndex
Column Syntax OID
emsSmokeSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.19.1.1.1
emsSmokeSensorConfigSensorName mandatory
The user defined name of the smoke sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.1.1.2
emsSmokeSensorConfigSensorLocation mandatory
The user defined location of the smoke sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.1.1.3
emsSmokeSensorConfigSensorSeverity mandatory
The severity of the alarm that will be triggered when
the smoke sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.3.19.1.1.4
.1.3.6.1.4.1.318.1.1.10.3.19.2 · 1 row entry · 4 columns
Allows for the configuration of individual sensors.
emsVibrationSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.19.2.1
The sensors to configure.
Indexes
emsVibrationSensorConfigSensorIndex
Column Syntax OID
emsVibrationSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.19.2.1.1
emsVibrationSensorConfigSensorName mandatory
The user defined name of the vibration sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.2.1.2
emsVibrationSensorConfigSensorLocation mandatory
The user defined location of the vibration sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.2.1.3
emsVibrationSensorConfigSensorSeverity mandatory
The severity of the alarm that will be triggered when
the vibration sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.3.19.2.1.4
.1.3.6.1.4.1.318.1.1.10.3.19.3 · 1 row entry · 4 columns
Allows for the configuration of individual sensors.
emsFluidSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.19.3.1
The sensors to configure.
Indexes
emsFluidSensorConfigSensorIndex
Column Syntax OID
emsFluidSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.19.3.1.1
emsFluidSensorConfigSensorName mandatory
The user defined name of the fluid sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.3.1.2
emsFluidSensorConfigSensorLocation mandatory
The user defined location of the fluid sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.3.1.3
emsFluidSensorConfigSensorSeverity mandatory
The severity of the alarm that will be triggered when
the fluid sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.3.19.3.1.4
.1.3.6.1.4.1.318.1.1.10.3.19.4 · 1 row entry · 4 columns
Allows for the configuration of individual sensors.
emsDoorSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.19.4.1
The sensors to configure.
Indexes
emsDoorSensorConfigSensorIndex
Column Syntax OID
emsDoorSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.19.4.1.1
emsDoorSensorConfigSensorName mandatory
The user defined name of the door sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.4.1.2
emsDoorSensorConfigSensorLocation mandatory
The user defined location of the door sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.4.1.3
emsDoorSensorConfigSensorSeverity mandatory
The severity of the alarm that will be triggered when
the door sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.3.19.4.1.4

emsLeakRopeConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.19.5 · 1 row entry · 4 columns
Allows for the configuration of an individual leak rope.
emsLeakRopeConfigEntry entry .1.3.6.1.4.1.318.1.1.10.3.19.5.1
The leak rope to configure.
Indexes
emsLeakRopeConfigIndex
Column Syntax OID
emsLeakRopeConfigIndex mandatory
The index of the leak rope entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.19.5.1.1
emsLeakRopeConfigName mandatory
The user-defined name of the leak rope.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.5.1.2
emsLeakRopeConfigLocation mandatory
The user-defined location of the leak rope.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.19.5.1.3
emsLeakRopeConfigSeverity mandatory
The severity of the alarm that will be triggered when the leak rope is activated.
Enumeration
Enumerated Values:
1critical
2major
3minor
4warning
5informational
.1.3.6.1.4.1.318.1.1.10.3.19.5.1.4
.1.3.6.1.4.1.318.1.1.10.3.20.2 · 1 row entry · 6 columns
Allows for the access of individual sensors.
emsSmokeSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.20.2.1
The sensor to access.
Indexes
emsSmokeSensorStatusSensorIndex
Column Syntax OID
emsSmokeSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.20.2.1.1
emsSmokeSensorStatusSensorName mandatory
The user defined name of the smoke sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.2.1.2
emsSmokeSensorStatusSensorLocation mandatory
The user defined location of the smoke sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.2.1.3
emsSmokeSensorStatusSensorState mandatory
The state of the smoke sensor.
smokeDetected (1) indicates there is smoke.
noSmoke (2) indicates there is no smoke.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1smokeDetected
2noSmoke
3unknown
.1.3.6.1.4.1.318.1.1.10.3.20.2.1.4
emsSmokeSensorStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the smoke sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.3.20.2.1.5
emsSmokeSensorCommStatus mandatory
The communication status of the smoke sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.3.20.2.1.6
.1.3.6.1.4.1.318.1.1.10.3.20.4 · 1 row entry · 6 columns
Allows for the access of individual sensors.
emsVibrationSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.20.4.1
The sensor to access.
Indexes
emsVibrationSensorStatusSensorIndex
Column Syntax OID
emsVibrationSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.20.4.1.1
emsVibrationSensorStatusSensorName mandatory
The user defined name of the vibration sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.4.1.2
emsVibrationSensorStatusSensorLocation mandatory
The user defined location of the vibration sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.4.1.3
emsVibrationSensorStatusSensorState mandatory
The state of the vibration sensor.
vibrationDetected (1) indicates there is vibration.
noVibration (2) indicates there is no vibration.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1vibrationDetected
2noVibration
3unknown
.1.3.6.1.4.1.318.1.1.10.3.20.4.1.4
emsVibrationSensorStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the vibration sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.3.20.4.1.5
emsVibrationSensorCommStatus mandatory
The communication status of the vibration sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.3.20.4.1.6
.1.3.6.1.4.1.318.1.1.10.3.20.6 · 1 row entry · 6 columns
Allows for the access of individual sensors.
emsFluidSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.20.6.1
The sensors to access.
Indexes
emsFluidSensorStatusSensorIndex
Column Syntax OID
emsFluidSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.20.6.1.1
emsFluidSensorStatusSensorName mandatory
The user defined name of the fluid sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.6.1.2
emsFluidSensorStatusSensorLocation mandatory
The user defined location of the fluid sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.6.1.3
emsFluidSensorStatusSensorState mandatory
The state of the fluid sensor.
fluidDetected (1) indicates there is fluid leak.
noFluid (2) indicates there is no fluid leak.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1fluidDetected
2noFluid
3unknown
.1.3.6.1.4.1.318.1.1.10.3.20.6.1.4
emsFluidSensorStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the fluid sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.3.20.6.1.5
emsFluidSensorCommStatus mandatory
The communication status of the fluid sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.3.20.6.1.6
.1.3.6.1.4.1.318.1.1.10.3.20.8 · 1 row entry · 6 columns
Allows for the access of individual sensors.
emsDoorSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.20.8.1
The sensor to access.
Indexes
emsDoorSensorStatusSensorIndex
Column Syntax OID
emsDoorSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.20.8.1.1
emsDoorSensorStatusSensorName mandatory
The user defined name of the door sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.8.1.2
emsDoorSensorStatusSensorLocation mandatory
The user defined location of the door sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.8.1.3
emsDoorSensorStatusSensorState mandatory
The state of the door sensor.
open (1) indicates door open.
closed (2) indicates door closed.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.10.3.20.8.1.4
emsDoorSensorStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the door sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.3.20.8.1.5
emsDoorSensorCommStatus mandatory
The communication status of the door sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.3.20.8.1.6

emsLeakRopeStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.3.20.10 · 1 row entry · 6 columns
Allows for the access of individual leak ropes.
emsLeakRopeStatusEntry entry .1.3.6.1.4.1.318.1.1.10.3.20.10.1
The leak rope to access.
Indexes
emsLeakRopeStatusIndex
Column Syntax OID
emsLeakRopeStatusIndex mandatory
The index of the leak rope entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.3.20.10.1.1
emsLeakRopeStatusName mandatory
The user defined name of the leak rope.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.10.1.2
emsLeakRopeStatusLocation mandatory
The user defined location of the leak rope.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.3.20.10.1.3
emsLeakRopeStatusState mandatory
The state of the leak rope.
The values can be noleak(1), leakdetected(2), or unknown(3).
Enumeration
Enumerated Values:
1noleak
2leakdetected
3unknown
.1.3.6.1.4.1.318.1.1.10.3.20.10.1.4
emsLeakRopeStatusSeverity mandatory
The severity of the alarm that will be triggered when the leak rope is activated.
Enumeration
Enumerated Values:
1critical
2major
3minor
4warning
5informational
.1.3.6.1.4.1.318.1.1.10.3.20.10.1.5
emsLeakRopeCommStatus mandatory
The communication status of the leak rope.
The values can be connected(1), disconnected(2), or commsLost(3).
Enumeration
Enumerated Values:
1connected
2disconnected
3commsLost
.1.3.6.1.4.1.318.1.1.10.3.20.10.1.6

memModulesStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.1.2 · 1 row entry · 7 columns
Allows for getting status information from the modules
attached to the system.
memModulesStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.1.2.1
The unit to get data from.
Indexes
memModulesStatusModuleNumber
Column Syntax OID
memModulesStatusModuleNumber mandatory
The module number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.1.2.1.1
memModulesStatusModuleName mandatory
The module name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.1.2.1.2
memModulesStatusModuleLocation mandatory
The location of the module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.1.2.1.3
memModulesStatusModelNumber mandatory
The model number of the module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.1.2.1.4
memModulesStatusSerialNumber mandatory
The serial number of the module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.1.2.1.5
memModulesStatusFirmwareRev mandatory
The firmware revision of the module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.1.2.1.6
memModulesStatusHardwareRev mandatory
The hardware revision.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.1.2.1.7

memModulesConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.1.4 · 1 row entry · 3 columns
Allows for getting status information from the modules
attached to the system.
memModulesConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.1.4.1
The unit to get data from.
Indexes
memModulesConfigModuleNumber
Column Syntax OID
memModulesConfigModuleNumber mandatory
The module number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.1.4.1.1
memModulesConfigModuleName mandatory
The module name.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.1.4.1.2
memModulesConfigModuleLocation mandatory
The location of the module.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.1.4.1.3

memSensorsStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.2.3 · 1 row entry · 10 columns
Allows for getting sensor status information.
memSensorsStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.2.3.1
The unit to get data from.
Indexes
memSensorsStatusModuleNumber memSensorsStatusSensorNumber
Column Syntax OID
memSensorsStatusModuleNumber mandatory
The number of the module that the sensor is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.1
memSensorsStatusSensorNumber mandatory
The number of this sensor on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.2
memSensorsStatusSensorName mandatory
The sensor name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.3
memSensorsStatusSensorLocation mandatory
The location of the sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.4
memSensorsTemperature mandatory
The sensor's current temperature reading.
Units are displayed in the scale shown in
the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.5
memSensorsHumidity mandatory
The current humidity reading from the sensor.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.6
memSensorsCommStatus mandatory
The communications status of the sensor.
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.7
memSensorsAlarmStatus mandatory
The alarm status of the sensor.
memWarning is not applicable to voltage sensor.
Enumeration
Enumerated Values:
1memNormal
2memWarning
3memCritical
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.8
memSensorsTemperatureHighPrec mandatory
The current temperature is displayed in tenths of degrees in the scale
shown in the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.9
memSensorsVoltage mandatory
The sensor's current voltage reading.

Values are displayed in tenths of Volts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.3.1.10

memSensorsConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.2.5 · 1 row entry · 25 columns
Allows for getting configuration information from
sensors attached to the system.
memSensorsConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.2.5.1
The unit to get data from.
Indexes
memSensorsConfigModuleNumber memSensorsConfigSensorNumber
Column Syntax OID
memSensorsConfigModuleNumber mandatory
The number of the module that the sensor is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.1
memSensorsConfigSensorNumber mandatory
The number of this sensor on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.2
memSensorsName mandatory
A descriptive name for the sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.3
memSensorsLocation mandatory
The location of the sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.4
memSensorsAlarmGeneration mandatory
Enable or disable alarm generation on this sensor.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.5
memSensorsTempMaxThresh mandatory
The temperature at which the MEM will generate a maximum
temperature threshold violation alarm on this sensor.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.6
memSensorsTempHighThresh mandatory
The temperature at which the MEM will generate a high
temperature threshold violation alarm on this sensor.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.7
memSensorsTempLowThresh mandatory
The temperature at which the MEM will generate a low
temperature threshold violation alarm on this sensor.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.8
memSensorsTempMinThresh mandatory
The temperature at which the MEM will generate a minimum
temperature threshold violation alarm on this sensor.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.9
memSensorsTempThreshHysteresis mandatory
The change in temperature required to cause a
temperature alarm to change from an active to an inactive state.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.10
memSensorsTempShortDecRateThreshValue mandatory
The value of the temperature short-term decreasing rate
time that will cause an alarm to be generated.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.11
memSensorsTempShortDecRateThreshTime mandatory
The time over which the temperature may not decrease
beyond the value specified by the temperature short-term
decreasing rate threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.12
memSensorsTempShortIncRateThreshValue mandatory
The value of the temperature short-term increasing rate
time that will cause an alarm to be generated.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.13
memSensorsTempShortIncRateThreshTime mandatory
The time over which the temperature may not increase
beyond the value specified by the temperature short-term
increasing rate threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.14
memSensorsTempLongDecRateThreshValue mandatory
The value of the temperature long-term decreasing rate
time that will cause an alarm to be generated.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.15
memSensorsTempLongDecRateThreshTime mandatory
The time over which the temperature may not decrease
beyond the value specified by the temperature long-term
decreasing rate threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.16
memSensorsTempLongIncRateThreshValue mandatory
The value of the temperature long-term increasing rate
time that will cause an alarm to be generated.
The temperature scale is based on the memSensorsStatusSysTempUnits OID.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.17
memSensorsTempLongIncRateThreshTime mandatory
The time over which the temperature may not increase
beyond the value specified by the temperature long-term
increasing rate threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.18
memSensorsHumidityMaxThresh mandatory
The humidity at which the maximum humidity threshold alarm
will be generated.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.19
memSensorsHumidityHighThresh mandatory
The humidity at which the high humidity threshold alarm
will be generated.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.20
memSensorsHumidityLowThresh mandatory
The humidity at which the low humidity threshold alarm
will be generated.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.21
memSensorsHumidityMinThresh mandatory
The humidity at which the minimum humidity threshold alarm
will be generated.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.22
memSensorsHumidityThreshHysteresis mandatory
The change in humidity required to cause an active humidity
alarm to change to the inactive state.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.23
memSensorsVoltMaxThresh mandatory
The voltage in tenths of volts at which the MEM will generate a maximum
voltage threshold violation alarm on this sensor.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.24
memSensorsVoltMinThresh mandatory
The voltage in tenths of volts at which the MEM will generate a minimum
voltage threshold violation alarm on this sensor.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.2.5.1.25

memInputsStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.3.2 · 1 row entry · 8 columns
Allows for getting input status information.
memInputsStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.3.2.1
The unit to get data from.
Indexes
memInputsStatusModuleNumber memInputsStatusInputNumber
Column Syntax OID
memInputsStatusModuleNumber mandatory
The number of the module that the input is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.3.2.1.1
memInputsStatusInputNumber mandatory
The number of this input on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.3.2.1.2
memInputsStatusInputName mandatory
The input name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.2.1.3
memInputsStatusInputLocation mandatory
The location of the input.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.2.1.4
memInputsStatusCurrentState mandatory
The current state of the input. This OID will return
inputStateNotAplicable(4) for analog input types.
Enumeration
Enumerated Values:
1inputClosedHighMEM
2inputOpenLowMEM
3inputDisabled
4inputStateNotApplicable
.1.3.6.1.4.1.318.1.1.10.4.3.2.1.5
memInputsStatusCurrentAnalogValue mandatory
The current analog value of the input in the units defined
by the user.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.2.1.6
memInputsStatusAlarmStatus mandatory
The alarm status of the input.
Enumeration
Enumerated Values:
1memNormal
2memWarning
3memCritical
.1.3.6.1.4.1.318.1.1.10.4.3.2.1.7
memInputsCommStatus mandatory
The communications status of the input. This OID is only supported by NBRK0200.
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.10.4.3.2.1.8

memInputsConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.3.4 · 1 row entry · 25 columns
Allows for getting input configuration information.
memInputsConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.3.4.1
The unit to get data from.
Indexes
memInputsConfigModuleNumber memInputsConfigInputNumber
Column Syntax OID
memInputsConfigModuleNumber mandatory
The number of the module that the input is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.1
memInputsConfigInputNumber mandatory
The number of this input on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.2
memInputName mandatory
The name of the input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.3
memInputLocation mandatory
The location of the input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.4
memInputType mandatory
The type of input this contact will take.
Enumerationr/w
Enumerated Values:
1noConnection
2dryContact
3digital
4analogmAmps
5analogVolts
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.5
memInputAlarmGeneration mandatory
Enable or disable alarm generation on this input.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.6
memInputNormalState mandatory
Defines the normal (no alarm) state of the input.
Enumerationr/w
Enumerated Values:
1inputClosedHighMEM
2inputOpenLowMEM
3inputDisabled
4inputStateNotApplicable
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.7
memInputAbnormalSeverity mandatory
Defines the severity of the event that is associated
with the abnormal state of the input. This OID will return
inputSeverityNotApplicable(4) for analog input types.
Enumerationr/w
Enumerated Values:
1inputSeverityinformational
2inputSeveritywarning
3inputSeveritysevere
4inputSeverityNotApplicable
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.8
memInputNumberCalibrationPoints mandatory
The number of calibration points that are required for
this input.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.9
memInputAnalogCalibrationPoint1 mandatory
The electrical value that the input sensor will measure at the
first calibration point.
This OID is relevant only for inputs configured as analog type (ma or V).
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.10
memInputAnalogCalibrationPoint2 mandatory
The electrical value that the input sensor will measure at the
second calibration point.
This OID is relevant only for inputs configured as analog type (ma or V).
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.11
memInputAnalogCalibrationPoint3 mandatory
The electrical value that the input sensor will measure at the
third calibration point.
This OID is relevant only for inputs configured as analog type (ma or V).
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.12
memInputAnalogCalibrationPoint4 mandatory
The electrical value that the input sensor will measure at the
fourth calibration point.
This OID is relevant only for inputs configured as analog type (ma or V).
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.13
memInputAnalogCalibrationPoint5 mandatory
The electrical value that the input sensor will measure at the
fifth calibration point.
This OID is relevant only for inputs configured as analog type (ma or V).
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.14
memInputAnalogCalibrationPoint1Value mandatory
The value of the input, in units of measure defined by
the user, that corresponds to the current setting at the
first calibration point.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.15
memInputAnalogCalibrationPoint2Value mandatory
The value of the input, in units of measure defined by
the user, that corresponds to the current setting at the
second calibration point.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.16
memInputAnalogCalibrationPoint3Value mandatory
The value of the input, in units of measure defined by
the user, that corresponds to the current setting at the
third calibration point.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.17
memInputAnalogCalibrationPoint4Value mandatory
The value of the input, in units of measure defined by
the user, that corresponds to the current setting at the
fourth calibration point.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.18
memInputAnalogCalibrationPoint5Value mandatory
The value of the input, in units of measure defined by
the user, that corresponds to the current setting at the
fifth calibration point.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.19
memInputAnalogMeasurementUnits mandatory
The units of measure to be used for this input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.20
memInputAnalogMaxThresh mandatory
The input value at which a maximum threshold violation
alarm will be generated on this input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.21
memInputAnalogHighThresh mandatory
The input value at which a high threshold violation
alarm will be generated on this input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.22
memInputAnalogLowThresh mandatory
The input value at which a low threshold violation
alarm will be generated on this input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.23
memInputAnalogMinThresh mandatory
The input value at which a minimum threshold violation
alarm will be generated on this input.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.24
memInputAnalogThreshHysteresis mandatory
The change in value required to cause an alarm on this input
to change from active to inactive.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.3.4.1.25

memOutputStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.4.2 · 1 row entry · 6 columns
Allows for getting output status information.
memOutputStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.4.2.1
The unit to get data from.
Indexes
memOutputStatusModuleNumber memOutputStatusOutputNumber
Column Syntax OID
memOutputStatusModuleNumber mandatory
The number of the module that the output is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.4.2.1.1
memOutputStatusOutputNumber mandatory
The number of this output on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.4.2.1.2
memOutputStatusOutputName mandatory
The output name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.4.2.1.3
memOutputStatusOutputLocation mandatory
The location of the output.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.4.2.1.4
memOutputStatusCurrentState mandatory
The state of the output.
Enumeration
Enumerated Values:
1memOutputClosed
2memOutputOpen
.1.3.6.1.4.1.318.1.1.10.4.4.2.1.5
memOutputStatusAlarmState mandatory
The alarm state of the output.
Enumeration
Enumerated Values:
1memOutputNormal
2memOutputAbnormal
.1.3.6.1.4.1.318.1.1.10.4.4.2.1.6

memOutputConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.4.4 · 1 row entry · 6 columns
Allows for getting output configuration information.
memOutputConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.4.4.1
The unit to get data from.
Indexes
memOutputConfigModuleNumber memOutputConfigOutputNumber
Column Syntax OID
memOutputConfigModuleNumber mandatory
The number of the module that the output is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.4.4.1.1
memOutputConfigOutputNumber mandatory
The number of this output on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.4.4.1.2
memOutputName mandatory
The name of the output.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.4.4.1.3
memOutputLocation mandatory
The location of the output.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.4.4.1.4
memOutputNormalState mandatory
The state of the output that will not generate an alarm.
Enumerationr/w
Enumerated Values:
1memOutputClosed
2memOutputOpen
.1.3.6.1.4.1.318.1.1.10.4.4.4.1.5
memOutputAction mandatory
Manual control actions for the output. SNMP get command will return the state
of the output, SNMP set of this OID controls the output.
Enumerationr/w
Enumerated Values:
1memActionClose
2memActionOpen
.1.3.6.1.4.1.318.1.1.10.4.4.4.1.6

memOutletStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.5.2 · 1 row entry · 6 columns
Allows for getting outlet status information.
memOutletStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.5.2.1
The unit to get data from.
Indexes
memOutletStatusModuleNumber memOutletStatusOutletNumber
Column Syntax OID
memOutletStatusModuleNumber mandatory
The number of the module that the outlet is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.5.2.1.1
memOutletStatusOutletNumber mandatory
The number of this outlet on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.5.2.1.2
memOutletStatusOutletName mandatory
The outlet name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.5.2.1.3
memOutletStatusOutletLocation mandatory
The location of the outlet.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.5.2.1.4
memOutletStatusCurrentState mandatory
The state of the outlet.
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.318.1.1.10.4.5.2.1.5
memOutletStatusAlarmState mandatory
The alarm state of the outlet.
Enumeration
Enumerated Values:
1memOutletNormal
2memOutletAbnormal
.1.3.6.1.4.1.318.1.1.10.4.5.2.1.6

memOutletConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.5.4 · 1 row entry · 6 columns
Allows for getting outlet configuration information.
memOutletConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.5.4.1
The unit to get data from.
Indexes
memOutletConfigModuleNumber memOutletConfigOutletNumber
Column Syntax OID
memOutletConfigModuleNumber mandatory
The number of the module that the Outlet is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.5.4.1.1
memOutletConfigOutletNumber mandatory
The number of this Outlet on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.5.4.1.2
memOutletName mandatory
The name of the Outlet.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.5.4.1.3
memOutletLocation mandatory
The location of the Outlet.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.5.4.1.4
memOutletNormalState mandatory
The state of the Outlet that will not generate an alarm.
Enumerationr/w
Enumerated Values:
1off
2on
.1.3.6.1.4.1.318.1.1.10.4.5.4.1.5
memOutletAction mandatory
Manual control actions for the Outlet. Get displays state
of outlet, set controls outlet.
Enumerationr/w
Enumerated Values:
1turnOff
2turnOn
.1.3.6.1.4.1.318.1.1.10.4.5.4.1.6

memBeaconStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.6.2 · 1 row entry · 6 columns
Allows for getting beacon status information.
memBeaconStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.6.2.1
The unit to get data from.
Indexes
memBeaconStatusModuleNumber memBeaconStatusBeaconNumber
Column Syntax OID
memBeaconStatusModuleNumber mandatory
The number of the module that the beacon is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.6.2.1.1
memBeaconStatusBeaconNumber mandatory
The number of this beacon on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.6.2.1.2
memBeaconStatusBeaconName mandatory
The beacon name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.6.2.1.3
memBeaconStatusBeaconLocation mandatory
The location of the beacon.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.6.2.1.4
memBeaconStatusCurrentState mandatory
The state of the beacon.
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.318.1.1.10.4.6.2.1.5
memBeaconStatusAlarmState mandatory
The alarm state of the beacon.
Enumeration
Enumerated Values:
1memBeaconNormal
2memBeaconAbnormal
.1.3.6.1.4.1.318.1.1.10.4.6.2.1.6

memBeaconConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.6.4 · 1 row entry · 5 columns
Allows for getting beacon configuration information.
memBeaconConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.6.4.1
The unit to get data from.
Indexes
memBeaconConfigModuleNumber memBeaconConfigBeaconNumber
Column Syntax OID
memBeaconConfigModuleNumber mandatory
The number of the module that the beacon is attached to.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.6.4.1.1
memBeaconConfigBeaconNumber mandatory
The number of this beacon on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.6.4.1.2
memBeaconConfigName mandatory
The name of the beacon.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.6.4.1.3
memBeaconConfigLocation mandatory
The location of the beacon.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.6.4.1.4
memBeaconAction mandatory
Control action (on/off) for the beacon. Setting this OID will turn the
beacon on/off. Getting this OID will respond with the current state.
Enumerationr/w
Enumerated Values:
1turnOff
2turnOn
.1.3.6.1.4.1.318.1.1.10.4.6.4.1.5
.1.3.6.1.4.1.318.1.1.10.4.7.2 · 1 row entry · 8 columns
Allows for the access of individual sensors.
memSmokeSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.2.1
The sensor to access.
Indexes
memSmokeSensorStatusModuleIndex
Column Syntax OID
memSmokeSensorStatusModuleIndex mandatory
The index to the module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.2.1.1
memSmokeSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.2.1.2
memSmokeSensorStatusSensorName mandatory
The user defined name of the smoke sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.2.1.3
memSmokeSensorStatusSensorLocation mandatory
The user defined location of the smoke sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.2.1.4
memSmokeSensorStatusSensorState mandatory
The state of the smoke sensor.
smokeDetected (1) indicates there is smoke.
noSmoke (2) indicates there is no smoke.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1smokeDetected
2noSmoke
3unknown
.1.3.6.1.4.1.318.1.1.10.4.7.2.1.5
memSmokeSensorStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the smoke sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.2.1.6
memSmokeStatusAlarmStatus mandatory
The alarm status of the smoke sensor.
Enumeration
Enumerated Values:
1memNormal
2memWarning
3memCritical
.1.3.6.1.4.1.318.1.1.10.4.7.2.1.7
memSmokeSensorCommStatus mandatory
The communication status of the smoke sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.4.7.2.1.8
.1.3.6.1.4.1.318.1.1.10.4.7.4 · 1 row entry · 8 columns
Allows for the access of individual sensors.
memVibrationSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.4.1
The sensors to access.
Indexes
memVibrationSensorStatusModuleIndex
Column Syntax OID
memVibrationSensorStatusModuleIndex mandatory
The index to the sensor module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.4.1.1
memVibrationSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.4.1.2
memVibrationSensorStatusSensorName mandatory
The user defined name of the vibration sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.4.1.3
memVibrationSensorStatusSensorLocation mandatory
The user defined location of the vibration sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.4.1.4
memVibrationSensorStatusSensorState mandatory
The state of the vibration sensor.
vibrationDetected (1) indicates there is vibration.
noVibration (2) indicates there is no vibration.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1vibrationDetected
2noVibration
3unknown
.1.3.6.1.4.1.318.1.1.10.4.7.4.1.5
memVibrationSensorStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the vibration sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.4.1.6
memVibrationStatusAlarmStatus mandatory
The alarm status of the vibration sensor.
Enumeration
Enumerated Values:
1memNormal
2memWarning
3memCritical
.1.3.6.1.4.1.318.1.1.10.4.7.4.1.7
memVibrationSensorCommStatus mandatory
The communication status of the vibration sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.4.7.4.1.8
.1.3.6.1.4.1.318.1.1.10.4.7.6 · 1 row entry · 8 columns
Allows for access of individual sensors.
memFluidSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.6.1
The sensor to access.
Indexes
memFluidSensorStatusModuleIndex
Column Syntax OID
memFluidSensorStatusModuleIndex mandatory
The index to the sensor module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.6.1.1
memFluidSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.6.1.2
memFluidSensorStatusSensorName mandatory
The user defined name of the fluid sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.6.1.3
memFluidSensorStatusSensorLocation mandatory
The user defined location of the fluid sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.6.1.4
memFluidSensorStatusSensorState mandatory
The state of the fluid sensor.
fluidDetected (1) indicates there is fluid leak.
noFluid (2) indicates there is no fluid leak.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1fluidDetected
2noFluid
3unknown
.1.3.6.1.4.1.318.1.1.10.4.7.6.1.5
memFluidSensorStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the fluid sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.6.1.6
memFluidStatusAlarmStatus mandatory
The alarm status of the fluid sensor.
Enumeration
Enumerated Values:
1memNormal
2memWarning
3memCritical
.1.3.6.1.4.1.318.1.1.10.4.7.6.1.7
memFluidSensorCommStatus mandatory
The communication status of the fluid sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.4.7.6.1.8
.1.3.6.1.4.1.318.1.1.10.4.7.8 · 1 row entry · 8 columns
Allows for the access of individual sensors.
memDoorSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.8.1
The sensor to access.
Indexes
memDoorSensorStatusModuleIndex
Column Syntax OID
memDoorSensorStatusModuleIndex mandatory
The index to the sensor module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.8.1.1
memDoorSensorStatusSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.8.1.2
memDoorSensorStatusSensorName mandatory
The user defined name of the door sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.8.1.3
memDoorSensorStatusSensorLocation mandatory
The user defined location of the door sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.8.1.4
memDoorSensorStatusSensorState mandatory
The state of the door sensor.
open (1) indicates door open.
closed (2) indicates door closed.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.10.4.7.8.1.5
memDoorSensorStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the door sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.8.1.6
memDoorStatusAlarmStatus mandatory
The alarm status of the door sensor.
Enumeration
Enumerated Values:
1memNormal
2memWarning
3memCritical
.1.3.6.1.4.1.318.1.1.10.4.7.8.1.7
memDoorSensorCommStatus mandatory
The communication status of the door sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.4.7.8.1.8
.1.3.6.1.4.1.318.1.1.10.4.7.9 · 1 row entry · 6 columns
Allows for the configuration of individual sensors.
memSmokeSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.9.1
The sensors to configure.
Indexes
memSmokeSensorConfigSensorModuleIndex
Column Syntax OID
memSmokeSensorConfigSensorModuleIndex mandatory
The index to the sensor module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.9.1.1
memSmokeSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.9.1.2
memSmokeSensorConfigSensorName mandatory
The user defined name of the smoke sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.9.1.3
memSmokeSensorConfigSensorLocation mandatory
The user defined location of the smoke sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.9.1.4
memSmokeSensorConfigSensorSeverity mandatory
The severity of the alarm that will be triggered when
the smoke sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.9.1.5
memSmokeSensorConfigAlarmGeneration mandatory
Enable or disable alarm generation on this input.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.4.7.9.1.6
.1.3.6.1.4.1.318.1.1.10.4.7.10 · 1 row entry · 6 columns
Allows for the configuration of individual sensors.
memVibrationSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.10.1
The sensor to configure.
Indexes
memVibrationSensorModuleConfigIndex
Column Syntax OID
memVibrationSensorModuleConfigIndex mandatory
The index to the sensor module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.10.1.1
memVibrationSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.10.1.2
memVibrationSensorConfigSensorName mandatory
The user defined name of the vibration sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.10.1.3
memVibrationSensorConfigSensorLocation mandatory
The user defined location of the vibration sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.10.1.4
memVibrationSensorConfigSensorSeverity mandatory
The severity of the alarm that will be triggered when
the vibration sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.10.1.5
memVibrationSensorConfigAlarmGeneration mandatory
Enable or disable alarm generation on this input.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.4.7.10.1.6
.1.3.6.1.4.1.318.1.1.10.4.7.11 · 1 row entry · 6 columns
Allows for the configuration of individual sensors.
memFluidSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.11.1
The sensor to configure.
Indexes
memFluidSensorModuleConfigIndex
Column Syntax OID
memFluidSensorModuleConfigIndex mandatory
The index to the sensor module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.11.1.1
memFluidSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.11.1.2
memFluidSensorConfigSensorName mandatory
The user defined name of the fluid sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.11.1.3
memFluidSensorConfigSensorLocation mandatory
The user defined location of the fluid sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.11.1.4
memFluidSensorConfigSensorSeverity mandatory
The severity of the alarm that will be triggered when
the fluid sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.11.1.5
memFluidSensorConfigAlarmGeneration mandatory
Enable or disable alarm generation on this input.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.4.7.11.1.6
.1.3.6.1.4.1.318.1.1.10.4.7.12 · 1 row entry · 6 columns
Allows for the configuration of individual sensors.
memDoorSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.12.1
The sensors to configure.
Indexes
memDoorSensorModuleConfigIndex
Column Syntax OID
memDoorSensorModuleConfigIndex mandatory
The index to the sensor module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.12.1.1
memDoorSensorConfigSensorIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.12.1.2
memDoorSensorConfigSensorName mandatory
The user defined name of the door sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.12.1.3
memDoorSensorConfigSensorLocation mandatory
The user defined location of the door sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.12.1.4
memDoorSensorConfigSensorSeverity mandatory
The severity of the alarm that will be triggered when
the door sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumerationr/w
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.12.1.5
memDoorSensorConfigAlarmGeneration mandatory
Enable or disable alarm generation on this input.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.4.7.12.1.6

memLeakRopeStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.7.14 · 1 row entry · 8 columns
Allows for access of individual leak ropes.
memLeakRopeStatusEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.14.1
The leak rope to access.
Indexes
memLeakRopeStatusModuleIndex
Column Syntax OID
memLeakRopeStatusModuleIndex mandatory
The index of the leak rope entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.14.1.1
memLeakRopeStatusSensorIndex mandatory
The index of the leak rope sensor.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.14.1.2
memLeakRopeStatusSensorName mandatory
The user defined name of the leak rope sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.14.1.3
memLeakRopeStatusSensorLocation mandatory
The user-defined location of the leak rope sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.14.1.4
memLeakRopeStatusSensorState mandatory
The state of the leak rope sensor.
noleak (1) indicates there is no leak.
leakdetected (2) indicates there is a detected leak.
unknown (3) indicates the state is unknown.
Enumeration
Enumerated Values:
1noleak
2leakdetected
3unknown
.1.3.6.1.4.1.318.1.1.10.4.7.14.1.5
memLeakRopeStatusSensorSeverity mandatory
The severity of the alarm that will be triggered when
the leak rope sensor is activated. The alarms can be
critical(1), warning(2) or informational(3).
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.14.1.6
memLeakRopeAlarmStatus mandatory
The alarm status of the rope link sensor.
Enumeration
Enumerated Values:
1memNormal
2memWarning
3memCritical
.1.3.6.1.4.1.318.1.1.10.4.7.14.1.7
memLeakRopeCommStatus mandatory
The communication status of the rope link sensor.
Enumeration
Enumerated Values:
1commOK
2commLost
.1.3.6.1.4.1.318.1.1.10.4.7.14.1.8

memLeakRopeConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.10.4.7.15 · 1 row entry · 6 columns
Allows for the configuration of individual leak ropes.
memLeakRopeConfigEntry entry .1.3.6.1.4.1.318.1.1.10.4.7.15.1
The leak rope to configure.
Indexes
memLeakRopeConfigModuleIndex
Column Syntax OID
memLeakRopeConfigModuleIndex mandatory
The index of the leak rope module entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.15.1.1
memLeakRopeConfigSensorIndex mandatory
The index of the leak rope sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.4.7.15.1.2
memLeakRopeConfigSensorName mandatory
The user-defined name of the leak rope sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.15.1.3
memLeakRopeConfigSensorLocation mandatory
The user-defined location of the leak rope sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.4.7.15.1.4
memLeakRopeConfigSensorSeverity mandatory
The severity level of the leak rope sensor.
Enumeration
Enumerated Values:
1critical
2warning
3informational
.1.3.6.1.4.1.318.1.1.10.4.7.15.1.5
memLeakRopeConfigAlarmGeneration mandatory
Enable or disable alarm generation on this input.
Enumeration
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.10.4.7.15.1.6
.1.3.6.1.4.1.318.1.1.10.5.1.1 · 1 row entry · 23 columns
Allows for the access of individual sensors.
wirelessSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.10.5.1.1.1
A list of wireless sensor status table entries.
Indexes
wirelessSensorStatusIndex
Column Syntax OID
wirelessSensorStatusIndex mandatory
The index to the sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.1
wirelessSensorStatusExtAddr mandatory
The extended address is the combination of the unique 10 byte
MAC address of the sensor concatenated with its short address.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.2
wirelessSensorStatusName mandatory
The name of the wireless sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.3
wirelessSensorStatusAlarmGeneration mandatory
Indicates whether alarm generation is enabled or disabled for the sensor.
Enumeration
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.4
wirelessSensorStatusTemperature mandatory
The current temperature are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.5
wirelessSensorStatusHighTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.6
wirelessSensorStatusLowTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.7
wirelessSensorStatusHumidity mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.8
wirelessSensorStatusHighHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.9
wirelessSensorStatusLowHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.10
wirelessSensorStatusCommStatus mandatory
The communication status of the wireless sensor.
inactive(0) indicates sensor is in the wireless network but not sending information.
active(1) indicates wireless sensor is live and sending information.
Enumeration
Enumerated Values:
0inactive
1active
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.11
wirelessSensorStatusMaxTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.12
wirelessSensorStatusMinTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.13
wirelessSensorStatusMaxHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.14
wirelessSensorStatusMinHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.15
wirelessSensorStatusBattery mandatory
Values are displayed in tenths of Volts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.16
wirelessSensorStatusLowBatteryThresh mandatory
Values are displayed in tenths of Volts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.17
wirelessSensorStatusMinBatteryThresh mandatory
Values are displayed in tenths of Volts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.18
wirelessSensorStatusRssi mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.19
wirelessSensorStatusLowRssiThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.20
wirelessSensorStatusMinRssiThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.21
wirelessSensorStatusLocation mandatory
A user-defined string identifying the location
of the wireless sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.22
wirelessSensorStatusAlarmStatus mandatory
The alarm status of the wireless sensor. This integer should be interpreted
as a bit map, with each bit representing the presence or absence of
the specific alarm conditions listed below. The bit will be '1' if
the co…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.23
.1.3.6.1.4.1.318.1.1.10.5.2.1 · 1 row entry · 26 columns
Allows for the access of individual pod sensors.
wirelessSensorPodStatusEntry entry .1.3.6.1.4.1.318.1.1.10.5.2.1.1
The sensor pod to access.
Indexes
wirelessSensorPodStatusIndex
Column Syntax OID
wirelessSensorPodStatusIndex mandatory
The index to the pod sensor entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.1
wirelessSensorPodPortIndex mandatory
The pod sensor port index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.2
wirelessSensorPodStatusExtAddr mandatory
The extended address is the combination of the unique 10 byte MAC address
of the sensor concatenated with its short address.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.3
wirelessSensorPodStatusName mandatory
The name of the sensor pod.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.4
wirelessSensorPodStatusAlarmGeneration mandatory
Status of whether alarm generation is enabled or disabled.
Enumeration
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.5
wirelessSensorPodStatusTemperature mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.6
wirelessSensorPodStatusHighTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.7
wirelessSensorPodStatusLowTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.8
wirelessSensorPodStatusHumidity mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.9
wirelessSensorPodStatusHighHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.10
wirelessSensorPodStatusLowHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.11
wirelessSensorPodStatusCommStatus mandatory
The communication status of the wireless sensor.
inactive(0) indicates pod sensor is in the wireless network but not sending information.
active(1) indicates wireless sensor is live and sending information.
Enumeration
Enumerated Values:
0inactive
1active
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.12
wirelessSensorPodStatusMaxTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.13
wirelessSensorPodStatusMinTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.14
wirelessSensorPodStatusMaxHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.15
wirelessSensorPodStatusMinHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.16
wirelessSensorPodStatusDryContactState mandatory
State of the dry contact. If the dry contact is closed,
the drycontactClosed (1) value will be returned. If the dry contact
state is open, the drycontactOpen (0) value will be returned.
Enumeration
Enumerated Values:
0drycontactOpen
1drycontactClosed
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.17
wirelessSensorPodStatusDryContactNormalState mandatory
The normal state of the dry contact. If the normal state is closed,
the normallyClosed (1) value will be returned. If the normal state is
open, the normallyOpen (0) value will be returned.
Enumeration
Enumerated Values:
0normallyOpen
1normallyClosed
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.18
wirelessSensorPodStatusBattery mandatory
Values are displayed in tenths of Volts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.19
wirelessSensorPodStatusLowBatteryThresh mandatory
Values are displayed in tenths of Volts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.20
wirelessSensorPodStatusMinBatteryThresh mandatory
Values are displayed in tenths of Volts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.21
wirelessSensorPodStatusRssi mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.22
wirelessSensorPodStatusLowRssiThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.23
wirelessSensorPodStatusMinRssiThresh mandatory
Values are represented in whole number percentage.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.24
wirelessSensorPodStatusLocation mandatory
The location of the wireless sensor pod.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.25
wirelessSensorPodStatusAlarmStatus mandatory
The alarm status of the wireless pod sensor. This integer should be interpreted
as a bit map, with each bit representing the presence or absence of
the specific alarm conditions listed below. The bit will be '1' if
th…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.26
.1.3.6.1.4.1.318.1.1.10.5.3.1 · 1 row entry · 16 columns
Allows for the configuration of individual sensors.
wirelessSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.10.5.3.1.1
The sensor to configure.
Indexes
wirelessSensorConfigIndex
Column Syntax OID
wirelessSensorConfigIndex mandatory
The index to the entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.1
wirelessSensorConfigName mandatory
The user-defined wireless sensor ID string.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.2
wirelessSensorConfigAlarmGeneration mandatory
Enable or disable alarm generation for this sensor.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.3
wirelessSensorConfigHighTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.4
wirelessSensorConfigLowTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.5
wirelessSensorConfigHighHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.6
wirelessSensorConfigLowHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.7
wirelessSensorConfigMaxTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.8
wirelessSensorConfigMinTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.9
wirelessSensorConfigMaxHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.10
wirelessSensorConfigMinHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.11
wirelessSensorConfigLowBatteryThresh mandatory
Values are displayed in tenths of Volts DC.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.12
wirelessSensorConfigMinBatteryThresh mandatory
Values are displayed in tenths of Volts DC.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.13
wirelessSensorConfigLowRssiThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.14
wirelessSensorConfigMinRssiThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.15
wirelessSensorConfigLocation mandatory
A user-defined string identifying the location of the
wireless sensor. Maximum text input is 20 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.3.1.1.16
.1.3.6.1.4.1.318.1.1.10.5.4.1 · 1 row entry · 18 columns
Allows for the configuration of individual sensors.
wirelessSensorPodConfigEntry entry .1.3.6.1.4.1.318.1.1.10.5.4.1.1
The sensor to configure.
Indexes
wirelessSensorPodConfigIndex wirelessSensorPodConfigPortIndex
Column Syntax OID
wirelessSensorPodConfigIndex mandatory
The index to the entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.1
wirelessSensorPodConfigPortIndex mandatory
The sensor pod port index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.2
wirelessSensorPodConfigName mandatory
The user defined name of the sensor pod.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.3
wirelessSensorPodConfigAlarmGeneration mandatory
Enable or disable alarm generation for this sensor.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.4
wirelessSensorPodConfigDryContactNormalState mandatory
The normal state of the dry contact. If the normal state is closed,
the normallyClosed (1) value will be returned. If the normal state is open,
the normallyOpen (0) value will be returned. Setting this variable will cha…
Enumerationr/w
Enumerated Values:
0normallyOpen
1normallyClosed
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.5
wirelessSensorPodConfigHighTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.6
wirelessSensorPodConfigLowTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.7
wirelessSensorPodConfigHighHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.8
wirelessSensorPodConfigLowHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.9
wirelessSensorPodConfigMaxTempThresh mandatory
Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.10
wirelessSensorPodConfigMinTempThresh mandatory
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.11
wirelessSensorPodConfigMaxHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.12
wirelessSensorPodConfigMinHumidityThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.13
wirelessSensorPodConfigLowBatteryThresh mandatory
Values are displayed in tenths of Volts DC.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.14
wirelessSensorPodConfigMinBatteryThresh mandatory
Values are displayed in tenths of Volts DC.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.15
wirelessSensorPodConfigLowRssiThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.16
wirelessSensorPodConfigMinRssiThresh mandatory
Values are represented in whole number percentage.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.17
wirelessSensorPodConfigLocation mandatory
A user-defined string identifying the location of the
wireless pod sensor. Maximum text input is 20 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.10.5.4.1.1.18

rPDULoadDevBankTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.2.1.6 · 1 row entry · 3 columns
Allows for getting the Bank Max Load in the Rack PDU.
rPDULoadDevBankEntry entry .1.3.6.1.4.1.318.1.1.12.2.1.6.1
The Rack PDU Banks Access.
Indexes
rPDULoadDevBankIndex
Column Syntax OID
rPDULoadDevBankIndex mandatory
The index to the Rack PDU bank entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.1.6.1.1
rPDULoadDevBankNumber mandatory
Getting this OID will return the bank number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.1.6.1.2
rPDULoadDevBankMaxLoad mandatory
Getting this OID will return the maximum rated power
that each bank of the Rack PDU can provide. It is
represented in Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.1.6.1.3
.1.3.6.1.4.1.318.1.1.12.2.1.8 · 1 row entry · 3 columns
Allows for getting the Max Outlet Load in an Outlet Monitored Rack PDU.
rPDULoadDevMaxOutletEntry entry .1.3.6.1.4.1.318.1.1.12.2.1.8.1
This gives access to Max Outlet Load of an Outlet Monitored Rack PDU
Indexes
rPDULoadDevOutletIndex
Column Syntax OID
rPDULoadDevOutletIndex mandatory
The index to the Outlet Monitored Rack PDU Max Outlet Load entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.1.8.1.1
rPDULoadDevOutletNumber mandatory
Getting this OID will return the Outlet number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.1.8.1.2
rPDULoadDevMaxOutletLoad mandatory
Getting this OID will return the maximum rated power
that each Outlet of an Outlet Monitored Rack PDU can provide. It is
represented in Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.1.8.1.3
.1.3.6.1.4.1.318.1.1.12.2.2.1 · 1 row entry · 5 columns
Allows for configuration of each Rack PDU phase.
The number of entries is contained in the
rPDULoadDevNumPhases OID.
rPDULoadPhaseConfigEntry entry .1.3.6.1.4.1.318.1.1.12.2.2.1.1
The Rack PDU phase to configure.
Indexes
rPDULoadPhaseConfigIndex
Column Syntax OID
rPDULoadPhaseConfigIndex mandatory
The index to the Rack PDU phase entry.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.12.2.2.1.1.1
rPDULoadPhaseConfigLowLoadThreshold mandatory
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less than the threshold value.

A …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.2.1.1.2
rPDULoadPhaseConfigNearOverloadThreshold mandatory
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.2.1.1.3
rPDULoadPhaseConfigOverloadThreshold mandatory
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.2.1.1.4
rPDULoadPhaseConfigAlarm mandatory
Getting this OID will return the current Phase Alarm.
Enumeration
Enumerated Values:
1noLoadAlarm
2underCurrentAlarm
3nearOverCurrentAlarm
4overCurrentAlarm
.1.3.6.1.4.1.318.1.1.12.2.2.1.1.5

rPDULoadStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.2.3.1 · 1 row entry · 5 columns
Allows for getting of status of each Rack PDU phase/bank.
The number of entries is calculated by adding
the number of phases (rPDULoadDevNumPhases OID) and
the number of banks of outlets (rPDULoadDevNumBanks)
Number of entries = #phases + #banks.
NOTE: If a device has phase and bank information, all phase information
shall precede the bank information.  If a device has total information,
it shall precede both the bank and the phase information.
rPDULoadStatusEntry entry .1.3.6.1.4.1.318.1.1.12.2.3.1.1
The Rack PDU phase/bank to gather status from.
Indexes
rPDULoadStatusIndex
Column Syntax OID
rPDULoadStatusIndex mandatory
The index to the Rack PDU phase/bank entry. All phase information will precede
any bank information
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.3.1.1.1
rPDULoadStatusLoad mandatory
Getting this OID will return the phase/bank load measured
in tenths of Amps.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.12.2.3.1.1.2
rPDULoadStatusLoadState mandatory
Getting this OID will return the phase/bank load state.

phaseLoadNormal(1) indicates that the phase/bank is
operating properly within the rPDULoadConfigLowLoadThreshold
and rPDULoadConfigNearOverloadThres…
Enumeration
Enumerated Values:
1phaseLoadNormal
2phaseLoadLow
3phaseLoadNearOverload
4phaseLoadOverload
.1.3.6.1.4.1.318.1.1.12.2.3.1.1.3
rPDULoadStatusPhaseNumber mandatory
The phase number to which this record refers.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.3.1.1.4
rPDULoadStatusBankNumber mandatory
The bank number to which this record refers. A value of 0 will be returned if
any bank is not present or if it is phase related.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.3.1.1.5
.1.3.6.1.4.1.318.1.1.12.2.4.1 · 1 row entry · 5 columns
Allows for configuration of each Rack PDU bank.
The number of entries is contained in the
rPDULoadDevNumBanks OID.
rPDULoadBankConfigEntry entry .1.3.6.1.4.1.318.1.1.12.2.4.1.1
The Rack PDU bank to configure.
Indexes
rPDULoadBankConfigIndex
Column Syntax OID
rPDULoadBankConfigIndex mandatory
The index to the Rack PDU bank entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.4.1.1.1
rPDULoadBankConfigLowLoadThreshold mandatory
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less than the threshold value.

A …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.4.1.1.2
rPDULoadBankConfigNearOverloadThreshold mandatory
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.4.1.1.3
rPDULoadBankConfigOverloadThreshold mandatory
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.2.4.1.1.4
rPDULoadBankConfigAlarm mandatory
Getting this OID will return the current Bank Alarm.
Enumeration
Enumerated Values:
1noLoadAlarm
2underCurrentAlarm
3nearOverCurrentAlarm
4overCurrentAlarm
.1.3.6.1.4.1.318.1.1.12.2.4.1.1.5

rPDUOutletPhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.3.2.1 · 1 row entry · 2 columns
Allows for management of outlets on a per phase basis.
rPDUOutletPhaseEntry entry .1.3.6.1.4.1.318.1.1.12.3.2.1.1
The phase to manage.
Indexes
rPDUOutletPhaseIndex
Column Syntax OID
rPDUOutletPhaseIndex mandatory
The index to the Switched Rack PDU phase entry.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.12.3.2.1.1.1
rPDUOutletPhaseOverloadRestriction mandatory
This OID controls the behavior of a Switched Rack PDU
phase when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will alwa…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
.1.3.6.1.4.1.318.1.1.12.3.2.1.1.2

rPDUOutletControlTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.3.3.1 · 1 row entry · 5 columns
Allows for control of the individual outlets.
The number of entries is contained in the
rPDUOutletDevNumCntrlOutlets OID.
rPDUOutletControlEntry entry .1.3.6.1.4.1.318.1.1.12.3.3.1.1
The outlet to control.
Indexes
rPDUOutletControlIndex
Column Syntax OID
rPDUOutletControlIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.3.1.1.1
rPDUOutletControlOutletName mandatory
The name of the outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.12.3.3.1.1.2
rPDUOutletControlOutletPhase mandatory
The phase/s associated with this outlet.

For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), or phase3 (…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.318.1.1.12.3.3.1.1.3
rPDUOutletControlOutletCommand mandatory
Getting this variable will return the outlet state. If
the outlet is on, the immediateOn (1) value will be returned.
If the outlet is off, the immediateOff (2) value will be
returned.


Setti…
Enumerationr/w
Enumerated Values:
1immediateOn
2immediateOff
3immediateReboot
4delayedOn
5delayedOff
6delayedReboot
7cancelPendingCommand
.1.3.6.1.4.1.318.1.1.12.3.3.1.1.4
rPDUOutletControlOutletBank mandatory
The bank associated with this outlet.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.3.1.1.5

rPDUOutletConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.3.4.1 · 1 row entry · 7 columns
Allows for configuration of individual outlets. The number of
entries is contained in the rPDUOutletDevNumCntrlOutlets OID.
rPDUOutletConfigEntry entry .1.3.6.1.4.1.318.1.1.12.3.4.1.1
The outlet to configure.
Indexes
rPDUOutletConfigIndex
Column Syntax OID
rPDUOutletConfigIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.1
rPDUOutletConfigOutletName mandatory
The name of the outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.2
rPDUOutletConfigOutletPhase mandatory
The phase/s associated with this outlet.

For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), or phase3 (…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.3
rPDUOutletConfigPowerOnTime mandatory
The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.

Allowed values are:

-1 - never power on.
0 …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.4
rPDUOutletConfigPowerOffTime mandatory
The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.

Allowed values are:

-1 - never power off.
0 - powe…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.5
rPDUOutletConfigRebootDuration mandatory
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence, before turning power back on, at the
en…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.6
rPDUOutletConfigOutletBank mandatory
The bank associated with this outlet.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.7
.1.3.6.1.4.1.318.1.1.12.3.4.3 · 1 row entry · 6 columns
Allows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU.
rPDUOutletConfigMonitoredEntry entry .1.3.6.1.4.1.318.1.1.12.3.4.3.1
This gives access to Monitored Outlet entries
Indexes
rPDUOutletConfigMonitoredIndex
Column Syntax OID
rPDUOutletConfigMonitoredIndex mandatory
The index to the RACK PDU Phase entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.3.1.1
rPDUOutletConfigMonitoredName mandatory
The name of the Monitored Outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.12.3.4.3.1.2
rPDUOutletConfigMonitoredNumber mandatory
The outlet number of an Outlet Monitored RACK PDU.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.3.1.3
rPDUOutletConfigMonitoredLowLoadThreshold mandatory
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less than the threshold value.

A …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.3.1.4
rPDUOutletConfigMonitoredNearOverloadThreshold mandatory
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.3.1.5
rPDUOutletConfigMonitoredOverloadThreshold mandatory
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.4.3.1.6

rPDUOutletStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.3.5.1 · 1 row entry · 7 columns
Allows for getting of status of individual outlets. The number of
entries is contained in the rPDUOutletDevNumCntrlOutlets OID or
rPDUOutletDevMonitoredOutlets OID.
rPDUOutletStatusEntry entry .1.3.6.1.4.1.318.1.1.12.3.5.1.1
The outlet to gather status from.
Indexes
rPDUOutletStatusIndex
Column Syntax OID
rPDUOutletStatusIndex mandatory
The index to the outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.1
rPDUOutletStatusOutletName mandatory
The name of the outlet. The maximum string size is device dependent.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.2
rPDUOutletStatusOutletPhase mandatory
The phase/s associated with this outlet.

For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), or phase3 (…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.3
rPDUOutletStatusOutletState mandatory
Getting this variable will return the outlet state. If
the outlet is on, the outletStatusOn (1) value will be returned.
If the outlet is off, the outletStatusOff (2) value will be
returned.
Enumeration
Enumerated Values:
1outletStatusOn
2outletStatusOff
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.4
rPDUOutletStatusCommandPending mandatory
Getting this variable will return the command pending
state of the outlet. If a command is pending on the
outlet, the outletStatusCommandPending (1) value
will be returned. If there is not a command pending
on the outle…
Enumeration
Enumerated Values:
1outletStatusCommandPending
2outletStatusNoCommandPending
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.5
rPDUOutletStatusOutletBank mandatory
The bank associated with this outlet.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.6
rPDUOutletStatusLoad mandatory
Getting this OID will return the measured Outlet load for
an Outlet Monitored Rack PDU in tenths of Amps. For other
models this OID is not supported.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.7

rPDUOutletBankTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.3.6.1 · 1 row entry · 2 columns
Allows for management of outlets on a per bank basis.
rPDUOutletBankEntry entry .1.3.6.1.4.1.318.1.1.12.3.6.1.1
The bank to manage.
Indexes
rPDUOutletBankIndex
Column Syntax OID
rPDUOutletBankIndex mandatory
The index to the Switched Rack PDU bank entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.3.6.1.1.1
rPDUOutletBankOverloadRestriction mandatory
This OID controls the behavior of a Switched Rack PDU
bank when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will alway…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
.1.3.6.1.4.1.318.1.1.12.3.6.1.1.2

rPDUStatusBankTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.5.2 · 1 row entry · 3 columns
Allows for getting of status of each Rack PDU Bank
rPDUStatusBankEntry entry .1.3.6.1.4.1.318.1.1.12.5.2.1
This gives access to Bank entries
Indexes
rPDUStatusBankIndex
Column Syntax OID
rPDUStatusBankIndex mandatory
The index to the RACK PDU Bank entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.5.2.1.1
rPDUStatusBankNumber mandatory
Getting this OID will return the bank number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.5.2.1.2
rPDUStatusBankState mandatory
Getting this OID will return the bank load state.

bankLoadNormal(1) indicates that the bank is
operating properly within the rPDULoadBankConfigLowLoadThreshold
and rPDULoadBankConfigNearOverloadThreshold …
Enumeration
Enumerated Values:
1bankLoadNormal
2bankLoadLow
3bankLoadNearOverload
4bankLoadOverload
.1.3.6.1.4.1.318.1.1.12.5.2.1.3

rPDUStatusPhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.5.4 · 1 row entry · 3 columns
Allows for getting of status of each Rack PDU Phase
rPDUStatusPhaseEntry entry .1.3.6.1.4.1.318.1.1.12.5.4.1
This gives access to Phase entries
Indexes
rPDUStatusPhaseIndex
Column Syntax OID
rPDUStatusPhaseIndex mandatory
The index to the RACK PDU Phase entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.5.4.1.1
rPDUStatusPhaseNumber mandatory
Getting this OID will return the phase number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.5.4.1.2
rPDUStatusPhaseState mandatory
Getting this OID will return the Phase load state.

phaseLoadNormal(1) indicates that the Phase is
operating properly within the rPDULoadPhaseConfigLowLoadThreshold
and rPDULoadPhaseConfigNearOverloadThres…
Enumeration
Enumerated Values:
1phaseLoadNormal
2phaseLoadLow
3phaseLoadNearOverload
4phaseLoadOverload
.1.3.6.1.4.1.318.1.1.12.5.4.1.3

rPDUStatusOutletTable

table mandatory
.1.3.6.1.4.1.318.1.1.12.5.6 · 1 row entry · 3 columns
Allows for getting of status of each Outlet of an Outlet Monitored Rack PDU.
rPDUStatusOutletEntry entry .1.3.6.1.4.1.318.1.1.12.5.6.1
This gives access to Outlet entries
Indexes
rPDUStatusOutletIndex
Column Syntax OID
rPDUStatusOutletIndex mandatory
The index to the RACK PDU Outlet entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.5.6.1.1
rPDUStatusOutletNumber mandatory
Getting this OID will return the Outlet number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.12.5.6.1.2
rPDUStatusOutletState mandatory
Getting this OID will return the Outlet load state.

outletLoadNormal(1) indicates that the Outlet is
operating properly within the rPDUOutletConfigMonitoredLowLoadThreshold
and rPDUOutletConfigMonitoredNe…
Enumeration
Enumerated Values:
1outletLoadNormal
2outletLoadLow
3outletLoadNearOverload
4outletLoadOverload
.1.3.6.1.4.1.318.1.1.12.5.6.1.3

airFMIdentTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.1.3 · 1 row entry · 6 columns
Allows for getting identification information
from each module in the system.
airFMIdentEntry entry .1.3.6.1.4.1.318.1.1.13.1.1.3.1
The module to get information from.
Indexes
airFMIdentModuleIndex
Column Syntax OID
airFMIdentModuleIndex mandatory
The index of the module information.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.1.3.1.1
airFMIdentModuleModelNumber mandatory
A character string identifying the
model number.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.1.3.1.2
airFMIdentModuleDateOfMfg mandatory
A character string identifying the
manufacture date.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.1.3.1.3
airFMIdentModuleSerialNumber mandatory
A character string identifying the
unit serial number.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.1.3.1.4
airFMIdentModuleFirmwareRev mandatory
A character string identifying the
firmware revision.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.1.3.1.5
airFMIdentModuleHardwareRev mandatory
A character string identifying the
hardware revision.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.1.3.1.6

airFMStatusModuleTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.2.20 · 1 row entry · 8 columns
Allows for getting information from each module
in the system.
airFMStatusModuleEntry entry .1.3.6.1.4.1.318.1.1.13.1.2.20.1
The module to get status from.
Indexes
airFMStatusModuleIndex
Column Syntax OID
airFMStatusModuleIndex mandatory
The index of the module information.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.2.20.1.1
airFMStatusModuleOutputCapacity mandatory
The module output capacity in kilowatts.
This OID has been deprecated in favor of
airFMModOutputCapacity.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.2.20.1.2
airFMStatusModuleSupplyTempC mandatory
The module supply air temperature in
tenths of degrees Celsius.
This OID has been deprecated in favor of
airFMModSupplyTempC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.2.20.1.3
airFMStatusModuleSupplyTempF mandatory
The module supply air temperature in
tenths of degrees Fahrenheit.
This OID has been deprecated in favor of
airFMModSupplyTempF.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.2.20.1.4
airFMStatusModuleSupplyHum mandatory
The module supply air humidity in tenths of percent RH.
This OID has been deprecated in favor of
airFMModSupplyHum.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.2.20.1.5
airFMStatusModuleReturnTempC mandatory
The module return air temperature in
tenths of degrees Celsius.
This OID has been deprecated in favor of
airFMModReturnTempC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.2.20.1.6
airFMStatusModuleReturnTempF mandatory
The module return air temperature in
tenths of degrees Fahrenheit.
This OID has been deprecated in favor of
airFMModReturnTempF.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.2.20.1.7
airFMStatusModuleReturnHum mandatory
The module return air humidity in tenths of percent RH.
This OID has been deprecated in favor of
airFMModReturnHum.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.2.20.1.8
.1.3.6.1.4.1.318.1.1.13.1.3.4.2 · 1 row entry · 7 columns
Allows for getting information from each system
in the group.
airFMGroupSysRolesEntry entry .1.3.6.1.4.1.318.1.1.13.1.3.4.2.1
The system to get status from.
Indexes
airFMGroupSysIndex
Column Syntax OID
airFMGroupSysIndex mandatory
The index of the system information.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.1
airFMGroupSysRoleStatus mandatory
The present mode of the System.
Enumeration
Enumerated Values:
1reserved1
2reserved2
3onLine
4idle
5loadShare
6failed
7offLine
.1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.2
airFMGroupSysPresentRole mandatory
The present role of the System in a Group.
Enumeration
Enumerated Values:
1primary
2backup
.1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.3
airFMGroupSysManualRoleSetting mandatory
The manual role setting of the System in a Group.
Only applies if Role Assignment Method is set
to static (Manually Assigned Roles).
Enumerationr/w
Enumerated Values:
1primary
2backup
.1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.4
airFMGroupSysRunHours mandatory
The total number of hours the System has been
contributing to environmental control.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.5
airFMGroupSysComm mandatory
Indicates whether a system is communicating with the
other Systems in the Group.
Enumeration
Enumerated Values:
1commLost
2commEstablished
.1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.6
airFMGroupSysIPAddress mandatory
The IP Address of the System.
RFC1155-SMIIpAddress
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.7

airFMSysInputTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.4.10.2 · 1 row entry · 6 columns
Allows for getting information from each input
contact.
airFMSysInputEntry entry .1.3.6.1.4.1.318.1.1.13.1.4.10.2.1
The input contact to obtain status from.
Indexes
airFMSysInputIndex
Column Syntax OID
airFMSysInputIndex mandatory
The number designator of the Input Contact.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.1
airFMSysInputName mandatory
The configurable name for the Input Contact. Maximum
text input is 13 characters.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.2
airFMSysInputStatus mandatory
The state of this contact: Open or Closed. A
violation will occur when this relay is not in its
normal state.
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3
airFMSysInputNormalState mandatory
Set the normal state of this contact (the state when
no alarm/event exists).
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.4
airFMSysInputDelay mandatory
Set the delay between this contact exiting its normal
state and an alarm being triggered. Measured in
seconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.5
airFMSysInputAlarmAction mandatory
Sets the behavior for this contact when it exits its
normal state.
Enumerationr/w
Enumerated Values:
1statusOnly
2minor
3major
4remoteRunStop
5nonessStop
6immShutdown
.1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.6

airFMSysOutputTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.4.11.2 · 1 row entry · 3 columns
Allows for getting information from each output relay.
airFMSysOutputEntry entry .1.3.6.1.4.1.318.1.1.13.1.4.11.2.1
The output relay to obtain status from.
Indexes
airFMSysOutputIndex
Column Syntax OID
airFMSysOutputIndex mandatory
The number designator of the output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.1
airFMSysOutputStatus mandatory
The state of this relay: Open or Closed. A violation
will occur when this relay is not in its normal state.
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.2
airFMSysOutputNormalState mandatory
Set the normal state of this relay (the state when no
alarm/event exists).
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.3
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2 · 1 row entry · 17 columns
Allows for getting alarm map information.
airFMSysAlarmMapSysEntry entry .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1
The system alarm map type to reference.
Indexes
airFMSysAlarmMapSysOutputIndex
Column Syntax OID
airFMSysAlarmMapSysOutputIndex mandatory
The index of the output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.1
airFMSysAlarmMapSysAnyAlarm mandatory
System alarm map setting for Any Alarm.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.2
airFMSysAlarmMapSystemOn mandatory
System alarm map setting for System On.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.3
airFMSysAlarmMapSystemOffline mandatory
System alarm map setting for System Offline.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.4
airFMSysAlarmMapSysHighEnvTemp mandatory
System alarm map setting for High Environmental
Temperature.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.5
airFMSysAlarmMapSysLowEnvTemp mandatory
System alarm map setting for Low Environmental
Temperature.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.6
airFMSysAlarmMapSysHighEnvHum mandatory
System alarm map setting for High Environmental
Humidity.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.7
airFMSysAlarmMapSysLowEnvHum mandatory
System alarm map setting for Low Environmental
Humidity.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.8
airFMSysAlarmMapSysFireDet mandatory
System alarm map setting for Fire Detected.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.9
airFMSysAlarmMapSysSmokeDet mandatory
System alarm map setting for Smoke Detected.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.10
airFMSysAlarmMapSysEconIsol mandatory
System alarm map setting for Econ Isolator.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.11
airFMSysAlarmMapSysSupplySensFail mandatory
System alarm map setting for Supply Sensor Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.12
airFMSysAlarmMapSysReturnSensFail mandatory
System alarm map setting for Return Sensor Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.13
airFMSysAlarmMapSysRemSensRemoved mandatory
System alarm map setting for Remote Sensor Removed.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.14
airFMSysAlarmMapSysPrimSensFail mandatory
System alarm map setting for Primary Sensor Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.15
airFMSysAlarmMapSysSecSensFail mandatory
System alarm map setting for Secondary Sensor Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.16
airFMSysAlarmMapSysSecSensActive mandatory
System alarm map setting for Secondary Sensor Active.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.17
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2 · 1 row entry · 15 columns
Allows for getting alarm map information.
airFMSysAlarmMapMainModEntry entry .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1
The main module alarm map type to reference.
Indexes
airFMSysAlarmMapMainModOutputIndex
Column Syntax OID
airFMSysAlarmMapMainModOutputIndex mandatory
The index of the output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.1
airFMSysAlarmMapMainModAnyAlarm mandatory
Main Module alarm map setting for Any Alarm.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.2
airFMSysAlarmMapMainModMaintReq mandatory
Main Module alarm map setting for Module Maintenance
Required.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.3
airFMSysAlarmMapMainModCoolFail mandatory
Main Module alarm map setting for Module Cooling
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.4
airFMSysAlarmMapMainModHighSupplyTemp mandatory
Main Module alarm map setting for High Supply
Temperature.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.5
airFMSysAlarmMapMainModLowSupplyTemp mandatory
Main Module alarm map setting for Low Supply
Temperature.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.6
airFMSysAlarmMapMainModHumFail mandatory
Main Module alarm map setting for Humidifier Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.7
airFMSysAlarmMapMainModHumReplCyl mandatory
Main Module alarm map setting for Humidifier Replace
Cylinder.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.8
airFMSysAlarmMapMainModCondPumpFail mandatory
Main Module alarm map setting for Condensate Pump
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.9
airFMSysAlarmMapMainModBlwrCntl1Fail mandatory
Main Module alarm map setting for Blower Controller 1
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.10
airFMSysAlarmMapMainModBlwrCntl2Fail mandatory
Main Module alarm map setting for Blower Controller 2
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.11
airFMSysAlarmMapMainModHighFltrDP mandatory
Main Module alarm map setting for High Filter
Differential Pressure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.12
airFMSysAlarmMapMainModLowAirFlow mandatory
Main Module alarm map setting for Low Air Flow.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.13
airFMSysAlarmMapMainModAirBlckIntOpen mandatory
Main Module alarm map setting for Air Block Interlock
Open.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.14
airFMSysAlarmMapMainModWaterDetected mandatory
Main Module alarm map setting for Water Detected.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.15
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2 · 1 row entry · 15 columns
Allows for getting alarm map information.
airFMSysAlarmMapExpMod1Entry entry .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1
The expansion module 1 alarm map type to reference.
Indexes
airFMSysAlarmMapExpMod1OutputIndex
Column Syntax OID
airFMSysAlarmMapExpMod1OutputIndex mandatory
The index of the output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.1
airFMSysAlarmMapExpMod1AnyAlarm mandatory
Exp Module 1 alarm map setting for Any Alarm.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.2
airFMSysAlarmMapExpMod1MaintReq mandatory
Exp Module 1 alarm map setting for Module Maintenance
Required.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.3
airFMSysAlarmMapExpMod1CoolFail mandatory
Exp Module 1 alarm map setting for Module Cooling
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.4
airFMSysAlarmMapExpMod1HighSupplyTemp mandatory
Exp Module 1 alarm map setting for High Supply
Temperature.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.5
airFMSysAlarmMapExpMod1LowSupplyTemp mandatory
Exp Module 1 alarm map setting for Low Supply
Temperature.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.6
airFMSysAlarmMapExpMod1HumFail mandatory
Exp Module 1 alarm map setting for Humidifier Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.7
airFMSysAlarmMapExpMod1HumReplCyl mandatory
Exp Module 1 alarm map setting for Humidifier Replace
Cylinder.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.8
airFMSysAlarmMapExpMod1CondPumpFail mandatory
Exp Module 1 alarm map setting for Condensate Pump
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.9
airFMSysAlarmMapExpMod1BlwrCntl1Fail mandatory
Exp Module 1 alarm map setting for Blower Controller 1
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.10
airFMSysAlarmMapExpMod1BlwrCntl2Fail mandatory
Exp Module 1 alarm map setting for Blower Controller 2
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.11
airFMSysAlarmMapExpMod1HighFltrDP mandatory
Exp Module 1 alarm map setting for High Filter
Differential Pressure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.12
airFMSysAlarmMapExpMod1LowAirFlow mandatory
Exp Module 1 alarm map setting for Low Air Flow.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.13
airFMSysAlarmMapExpMod1AirBlckIntOpen mandatory
Exp Module 1 alarm map setting for Air Block Interlock
Open.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.14
airFMSysAlarmMapExpMod1WaterDetected mandatory
Exp Module 1 alarm map setting for Water Detected.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.15
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2 · 1 row entry · 15 columns
Allows for getting alarm map information.
airFMSysAlarmMapExpMod2Entry entry .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1
The expansion module 2 alarm map type to reference.
Indexes
airFMSysAlarmMapExpMod2OutputIndex
Column Syntax OID
airFMSysAlarmMapExpMod2OutputIndex mandatory
The index of the output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.1
airFMSysAlarmMapExpMod2AnyAlarm mandatory
Exp Module 2 alarm map setting for Any Alarm.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.2
airFMSysAlarmMapExpMod2MaintReq mandatory
Exp Module 2 alarm map setting for Module Maintenance
Required.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.3
airFMSysAlarmMapExpMod2CoolFail mandatory
Exp Module 2 alarm map setting for Module Cooling
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.4
airFMSysAlarmMapExpMod2HighSupplyTemp mandatory
Exp Module 2 alarm map setting for High Supply
Temperature.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.5
airFMSysAlarmMapExpMod2LowSupplyTemp mandatory
Exp Module 2 alarm map setting for Low Supply
Temperature.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.6
airFMSysAlarmMapExpMod2HumFail mandatory
Exp Module 2 alarm map setting for Humidifier Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.7
airFMSysAlarmMapExpMod2HumReplCyl mandatory
Exp Module 2 alarm map setting for Humidifier Replace
Cylinder.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.8
airFMSysAlarmMapExpMod2CondPumpFail mandatory
Exp Module 2 alarm map setting for Condensate Pump
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.9
airFMSysAlarmMapExpMod2BlwrCntl1Fail mandatory
Exp Module 2 alarm map setting for Blower Controller 1
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.10
airFMSysAlarmMapExpMod2BlwrCntl2Fail mandatory
Exp Module 2 alarm map setting for Blower Controller 2
Failure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.11
airFMSysAlarmMapExpMod2HighFltrDP mandatory
Exp Module 2 alarm map setting for High Filter
Differential Pressure.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.12
airFMSysAlarmMapExpMod2LowAirFlow mandatory
Exp Module 2 alarm map setting for Low Air Flow.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.13
airFMSysAlarmMapExpMod2AirBlckIntOpen mandatory
Exp Module 2 alarm map setting for Air Block Interlock
Open.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.14
airFMSysAlarmMapExpMod2WaterDetected mandatory
Exp Module 2 alarm map setting for Water Detected.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.15
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2 · 1 row entry · 17 columns
Allows for getting alarm map information.
airFMSysAlarmMapInputEntry entry .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1
The input contact alarm map type to reference.
Indexes
airFMSysAlarmMapInputOutputIndex
Column Syntax OID
airFMSysAlarmMapInputOutputIndex mandatory
The index of the output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.1
airFMSysAlarmMapInput1 mandatory
Input contact 1 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.2
airFMSysAlarmMapInput2 mandatory
Input contact 2 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.3
airFMSysAlarmMapInput3 mandatory
Input contact 3 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.4
airFMSysAlarmMapInput4 mandatory
Input contact 4 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.5
airFMSysAlarmMapInput5 mandatory
Input contact 5 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.6
airFMSysAlarmMapInput6 mandatory
Input contact 6 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.7
airFMSysAlarmMapInput7 mandatory
Input contact 7 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.8
airFMSysAlarmMapInput8 mandatory
Input contact 8 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.9
airFMSysAlarmMapInput9 mandatory
Input contact 9 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.10
airFMSysAlarmMapInput10 mandatory
Input contact 10 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.11
airFMSysAlarmMapInput11 mandatory
Input contact 11 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.12
airFMSysAlarmMapInput12 mandatory
Input contact 12 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.13
airFMSysAlarmMapInput13 mandatory
Input contact 13 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.14
airFMSysAlarmMapInput14 mandatory
Input contact 14 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.15
airFMSysAlarmMapInput15 mandatory
Input contact 15 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.16
airFMSysAlarmMapInput16 mandatory
Input contact 16 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.17
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2 · 1 row entry · 17 columns
Allows for getting alarm map information.
airFMSysAlarmMapOutputEntry entry .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1
The input contact alarm map type to reference.
Indexes
airFMSysAlarmMapOutputIndex
Column Syntax OID
airFMSysAlarmMapOutputIndex mandatory
The index of the output relay.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.1
airFMSysAlarmMapOutput1 mandatory
Output relay 1 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.2
airFMSysAlarmMapOutput2 mandatory
Output relay 2 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.3
airFMSysAlarmMapOutput3 mandatory
Output relay 3 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.4
airFMSysAlarmMapOutput4 mandatory
Output relay 4 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.5
airFMSysAlarmMapOutput5 mandatory
Output relay 5 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.6
airFMSysAlarmMapOutput6 mandatory
Output relay 6 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.7
airFMSysAlarmMapOutput7 mandatory
Output relay 7 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.8
airFMSysAlarmMapOutput8 mandatory
Output relay 8 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.9
airFMSysAlarmMapOutput9 mandatory
Output relay 9 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.10
airFMSysAlarmMapOutput10 mandatory
Output relay 10 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.11
airFMSysAlarmMapOutput11 mandatory
Output relay 11 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.12
airFMSysAlarmMapOutput12 mandatory
Output relay 12 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.13
airFMSysAlarmMapOutput13 mandatory
Output relay 13 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.14
airFMSysAlarmMapOutput14 mandatory
Output relay 14 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.15
airFMSysAlarmMapOutput15 mandatory
Output relay 15 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.16
airFMSysAlarmMapOutput16 mandatory
Output relay 16 alarm map setting.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2disabled
3enabled
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.17

airFMModIdentTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.5.1.2 · 1 row entry · 6 columns
Allows for getting information from each module in
the system.
airFMModIdentEntry entry .1.3.6.1.4.1.318.1.1.13.1.5.1.2.1
The module to get information from.
Indexes
airFMModIdentModuleIndex
Column Syntax OID
airFMModIdentModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.1
airFMModModelNumber mandatory
Model number of the Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.2
airFMModSerialNumber mandatory
Unique identification number for this Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.3
airFMModManufactureDate mandatory
Date the Module was manufactured.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.4
airFMModFirmwareRev mandatory
Revision number of the firmware installed on this
Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.5
airFMModHardwareRev mandatory
Revision number of the hardware installed on this
Module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.6

airFMModStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.5.2.2 · 1 row entry · 11 columns
Allows for getting information from each module in
the system.
airFMModStatusEntry entry .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1
The module to get information from.
Indexes
airFMModStatusModuleIndex
Column Syntax OID
airFMModStatusModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.1
airFMModSupplyTempC mandatory
The temperature measured at the supply sensor.
Measured in tenths of degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.2
airFMModSupplyTempF mandatory
The temperature measured at the supply sensor.
Measured in tenths of degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.3
airFMModSupplyHum mandatory
The humidity measured at the supply sensor.
Measured in tenths of percent relative humidity.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.4
airFMModReturnTempC mandatory
The temperature measured at the return sensor.
Measured in tenths of degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.5
airFMModReturnTempF mandatory
The temperature measured at the return sensor.
Measured in tenths of degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.6
airFMModReturnHum mandatory
The humidity measured at the return sensor.
Measured in tenths of percent relative humidity.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.7
airFMModFilterDiffPresPa mandatory
The difference in pressure on either side of the air
filters. A high differential pressure indicates a
clogged filter. Measured in Pascals.
A value of -2147483648 indicates that this OID does
not apply to this device d…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.8
airFMModFilterDiffPresInWC mandatory
The difference in pressure on either side of the air
filters. A high differential pressure indicates a
clogged filter. Measured in hundredths of inches
water column.
A value of -2147483648 indicates that this OID does
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.9
airFMModCoilDiffPresPa mandatory
The difference in pressure on either side of the
cooling/dehumidification coils. Measured in Pascals.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.10
airFMModCoilDiffPresInWC mandatory
The difference in pressure on either side of the
cooling/dehumidification coils. Measured in
hundredths of inches water column.
A value of -2147483648 indicates that this OID does
not apply to this device due to its co…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.11

airFMModPropTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.5.3.2 · 1 row entry · 13 columns
Allows for getting information from each module in
the system.
airFMModPropEntry entry .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1
The module to get information from.
Indexes
airFMModPropModuleIndex
Column Syntax OID
airFMModPropModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.1
airFMModOutputCapacity mandatory
The cooling capacity (in Kilowatts) of the displayed
Module.
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2kw45
3kw35
4kw40
5kw50
6kw80
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.2
airFMModCapacityCtrl mandatory
The method used to load and unload the compressors.
Tandem compressor Modules use two stages (one
compressor each). Single compressor Modules use hot
gas bypass.
A value of notApplicable indicates that this OID
does not…
Enumeration
Enumerated Values:
1notApplicable
2tandem
3hotGasBypass
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.3
airFMModHeaterType mandatory
The type of reheating device installed in this Module.
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2none
3electricSCR
4steam
5hotWaterOnOff
6hotGasReheat
7hotGasAndElectric
8hotWaterProp
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.4
airFMModElectricHeaterType mandatory
The type/capacity of the electric heater, if installed.
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2kw10
3kw15
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.5
airFMModHumidifierType mandatory
The type of equipment installed in the Module to run
the humidification mode.
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2none
3steamElectrode
4liveSteam
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.6
airFMModBlwrFreqSetting mandatory
Frequency of the blower in tenths of hertz.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.7
airFMModNomCoilDiffPresPa mandatory
The difference in pressure on either side of the
cooling/dehumidification coils. Measured in Pascals.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.8
airFMModNomCoilDiffPresInWC mandatory
The difference in pressure on either side of the
cooling/dehumidification coils. Measured in
hundredths of inches water column.
A value of -2147483648 indicates that this OID does
not apply to this device due to its co…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.9
airFMModCondPump mandatory
Indicates the presence of a condensate pump in the
Modules of this System.
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2notPresent
3present
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.10
airFMModFireDetector mandatory
Indicates the presence of a fire detector for each
of the Modules in this System.
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2notPresent
3present
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.11
airFMModSmokeDetector mandatory
Indicates the presence of a smoke detector for each
of the Modules in this System.
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2notPresent
3present
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.12
airFMModWaterDetector mandatory
Indicates the presence of a water leak detector for
each of the Modules in this System.
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2notPresent
3present
.1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.13

airFMModCoolTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.5.4.2 · 1 row entry · 9 columns
Allows for getting information from each module in
the system.
airFMModCoolEntry entry .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1
The module to get information from.
Indexes
airFMModCoolModuleIndex
Column Syntax OID
airFMModCoolModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.1
airFMModComp1 mandatory
The status of compressor 1 of the tandem compressor
unit (on or off).
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2on
3off
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.2
airFMModComp2 mandatory
The status of compressor 2 of the tandem compressor
unit (on or off).
A value of notApplicable indicates that this OID
does not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2on
3off
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.3
airFMModSuctPresKPa mandatory
The refrigerant pressure measured at the suction
inlet of the compressor. Measured in kiloPascals.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.4
airFMModSuctPresPSI mandatory
The refrigerant pressure measured at the suction
inlet of the compressor. Measured in pounds per
square inch.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.5
airFMModDischPresKPa mandatory
The refrigerant pressure measured at the discharge
outlet of the compressor. Measured in kiloPascals.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.6
airFMModDischPresPSI mandatory
The refrigerant pressure measured at the discharge
outlet of the compressor. Measured in pounds per
square inch.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.7
airFMModCondFluidVlvPos mandatory
The position of the condenser fluid valve. The valve
regulates the flow of liquid coolant into the heat
exchanger (condenser). 100% indicates the valve is
completely open, and 0% indicates that the valve is
closed. Mea…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.8
airFMModCoilFluidVlvPos mandatory
The position of the coil fluid valve. The valve
regulates the flow of liquid coolant in the fluid
cooling coil (MultiCool, Economizer, or Chilled
Water). 100% indicates the valve is completely open,
and 0% indicates tha…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.9

airFMModHumTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.5.5.2 · 1 row entry · 7 columns
Allows for getting information from each module in
the system.
airFMModHumEntry entry .1.3.6.1.4.1.318.1.1.13.1.5.5.2.1
The module to get information from.
Indexes
airFMModHumModuleIndex
Column Syntax OID
airFMModHumModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.1
airFMModHumidifier mandatory
The type of equipment installed in the Module to run
the humidification mode.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2none
3steamElectrode
4liveSteam
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.2
airFMModElectrodeCurrent mandatory
The current drawn by the electrodes of the steam
cylinder humidifier. Measured in tenths of amps.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.3
airFMModHumActualOutput mandatory
The humidification output of an individual Module.
Measured in percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.4
airFMModWaterConductivity mandatory
The conductivity of the water in the humidifier
cylinder. Measured in microSiemens per centimeter.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.5
airFMModHotWaterVlvPos mandatory
The position of the hot water valve. 100% indicates
the valve is completely open, and 0% indicates that
the valve is closed. Measured in percent.
A value of -2147483648 indicates that this OID does
not apply to this de…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.6
airFMModStmElectHumMode mandatory
Set the humidifier function mode.
Off: Remove power from electrodes.
Auto: Humidifier controlled by Module controller.
Drain: Remove power from electrodes and drain the cylinder.

A value of notApplicable …
Enumerationr/w
Enumerated Values:
1notApplicable
2off
3auto
4drain
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.7

airFMModBlwr1Table

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.5.6.2 · 1 row entry · 25 columns
Allows for getting information from each module in
the system.
airFMModBlwr1Entry entry .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1
The module to get information from.
Indexes
airFMModBlwr1ModuleIndex
Column Syntax OID
airFMModBlwr1ModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.1
airFMModBlwr1CtrlType mandatory
The type of blower controller.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2fujiVFD
3ecController
4danfossVFD
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.2
airFMModBlwr1CmdFreq mandatory
The requested operating frequency for the blower.
Measured in tenths of hertz.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.3
airFMModBlwr1ActFreq mandatory
The frequency at which the blower controller is
operating. Measured in tenths of hertz.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.4
airFMModBlwr1Poles mandatory
The number of poles of the blower motor that the
blower controller is controlling.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.5
airFMModBlwr1RatedHorsePower mandatory
The power rating of the blower motor. Measured in
hundredths of horsepower.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.6
airFMModBlwr1RatedCurrent mandatory
The current rating of the blower motor. Measured in
hundredths of amps.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.7
airFMModBlwr1ActTorq mandatory
The actual torque of the blower motor. Measured in
hundredths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.8
airFMModBlwr1Current mandatory
The percent of rated current drawn by the blower
motor. Measured in hundredths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.9
airFMModBlwr1Vlt mandatory
The voltage supplied to the blower motor. Measured
in tenths of volts RMS.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.10
airFMModBlwr1DCLinkVlt mandatory
The voltage of the blower controller's DC bus.
Measured in volts DC.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.11
airFMModBlwr1AccTime mandatory
The time to accelerate the blower to the specified
frequency. Measured in tenths of seconds.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.12
airFMModBlwr1DecTime mandatory
The time to decelerate the blower frequency to zero.
Measured in tenths of seconds.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.13
airFMModBlwr1CapLife mandatory
The remaining life of the main circuit capacitor.
Measured in tenths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.14
airFMModBlwr1CtrlCoolFanLife mandatory
The total operation time of the blower controller
cooling fan. Measured in hours.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.15
airFMModBlwr1ElOvMode mandatory
Enables or disables the electronic overload relay.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2inactive
3active
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.16
airFMModBlwr1ElOvSetting mandatory
The electronic overload relay is activated when the
current exceeds this threshold. Measured in
hundredths of amps.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.17
airFMModBlwr1ElOvTimeConst mandatory
The delay between the current exceeding the overload
threshold and the activation of the electronic
overload relay. Measured in tenths of minutes.
A value of -2147483648 indicates that this OID does
not apply to this d…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.18
airFMModBlwr1FanPower mandatory
The actual power of the blower motor. Measured in
tenths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.19
airFMModBlwr1HeatsinkTempC mandatory
The temperature of the heatsink on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.20
airFMModBlwr1HeatsinkTempF mandatory
The temperature of the heatsink on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.21
airFMModBlwr1ChokeTempC mandatory
The temperature of the choke on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.22
airFMModBlwr1ChokeTempF mandatory
The temperature of the choke on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.23
airFMModBlwr1InverterTempC mandatory
The temperature of the inverter on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.24
airFMModBlwr1InverterTempF mandatory
The temperature of the inverter on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.25

airFMModBlwr2Table

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.5.7.2 · 1 row entry · 25 columns
Allows for getting information from each module in
the system.
airFMModBlwr2Entry entry .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1
The module to get information from.
Indexes
airFMModBlwr2ModuleIndex
Column Syntax OID
airFMModBlwr2ModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.1
airFMModBlwr2CtrlType mandatory
The type of blower controller.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2fujiVFD
3ecController
4danfossVFD
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.2
airFMModBlwr2CmdFreq mandatory
The requested operating frequency for the blower.
Measured in tenths of hertz.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.3
airFMModBlwr2ActFreq mandatory
The frequency at which the blower controller is
operating. Measured in tenths of hertz.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.4
airFMModBlwr2Poles mandatory
The number of poles of the blower motor that the
blower controller is controlling.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.5
airFMModBlwr2RatedHorsePower mandatory
The power rating of the blower motor. Measured in
hundredths of horsepower.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.6
airFMModBlwr2RatedCurrent mandatory
The current rating of the blower motor. Measured in
hundredths of amps.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.7
airFMModBlwr2ActTorq mandatory
The actual torque of the blower motor. Measured in
hundredths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.8
airFMModBlwr2Current mandatory
The percent of rated current drawn by the blower
motor. Measured in hundredths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.9
airFMModBlwr2Vlt mandatory
The voltage supplied to the blower motor. Measured
in tenths of volts RMS.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.10
airFMModBlwr2DCLinkVlt mandatory
The voltage of the blower controller's DC bus.
Measured in volts DC.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.11
airFMModBlwr2AccTime mandatory
The time to accelerate the blower to the specified
frequency. Measured in tenths of seconds.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.12
airFMModBlwr2DecTime mandatory
The time to decelerate the blower frequency to zero.
Measured in tenths of seconds.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.13
airFMModBlwr2CapLife mandatory
The remaining life of the main circuit capacitor.
Measured in tenths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.14
airFMModBlwr2CtrlCoolFanLife mandatory
The total operation time of the blower controller
cooling fan. Measured in hours.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.15
airFMModBlwr2ElOvMode mandatory
Enables or disables the electronic overload relay.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumeration
Enumerated Values:
1notApplicable
2inactive
3active
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.16
airFMModBlwr2ElOvSetting mandatory
The electronic overload relay is activated when the
current exceeds this threshold. Measured in
hundredths of amps.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.17
airFMModBlwr2ElOvTimeConst mandatory
The delay between the current exceeding the overload
threshold and the activation of the electronic
overload relay. Measured in tenths of minutes.
A value of -2147483648 indicates that this OID does
not apply to this d…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.18
airFMModBlwr2FanPower mandatory
The actual power of the blower motor. Measured in
tenths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.19
airFMModBlwr2HeatsinkTempC mandatory
The temperature of the heatsink on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.20
airFMModBlwr2HeatsinkTempF mandatory
The temperature of the heatsink on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.21
airFMModBlwr2ChokeTempC mandatory
The temperature of the choke on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.22
airFMModBlwr2ChokeTempF mandatory
The temperature of the choke on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.23
airFMModBlwr2InverterTempC mandatory
The temperature of the inverter on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.24
airFMModBlwr2InverterTempF mandatory
The temperature of the inverter on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.25

airFMModRHTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.1.5.8.2 · 1 row entry · 15 columns
Allows for getting information from each module in
the system.
airFMModRHEntry entry .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1
The module to get information from.
Indexes
airFMModRHModuleIndex
Column Syntax OID
airFMModRHModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.1
airFMModRHComp1 mandatory
Compressor 1 run hours.
A value of -2147483648 indicates that this OID
does not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.2
airFMModRHComp2 mandatory
Compressor 2 run hours.
A value of -2147483648 indicates that this OID
does not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.3
airFMModRHHeater mandatory
Heater run hours.
A value of -2147483648 indicates that this OID
does not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.4
airFMModRHHum mandatory
Humidifier run hours
A value of -2147483648 indicates that this OID
does not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.5
airFMModRHBlwr1 mandatory
Blower 1 run hours.
A value of -2147483648 indicates that this OID
does not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.6
airFMModRHBlwr2 mandatory
Blower 2 run hours.
A value of -2147483648 indicates that this OID
does not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.7
airFMModRHBlwrCtrl1 mandatory
Blower Controller 1 run hours.
A value of -2147483648 indicates that this OID
does not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.8
airFMModRHBlwrCtrl2 mandatory
Blower Controller 2 run hours.
A value of -2147483648 indicates that this OID
does not apply to this device due to its configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.9
airFMModRHComp1Reset mandatory
Reset the compressor 1 run hours.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.10
airFMModRHComp2Reset mandatory
Reset the compressor 2 run hours.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.11
airFMModRHHeaterReset mandatory
Reset the heater run hours.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.12
airFMModRHHumReset mandatory
Reset the humidifier run hours.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.13
airFMModRHBlwr1Reset mandatory
Reset the blower 1 run hours.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.14
airFMModRHBlwr2Reset mandatory
Reset the blower 2 run hours.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.15
.1.3.6.1.4.1.318.1.1.13.1.5.10.2 · 1 row entry · 9 columns
Allows for getting information from each module in
the system.
airFMModServIntResetEntry entry .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1
The module to get information from.
Indexes
airFMModServIntResetModuleIndex
Column Syntax OID
airFMModServIntResetModuleIndex mandatory
The index of the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.1
airFMModServIntComp1Reset mandatory
Reset the compressor 1 service interval maintenance
alarm.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its con…
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.2
airFMModServIntComp2Reset mandatory
Reset the compressor 2 service interval maintenance
alarm.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its con…
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.3
airFMModServIntHeaterReset mandatory
Reset the heater service interval maintenance alarm.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configura…
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.4
airFMModServIntHumReset mandatory
Reset the humidifier service interval maintenance
alarm.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its confi…
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.5
airFMModServIntBlwr1Reset mandatory
Reset the blower 1 service interval maintenance
alarm.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configu…
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.6
airFMModServIntBlwr2Reset mandatory
Reset the blower 2 service interval maintenance
alarm.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to its configu…
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.7
airFMModServIntBlwrCtrl1Reset mandatory
Reset the blower controller 1 service interval
maintenance alarm.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to …
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.8
airFMModServIntBlwrCtrl2Reset mandatory
Reset the blower controller 2 service interval
maintenance alarm.
Getting this OID will do nothing and return the
noOperation value.
A value of notApplicable indicates that this OID does
not apply to this device due to …
Enumerationr/w
Enumerated Values:
1notApplicable
2noOperation
3reset
.1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.9
.1.3.6.1.4.1.318.1.1.13.1.6.4 · 1 row entry · 7 columns
Table of active alarm conditions for the device.
airFMAlarmConditionsEntry entry .1.3.6.1.4.1.318.1.1.13.1.6.4.1
Alarm condition specification
Indexes
airFMAlarmConditionsIndex
Column Syntax OID
airFMAlarmConditionsIndex mandatory
Alarm condition index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.6.4.1.1
airFMAlarmSeverity mandatory
Severity of the alarm.
Enumeration
Enumerated Values:
1informational
2warningMinor
3criticalMajor
.1.3.6.1.4.1.318.1.1.13.1.6.4.1.2
airFMAlarmType mandatory
Type of alarm.
Enumeration
Enumerated Values:
1group
2system
3mainMod
4expMod1
5expMod2
.1.3.6.1.4.1.318.1.1.13.1.6.4.1.3
airFMEventCode mandatory
APC event code for the alarm.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.1.6.4.1.4
airFMAlarmDate mandatory
Date the alarm was recorded.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.6.4.1.5
airFMAlarmTime mandatory
Time the alarm was recorded.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.1.6.4.1.6
airFMAlarmDescription mandatory
Description of the alarm.
OctetString
Constraints:
range: 0-64
.1.3.6.1.4.1.318.1.1.13.1.6.4.1.7
.1.3.6.1.4.1.318.1.1.13.3.1.2 · 1 row entry · 3 columns
Table of active alarm conditions for the device.
airIRAlarmConditionsEntry entry .1.3.6.1.4.1.318.1.1.13.3.1.2.1
Alarm condition specification
Indexes
airIRAlarmConditionsIndex
Column Syntax OID
airIRAlarmConditionsIndex mandatory
Alarm condition index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.3.1.2.1.1
airIREventCode mandatory
Code for the alarm.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.3.1.2.1.2
airIRAlarmDescription mandatory
Description of the alarm.
OctetString
Constraints:
range: 0-64
.1.3.6.1.4.1.318.1.1.13.3.1.2.1.3

airIRG2AlarmsTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.4.3.2 · 1 row entry · 3 columns
Table of active alarms for the device.
airIRG2AlarmsEntry entry .1.3.6.1.4.1.318.1.1.13.4.3.2.1
Alarms specification
Indexes
airIRG2AlarmsIndex
Column Syntax OID
airIRG2AlarmsIndex mandatory
Alarm index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.4.3.2.1.1
airIRG2AlarmsEventCode mandatory
Code for the alarm.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.4.3.2.1.2
airIRG2AlarmsDescription mandatory
Description of the alarm.
OctetString
Constraints:
range: 0-64
.1.3.6.1.4.1.318.1.1.13.4.3.2.1.3
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.5 · 1 row entry · 3 columns
Allows for getting run hour information from each power supply.
airIRG2RDT2RunHoursFanPSEntry entry .1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1
The run hours fan power supply table entry.
Indexes
airIRG2RDT2RunHoursFanPSIndex
Column Syntax OID
airIRG2RDT2RunHoursFanPSIndex mandatory
Index of run hours fan power supply table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.1
airIRG2RDT2RunHoursFanPSHours mandatory
Fan power supply run time in hours.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.2
airIRG2RDT2RunHoursFanPSPosition mandatory
Position of fan power supply within the unit.
Enumeration
Enumerated Values:
1upper
2lower
3left
4right
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.3
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.7 · 1 row entry · 2 columns
Allows for getting information from each evaporator fan run
hour in the system.
airIRG2RDT2RunHoursEvapFanEntry entry .1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1
Allows for getting information from each evaporator fan run
hour in the system.
Indexes
airIRG2RDT2RunHoursEvapFanIndex
Column Syntax OID
airIRG2RDT2RunHoursEvapFanIndex mandatory
Index of run hours evaporator fan table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1.1
airIRG2RDT2RunHoursEvapFanHours mandatory
Evaporator fan run time in hours.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1.2

airIRmAlarmsTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.5.2.2 · 1 row entry · 3 columns
Table of active alarms for the device.
airIRmAlarmsEntry entry .1.3.6.1.4.1.318.1.1.13.5.2.2.1
Alarms specification
Indexes
airIRmAlarmsIndex
Column Syntax OID
airIRmAlarmsIndex mandatory
Alarm index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.5.2.2.1.1
airIRmAlarmsEventCode mandatory
Code for the alarm.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.5.2.2.1.2
airIRmAlarmsDescription mandatory
Description of the alarm.
OctetString
Constraints:
range: 0-64
.1.3.6.1.4.1.318.1.1.13.5.2.2.1.3

airIRG3IdentTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.6.1.2 · 1 row entry · 11 columns
Allows to get ident information of current RDU and its assigned CM's.
airIRG3IdentEntry entry .1.3.6.1.4.1.318.1.1.13.6.1.2.1
The ident table entry.
Indexes
airIRG3IdentIndex
Column Syntax OID
airIRG3IdentIndex mandatory
Index of ident table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.1.2.1.1
airIRG3IdentName mandatory
A character string identifying the unit name.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.1.2.1.2
airIRG3IdentLocation mandatory
A character string identifying the unit location.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.1.2.1.3
airIRG3IdentModelNumber mandatory
A character string identifying the unit model number.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.1.2.1.4
airIRG3IdentSerialNumber mandatory
A character string identifying the unit serial number.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.1.2.1.5
airIRG3IdentFirmwareRevision mandatory
A character string identifying the unit firmware version.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.1.2.1.6
airIRG3IdentHardwareRevision mandatory
A character string identifying the unit controller hardware revision.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.1.2.1.7
airIRG3IdentManufactureDate mandatory
A character string identifying the unit manufacture date.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.1.2.1.8
airIRG3IdentRDUSysOID mandatory
This OID contains an OID path to the RDU data.
ObjectIdentifier .1.3.6.1.4.1.318.1.1.13.6.1.2.1.9
airIRG3IdentCMSysOID mandatory
This OID contains an OID path to the cooling module data.
ObjectIdentifier .1.3.6.1.4.1.318.1.1.13.6.1.2.1.10
airIRG3IdentGroupSysOID mandatory
This OID contains an OID path to the group data.
ObjectIdentifier .1.3.6.1.4.1.318.1.1.13.6.1.2.1.11
.1.3.6.1.4.1.318.1.1.13.6.2.2 · 1 row entry · 22 columns
Allows to get group status information.
airIRG3GroupStatusEntry entry .1.3.6.1.4.1.318.1.1.13.6.2.2.1
The group staus table entry.
Indexes
airIRG3GroupStatusIndex
Column Syntax OID
airIRG3GroupStatusIndex mandatory
Index of group status table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.1
airIRG3GroupStatusCoolOutput mandatory
The group cooling output in tenths of kilowatts (kW).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.2
airIRG3GroupStatusCoolDemand mandatory
The group cooling demand in tenths of kilowatts (kW).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.3
airIRG3GroupStatusAirFlowUS mandatory
The group air flow in cubic feet per minute (CFM).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.4
airIRG3GroupStatusAirFlowMetric mandatory
The group air flow in liters per second (L/s).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.5
airIRG3GroupStatusMaxRackInletTempUS mandatory
The group maximum rack inlet temperature in tenths of
degrees Fahrenheit. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.6
airIRG3GroupStatusMaxRackInletTempMetric mandatory
The group maximum rack inlet temperature in tenths of
degrees Celsius. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.7
airIRG3GroupStatusMinRackInletTempUS mandatory
The group minimum rack inlet temperature in tenths of
degrees Fahrenheit. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.8
airIRG3GroupStatusMinRackInletTempMetric mandatory
The group minimum rack inlet temperature in tenths of
degrees Celsius. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.9
airIRG3GroupStatusMaxReturnAirTempUS mandatory
The group maximum return air temperature in tenths of
degrees Fahrenheit. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.10
airIRG3GroupStatusMaxReturnAirTempMetric mandatory
The group maximum return air temperature in tenths of
degrees Celsius. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.11
airIRG3GroupStatusMinReturnAirTempUS mandatory
The group minimum return air temperature in tenths of
degrees Fahrenheit. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.12
airIRG3GroupStatusMinReturnAirTempMetric mandatory
The group minimum return air temperature in tenths of
degrees Celsius. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.13
airIRG3GroupStatusAvgSupplyTempUS mandatory
The group average supply air temperature in tenths of
degrees Fahrenheit. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.14
airIRG3GroupStatusAvgSupplyTempMetric mandatory
The group average supply air temperature in tenths of
degrees Celsius. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.15
airIRG3GroupStatusAvgReturnTempUS mandatory
The group average return air temperature in tenths of
degrees Fahrenheit. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.16
airIRG3GroupStatusAvgReturnTempMetric mandatory
The group average return air temperature in tenths of
degrees Celsius. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.17
airIRG3GroupStatusAvgFanSpeed mandatory
The group average fan speed in revolutions per minute (RPM).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.18
airIRG3GroupStatusAvgAirFlowUS mandatory
The group average air flow in cubic feet per minute (CFM).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.19
airIRG3GroupStatusAvgAirFlowMetric mandatory
The group average air flow in liters per second (L/s).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.20
airIRG3GroupStatusTotalAirFlowUS mandatory
The group total air flow in cubic feet per minute (CFM).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.21
airIRG3GroupStatusTotalAirFlowMetric mandatory
The group total air flow in liters per second (L/s).
Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.2.1.22
.1.3.6.1.4.1.318.1.1.13.6.2.3 · 1 row entry · 10 columns
Allows to access the group setpoints.
airIRG3GroupSetpointsEntry entry .1.3.6.1.4.1.318.1.1.13.6.2.3.1
The group setpoints table entry.
Indexes
airIRG3GroupSetpointsIndex
Column Syntax OID
airIRG3GroupSetpointsIndex mandatory
Index of group setpoints table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.1
airIRG3GroupSetpointsCoolSetpointUS mandatory
Group cooling setpoint in tenths of
degrees Fahrenheit.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.2
airIRG3GroupSetpointsCoolSetpointMetric mandatory
Group cooling setpoint in tenths of
degrees Celsius.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.3
airIRG3GroupSetpointsCoolDeadbandUS mandatory
Group cooling deadband in tenths of
degrees Fahrenheit. Returns (-1) if not supported.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.4
airIRG3GroupSetpointsCoolDeadbandMetric mandatory
Group cooling deadband in tenths of
degrees Celsius. Returns (-1) if not supported.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.5
airIRG3GroupSetpointsFanSpeedPreference mandatory
The group preferred fan speed setting.
Enumerationr/w
Enumerated Values:
1low
2med-low
3med
4med-high
5high
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.6
airIRG3GroupSetpointsSupplyAirSetpointUS mandatory
Group supply air setpoint in tenths of
degrees Fahrenheit.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.7
airIRG3GroupSetpointsSupplyAirSetpointMetric mandatory
Group supply air setpoint in tenths of
degrees Celsius.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.8
airIRG3GroupSetpointsAirFlowControl mandatory
The group air flow control.
Enumerationr/w
Enumerated Values:
1automatic
2manual
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.9
airIRG3GroupSetpointsLightingOnTime mandatory
The group lighting on time in minutes.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.3.1.10
.1.3.6.1.4.1.318.1.1.13.6.2.4 · 1 row entry · 12 columns
Allows to access group configuration table.
airIRG3GroupConfigEntry entry .1.3.6.1.4.1.318.1.1.13.6.2.4.1
The group config table entry.
Indexes
airIRG3GroupConfigIndex
Column Syntax OID
airIRG3GroupConfigIndex mandatory
Index of group config table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.1
airIRG3GroupConfigNumberofCoolingUnits mandatory
The number of cooling units.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.2
airIRG3GroupConfigConfigurationType mandatory
The group configuration type.
The spot configuration type is not supported.
Returns (-1) if not supported.
Enumerationr/w
Enumerated Values:
1racs
2spot
3in-row
4hacs
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.3
airIRG3GroupConfigCapacityControlType mandatory
The group capacity control. Returns (-1) if not supported.
Enumerationr/w
Enumerated Values:
1discrete
2proportional
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.4
airIRG3GroupConfigFanSpeedControl mandatory
The group fan speed control.
Enumerationr/w
Enumerated Values:
1automatic
2manual
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.5
airIRG3GroupConfigCoolGainP mandatory
The gain component of the PID in hundredths.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.6
airIRG3GroupConfigCoolResetRateI mandatory
The integral component of the PID in hundredths.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.7
airIRG3GroupConfigCoolDerivativeD mandatory
The derivative component of the PID in hundredths.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.8
airIRG3GroupConfigCoolPIDReset mandatory
Will reset the PID coefficients back to the factory defaults.
Readback is not supported, returns -1.
Enumerationr/w
Enumerated Values:
1readBack
2reset
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.9
airIRG3GroupConfigNumberofBackupUnits mandatory
The number of backup units.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.10
airIRG3GroupConfigRuntimeBalancingEnable mandatory
Enable or disable runtime balancing feature.
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.11
airIRG3GroupConfigLoadAssistEnable mandatory
Enable or disable load assist feature.
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.318.1.1.13.6.2.4.1.12

airIRG3AlarmsTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.6.3.2 · 1 row entry · 3 columns
Table of active alarms for the device.
airIRG3AlarmsEntry entry .1.3.6.1.4.1.318.1.1.13.6.3.2.1
Alarms specification
Indexes
airIRG3AlarmsIndex
Column Syntax OID
airIRG3AlarmsIndex mandatory
Alarm index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.3.2.1.1
airIRG3AlarmsEventCode mandatory
Event Code for the alarm. Returns (-1) if not supported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.3.2.1.2
airIRG3AlarmsDescription mandatory
Description of the alarm. Returns (-1) if not supported.
OctetString
Constraints:
range: 0-64
.1.3.6.1.4.1.318.1.1.13.6.3.2.1.3

airIRG3RDUStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.6.4.2 · 1 row entry · 43 columns
Allows to access RDU status table.
airIRG3RDUStatusEntry entry .1.3.6.1.4.1.318.1.1.13.6.4.2.1
The RDU status table entry.
Indexes
airIRG3RDUStatusDeviceIndex
Column Syntax OID
airIRG3RDUStatusDeviceIndex mandatory
Index of RDU status table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.1
airIRG3RDUID mandatory
The current RDU ID (1 to F).
Configured RDU only shall display ID, else return -1.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.2
airIRG3RDUStatusOnReadyStandby mandatory
The RDU current status.
Enumeration
Enumerated Values:
1standby
2ready
3on
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.3
airIRG3RDUStatusOperatingMode mandatory
The RDU actual operating mode.
Enumeration
Enumerated Values:
1standby
2ready
3on
4stop
5maintenancemode
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.4
airIRG3RDUStatusLeadPump mandatory
The RDU lead pump.
Enumeration
Enumerated Values:
1pump1
2pump2
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.5
airIRG3RDUStatusStartupDelay mandatory
The RDU start up delay in seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.6
airIRG3RDUStatusPumpChangeOverInterval mandatory
The RDU pump change over interval in days.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.7
airIRG3RDUStatusStopOnLeakDetect mandatory
The RDU status of stop on leak detect.
Enumeration
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.8
airIRG3RDUStatusPowerSource mandatory
The RDU power source status.
Enumeration
Enumerated Values:
1singleFeed
2dualFeed
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.9
airIRG3RDUStatusTotalRDUOutputPower mandatory
The RDU output power in tenths of kilowatts (kW).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.10
airIRG3RDUStatusInletWaterTempUS mandatory
The RDU inlet water temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.11
airIRG3RDUStatusInletWaterTempMetric mandatory
The RDU inlet water temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.12
airIRG3RDUStatusOutletWaterTempUS mandatory
The RDU outlet water temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.13
airIRG3RDUStatusOutletWaterTempMetric mandatory
The RDU outlet water temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.14
airIRG3RDUStatusCondenserSaturationTempUS mandatory
The RDU condenser saturation temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.15
airIRG3RDUStatusCondenserSaturationTempMetric mandatory
The RDU condenser saturation temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.16
airIRG3RDUStatusDewPointTempUS mandatory
The RDU dew point temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.17
airIRG3RDUStatusDewPointTempMetric mandatory
The RDU dew point temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.18
airIRG3RDUStatusPumpOutletTempUS mandatory
The RDU pump outlet temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.19
airIRG3RDUStatusPumpOutletTempMetric mandatory
The RDU pump outlet temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.20
airIRG3RDUStatusSubcoolerOutletTempUS mandatory
The RDU sub cooler outlet temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.21
airIRG3RDUStatusSubcoolerOutletTempMetric mandatory
The RDU sub cooler outlet temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.22
airIRG3RDUStatusCondenserOutletTempUS mandatory
The RDU condenser outlet temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.23
airIRG3RDUStatusCondenserOutletTempMetric mandatory
The RDU condenser outlet temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.24
airIRG3RDUStatusCondenserInletTempUS mandatory
The RDU condenser inlet temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.25
airIRG3RDUStatusCondenserInletTempMetric mandatory
The RDU condenser inlet temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.26
airIRG3RDUStatusCondenserOutletPressureUS mandatory
The RDU condenser outlet pressure in
pounds per square inch (PSI).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.27
airIRG3RDUStatusCondenserOutletPressureMetric mandatory
The RDU condenser outlet pressure in kiloPascals (KPa).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.28
airIRG3RDUStatusPump1HeadPressureUS mandatory
The RDU Pump 1 head pressure in pounds per square inch (PSI).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.29
airIRG3RDUStatusPump1HeadPressureMetric mandatory
The RDU Pump 1 head pressure in kiloPascals (KPa).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.30
airIRG3RDUStatusPump2HeadPressureUS mandatory
The RDU Pump 2 head pressure in pounds per square inch (PSI).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.31
airIRG3RDUStatusPump2HeadPressureMetric mandatory
The RDU Pump 2 head pressure in kiloPascals (KPa).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.32
airIRG3RDUStatusPump1Speed mandatory
The RDU Pump 1 speed in revolutions per minute (RPM).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.33
airIRG3RDUStatusPump2Speed mandatory
The RDU Pump 2 speed in revolutions per minute (RPM).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.34
airIRG3RDUStatusCWValvePosition mandatory
The RDU CW Valve position in % open
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.35
airIRG3RDUStatusReceiverLiquidLevel mandatory
The RDU receiver liquid level in % Full
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.36
airIRG3RDUStatusDCPowerSupply1Current mandatory
The RDU DC Power Supply 1 Current in Amps
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.37
airIRG3RDUStatusDCPowerSupply2Current mandatory
The RDU DC Power Supply 2 Current in Amps
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.38
airIRG3RDUStatusTotalDCPowerSupplyCurrent mandatory
The RDU Total DC Power Supply Current in Amps
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.39
airIRG3RDUStatusInputState mandatory
The RDU Input state.
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.40
airIRG3RDUStatusOutputState mandatory
The RDU Output state
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.41
airIRG3RDUStatusByPassValvePosition mandatory
The RDU By Pass Valve position in % open
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.42
airIRG3RDUStatusRefrigerantLeakDetector mandatory
The RDU refrigerant leak detector status.
Enumeration
Enumerated Values:
1suspended
2calibrating
3operating
4disabled
.1.3.6.1.4.1.318.1.1.13.6.4.2.1.43
.1.3.6.1.4.1.318.1.1.13.6.4.3 · 1 row entry · 6 columns
Allows to access RDU run hours table.
airIRG3RDURunHoursEntry entry .1.3.6.1.4.1.318.1.1.13.6.4.3.1
The RDU run hours table entry.
Indexes
airIRG3RDURunHoursDeviceIndex
Column Syntax OID
airIRG3RDURunHoursDeviceIndex mandatory
Index of RDU run hours table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.3.1.1
airIRG3RDURunHoursRDUID mandatory
The current RDU ID (1 to F).
Configured RDU only shall display ID, else return -1.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.4.3.1.2
airIRG3RDURunHoursPump1 mandatory
The RDU run hours of Pump 1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.3.1.3
airIRG3RDURunHoursPump2 mandatory
The RDU run hours of Pump 2.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.3.1.4
airIRG3RDURunHoursPowerSupply1 mandatory
The RDU run hours of power supply 1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.3.1.5
airIRG3RDURunHoursPowerSupply2 mandatory
The RDU run hours of power supply 2.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.3.1.6
.1.3.6.1.4.1.318.1.1.13.6.4.4 · 1 row entry · 4 columns
Allows to access RDU service intervals table.
airIRG3RDUServiceIntervalsEntry entry .1.3.6.1.4.1.318.1.1.13.6.4.4.1
The service interval table entry.
Indexes
airIRG3RDUServiceIntervalsDeviceIndex
Column Syntax OID
airIRG3RDUServiceIntervalsDeviceIndex mandatory
Index of service interval table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.4.1.1
airIRG3RDUServiceIntervalsRDUID mandatory
The current RDU ID (1 to F).
Configured RDU only shall display ID, else return -1.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.4.4.1.2
airIRG3RDUServiceIntervalsAirFilterInterval mandatory
The RDU service interval for air filter in hours.
Returns -1 if not supported.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.4.1.3
airIRG3RDUServiceIntervalsAirFilterAlarm mandatory
The RDU service interval air filter alarm status.
Returns -1 if not supported.
Enumerationr/w
Enumerated Values:
1enable
2disable
.1.3.6.1.4.1.318.1.1.13.6.4.4.1.4
.1.3.6.1.4.1.318.1.1.13.6.4.5 · 1 row entry · 4 columns
Allows to access RDU thresholds table.
airIRG3RDUThresholdsEntry entry .1.3.6.1.4.1.318.1.1.13.6.4.5.1
The RDU thresholds table entry.
Indexes
airIRG3RDUThresholdsDeviceIndex
Column Syntax OID
airIRG3RDUThresholdsDeviceIndex mandatory
Index of RDU thresholds table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.5.1.1
airIRG3RDUThresholdsRDUID mandatory
The current RDU ID (1 to F).
Configured RDU only shall display ID, else return -1.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.4.5.1.2
airIRG3RDUThresholdsEnteringFluidTempHighUS mandatory
The RDU threshold for entering fluid temperature in tenths of
degrees Fahrenheit.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.5.1.3
airIRG3RDUThresholdsEnteringFluidTempHighMetric mandatory
The RDU threshold for entering fluid temperature in tenths of
degrees Celsius.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.5.1.4
.1.3.6.1.4.1.318.1.1.13.6.4.6 · 1 row entry · 1 columns
Allows to access RDU set points table.
airIRG3RDUSetpointsEntry entry .1.3.6.1.4.1.318.1.1.13.6.4.6.1
The RDU set points table entry.
Indexes
airIRG3RDUSetpointsDeviceIndex
Column Syntax OID
airIRG3RDUSetpointsDeviceIndex mandatory
Index of RDU set points table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.6.1.1

airIRG3RDUConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.6.4.7 · 1 row entry · 13 columns
Allows to access RDU configuration table.
airIRG3RDUConfigEntry entry .1.3.6.1.4.1.318.1.1.13.6.4.7.1
The RDU configuration table entry.
Indexes
airIRG3RDUConfigDeviceIndex
Column Syntax OID
airIRG3RDUConfigDeviceIndex mandatory
Index of RDU configuration table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.1
airIRG3RDUConfigRDUID mandatory
The current RDU ID (1 to F).
Configured RDU only shall display ID, else return -1.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.2
airIRG3RDUConfigStopOnLeakDetect mandatory
The RDU stop on leak detect set.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.3
airIRG3RDUConfigStartupDelay mandatory
The RDU start up delay in seconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.4
airIRG3RDUConfigPumpChangeOverInterval mandatory
The RDU pump change over interval in days.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.5
airIRG3RDUConfigPowerSource mandatory
The RDU power source.
Enumerationr/w
Enumerated Values:
1singleFeed
2dualFeed
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.6
airIRG3RDUConfigOutputSource mandatory
The RDU output source.
Enumerationr/w
Enumerated Values:
1anyalarm
2onlycriticalalarms
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.7
airIRG3RDUConfigInputNormalState mandatory
The RDU Input Normal State.
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.8
airIRG3RDUConfigOutputNormalState mandatory
The RDU Output Normal State.
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.9
airIRG3RDUConfigByPassValveEnabled mandatory
The RDU By Pass Valve Enabled State.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.10
airIRG3RDUConfigRefrigerantLeakDetectorEnabled mandatory
The RDU Refrigerant Leak Detector Enabled State.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.11
airIRG3RDUConfigCalibrateRefrigerantLeakDetector mandatory
This parameter allows to calibrate the RDU Refrigerant Leak Detector and is write only.
The read returns -1. Only 'yes' is supported.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.12
airIRG3RDUConfigOnReadyStandby mandatory
This parameter allows to configure RDU on/standby parameter.
Ready is currently not supported. If unsupported returns -1.
Enumerationr/w
Enumerated Values:
1standby
2ready
3on
.1.3.6.1.4.1.318.1.1.13.6.4.7.1.13

airIRG3CMStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.6.5.2 · 1 row entry · 22 columns
Allows to access CM status table.
airIRG3CMStatusEntry entry .1.3.6.1.4.1.318.1.1.13.6.5.2.1
The CM status table entry.
Indexes
airIRG3CMStatusDeviceIndex
Column Syntax OID
airIRG3CMStatusDeviceIndex mandatory
Index of CM status table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.1
airIRG3CMStatusCMID mandatory
The CM ID (RDU Number - Group Number - CM Unit Number).
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.2
airIRG3CMStatusOperatingMode mandatory
The current operating mode of the CM.
Enumeration
Enumerated Values:
1standBy
2on
3idle
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.3
airIRG3CMStatusUnitType mandatory
The current CM unit type.
Enumeration
Enumerated Values:
1unconfigured
2oa
3ra
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.4
airIRG3CMStatusRackInletTempUS mandatory
The CM rack inlet temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.5
airIRG3CMStatusRackInletTempMetric mandatory
The CM rack inlet temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.6
airIRG3CMStatusReturnAirTempUS mandatory
The CM return air temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.7
airIRG3CMStatusReturnAirTempMetric mandatory
The CM return air temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.8
airIRG3CMStatusLiquidTempUS mandatory
The CM liquid temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.9
airIRG3CMStatusLiquidTempMetric mandatory
The CM liquid temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.10
airIRG3CMStatusVaporTempUS mandatory
The CM vapor temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.11
airIRG3CMStatusVaporTempMetric mandatory
The CM vapor temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.12
airIRG3CMStatusEvaporatorTempUS mandatory
The CM saturation temperature in tenths of
degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.13
airIRG3CMStatusEvaporatorTempMetric mandatory
The CM saturation temperature in tenths of
degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.14
airIRG3CMStatusLiquidInletPressureUS mandatory
The CM Liquid Inlet pressure in pounds per square inch (PSI).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.15
airIRG3CMStatusLiquidInletPressureMetric mandatory
The CM Liquid Inlet pressure in kiloPascals (kPa).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.16
airIRG3CMStatusVaporOutletPressureUS mandatory
The CM Vapor Outlet pressure in pounds per square inch (PSI).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.17
airIRG3CMStatusVaporOutletPressureMetric mandatory
The CM Vapor Outlet pressure in kiloPascals (kPa).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.18
airIRG3CMStatusExpansionValvePosition mandatory
The CM expansion valve position in % open
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.19
airIRG3CMStatusEPRValvePosition mandatory
The CM Evaporator Pressure Regulator Valve Position
in tenths of percent open
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.20
airIRG3CMStatusLocalDisplayOnOffEnabled mandatory
The status of the on/off control on the CM local display.
Enumeration
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.21
airIRG3CMStatusAverageFanSpeed mandatory
The CM Average Fan Speed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.2.1.22

airIRG3CMRunHoursTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.6.5.3 · 1 row entry · 8 columns
Allows to access CM run hours table.
airIRG3CMRunHoursEntry entry .1.3.6.1.4.1.318.1.1.13.6.5.3.1
The CM run hours table entry.
Indexes
airIRG3CMRunHoursDeviceIndex
Column Syntax OID
airIRG3CMRunHoursDeviceIndex mandatory
Index of CM run hours table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.3.1.1
airIRG3CMRunHoursCMID mandatory
The CM ID (RDU Number - Group Number - CM Unit Number).
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.5.3.1.2
airIRG3CMRunHoursFan1 mandatory
The CM run hours for Fan1.
Returns (-1) if not appilcable.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.3.1.3
airIRG3CMRunHoursFan2 mandatory
The CM run hours for Fan2.
Returns (-1) if not appilcable.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.3.1.4
airIRG3CMRunHoursFan3 mandatory
The CM run hours for Fan3.
Returns (-1) if not appilcable.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.3.1.5
airIRG3CMRunHoursFan4 mandatory
The CM run hours for Fan4.
Returns (-1) if not appilcable.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.3.1.6
airIRG3CMRunHoursFan5 mandatory
The CM run hours for Fan5.
Returns (-1) if not appilcable.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.3.1.7
airIRG3CMRunHoursAirFilter mandatory
The CM run hours for air filter.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.3.1.8
.1.3.6.1.4.1.318.1.1.13.6.5.4 · 1 row entry · 4 columns
Allows to access CM service intervals table.
airIRG3CMServiceIntervalsEntry entry .1.3.6.1.4.1.318.1.1.13.6.5.4.1
The CM service interval table entry.
Indexes
airIRG3CMServiceIntervalsDeviceIndex
Column Syntax OID
airIRG3CMServiceIntervalsDeviceIndex mandatory
Index of CM service intervals table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.4.1.1
airIRG3CMServiceIntervalsCMID mandatory
The CM ID (RDU Number - Group Number - CM Unit Number).
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.5.4.1.2
airIRG3CMServiceIntervalsAirFilterInterval mandatory
The CM service interval for air filter in weeks.
Supported only for RA. Returns -1 if not supported.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.4.1.3
airIRG3CMServiceIntervalsAirFilterAlarm mandatory
The CM service interval air filter alarm status.
Supported only for RA. Returns -1 if not supported.
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.318.1.1.13.6.5.4.1.4
.1.3.6.1.4.1.318.1.1.13.6.5.5 · 1 row entry · 8 columns
Allows to access CM thresholds table.
airIRG3CMThresholdsEntry entry .1.3.6.1.4.1.318.1.1.13.6.5.5.1
The CM thresholds table entry.
Indexes
airIRG3CMThresholdsDeviceIndex
Column Syntax OID
airIRG3CMThresholdsDeviceIndex mandatory
Index for CM thresholds table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.5.1.1
airIRG3CMThresholdsCMID mandatory
The CM ID (RDU Number - Group Number - CM Unit Number).
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.5.5.1.2
airIRG3CMThresholdsRackInletTempHighUS mandatory
The CM high threshold for rack inlet temperature in tenths of
degrees Fahrenheit.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.5.1.3
airIRG3CMThresholdsRackInletTempHighMetric mandatory
The CM high threshold for rack inlet temperature in tenths of
degrees Celsius.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.5.1.4
airIRG3CMThresholdsSupplyAirTempHighUS mandatory
The CM high threshold for supply air temperature in tenths of
degrees Fahrenheit.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.5.1.5
airIRG3CMThresholdsSupplyAirTempHighMetric mandatory
The CM high threshold for supply air temperature in tenths of
degrees Celsius.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.5.1.6
airIRG3CMThresholdsReturnAirTempHighUS mandatory
The CM high threshold for return air temperature in tenths of
degrees Fahrenheit.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.5.1.7
airIRG3CMThresholdsReturnAirTempHighMetric mandatory
The CM high threshold for return air temperature in tenths of
degrees Celsius.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.5.1.8
.1.3.6.1.4.1.318.1.1.13.6.5.6 · 1 row entry · 1 columns
Allows to access CM set points table.
airIRG3CMSetpointsEntry entry .1.3.6.1.4.1.318.1.1.13.6.5.6.1
The CM set points table entry.
Indexes
airIRG3CMSetpointsDeviceIndex
Column Syntax OID
airIRG3CMSetpointsDeviceIndex mandatory
Index of CM set points table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.6.1.1

airIRG3CMConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.13.6.5.7 · 1 row entry · 6 columns
Allows to access CM configuration table.
airIRG3CMConfigEntry entry .1.3.6.1.4.1.318.1.1.13.6.5.7.1
The CM configuration table entry.
Indexes
airIRG3CMConfigDeviceIndex
Column Syntax OID
airIRG3CMConfigDeviceIndex mandatory
Index of CM configuration table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.7.1.1
airIRG3CMConfigCMID mandatory
The CM ID (RDU Number - Group Number - CM Unit Number).
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.13.6.5.7.1.2
airIRG3CMConfigStopOnCoolFail mandatory
Enable/Disable Stop On cool fail. When enabled, stops the unit
if it detects that it is blowing warm air into the cold aisle.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.13.6.5.7.1.3
airIRG3CMConfigStartupDelay mandatory
The CM start up delay in seconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.13.6.5.7.1.4
airIRG3CMConfigRemoteOnStandby mandatory
The CM configuration for operating mode.
Enumerationr/w
Enumerated Values:
1standBy
2on
.1.3.6.1.4.1.318.1.1.13.6.5.7.1.5
airIRG3CMConfigPowerSource mandatory
The CM power source.
Enumerationr/w
Enumerated Values:
1singleFeed
2dualFeed
.1.3.6.1.4.1.318.1.1.13.6.5.7.1.6

rARUIdentTable

table mandatory
.1.3.6.1.4.1.318.1.1.14.1.1 · 1 row entry · 2 columns
Allows for query of the individual devices.
The number of entries is contained in the
rARUStatusAruDeviceCount OID.
rARUIdentEntry entry .1.3.6.1.4.1.318.1.1.14.1.1.1
The device to query.
Indexes
rARUIdentAruIndex
Column Syntax OID
rARUIdentAruIndex mandatory
The index to the ARU entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.1.1.1.1
rARUIdentName mandatory
A character string identifying the device.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.14.1.1.1.2

rARUConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.14.2.1 · 1 row entry · 6 columns
Allows for configuration of the individual ARU devices accessible from this IP address.
The number of entries is contained in the rARUStatusAruDeviceCount OID.
rARUConfigEntry entry .1.3.6.1.4.1.318.1.1.14.2.1.1
The ARUs to configure.
Indexes
rARUConfigAruIndex
Column Syntax OID
rARUConfigAruIndex mandatory
The index to the ARU entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.2.1.1.1
rARUConfigAruName mandatory
The name of the ARU.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.14.2.1.1.2
rARUConfigAruRemoteSetpoint mandatory
This OID defines the desired base airflow of the ARU, and sets the
speed of the ARU fans when the temperature override is inactive.

Values specified in cfm (cubic feet per minute) can be converted
to metr…
Enumerationr/w
Enumerated Values:
1aruOff
2aru85F-29C
3aru90F-32C
4aru95F-35C
5aru100F-38C
6aru7kW-1200cfm
7aru5kW-800cfm
8aru3kW-500cfm
9aru2kW-300cfm
10aru400cfm
11aru600cfm
12aru700cfm
13aru900cfm
14aru1000cfm
15aru1400cfm
16aru1600cfm
17aru1800cfm
18aru2000cfm
.1.3.6.1.4.1.318.1.1.14.2.1.1.3
rARUConfigAruTempOvrdEnableDisable mandatory
This OID is used to enable/disable the remote temperature override setting of the ARU.

If this OID is set to 1, the remote setting for temperature override is disabled.
If this OID is set to 2, the remote…
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.14.2.1.1.4
rARUConfigAruTempOvrdSetpoint mandatory
This OID is the Temperature Override setpoint of the ARU.

NOTE: -1 will be returned if the ARU is not communicating.

Values are represented in whole number degrees using the
units specified…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.2.1.1.5
rARUConfigAruMasterControl mandatory
This is the master on/off control for the ARU.
Enumerationr/w
Enumerated Values:
1aruOn
2aruOff
.1.3.6.1.4.1.318.1.1.14.2.1.1.6

rARUStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.14.3.3 · 1 row entry · 14 columns
Allows for query of the individual ARUs accessible from this IP address.
The number of entries is contained in the rARUStatusAruDeviceCount OID.
rARUStatusEntry entry .1.3.6.1.4.1.318.1.1.14.3.3.1
The ARUs to access.
Indexes
rARUStatusAruIndex
Column Syntax OID
rARUStatusAruIndex mandatory
The index to the ARU entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.3.3.1.1
rARUStatusAruName mandatory
The name of the ARU.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.14.3.3.1.2
rARUStatusAruRemoteSetpoint mandatory
This OID defines the desired base airflow of the ARU, or the
speed of the ARU fans when the temperature override is inactive.

See also the rARUConfigAruRemoteSetpoint OID.

NOTE: -1 will be …
Enumeration
Enumerated Values:
1aruOff
2aru85F-29C
3aru90F-32C
4aru95F-35C
5aru100F-38C
6aru7kW-1200cfm
7aru5kW-800cfm
8aru3kW-500cfm
9aru2kW-300cfm
10aru400cfm
11aru600cfm
12aru700cfm
13aru900cfm
14aru1000cfm
15aru1400cfm
16aru1600cfm
17aru1800cfm
18aru2000cfm
.1.3.6.1.4.1.318.1.1.14.3.3.1.3
rARUStatusAruManualSetpoint mandatory
Manual operating setpoint of the ARU, which is set on the
panel of the ARU. If the ARU doesn't have a manual ,
the OID will always return a value of aruRem (10).

NOTE: -1 will be returned if the ARU is no…
Enumeration
Enumerated Values:
1aruOff
2aru85F-29C
3aru90F-32C
4aru95F-35C
5aru100F-38C
6aru7kW
7aru5kW
8aru3kW
9aru2kW
10aruRem
.1.3.6.1.4.1.318.1.1.14.3.3.1.4
rARUStatusAruTemp1 mandatory
ARU temperature probe #1 reading.
The summary exhaust temperature on 2nd generation ARUs.

NOTE: -1 will be returned if the ARU is not communicating.

Values are represented in whole number d…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.3.3.1.5
rARUStatusAruTemp2 mandatory
ARU temperature probe #2 reading.
The exhaust temperature in the upper plenum on 2nd generation ARUs.

NOTE: -1 will be returned if the ARU is not communicating.

Values are represented in wh…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.3.3.1.6
rARUStatusAruTemp3 mandatory
ARU temperature probe #3 reading.
The exhaust temperature in the lower plenum on 2nd generation ARUs.

NOTE: -1 will be returned if the ARU is not communicating.

Values are represented in wh…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.3.3.1.7
rARUStatusAruTempOvrdEnableDisable mandatory
This OID indicates whether the ARU remote temperature override is enabled or disabled.
If this OID is a 1, the remote setting for temperature override is disabled.
If this OID is a 2, the remote setting for temperature …
Enumeration
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.14.3.3.1.8
rARUStatusAruTempOvrdSetpoint mandatory
ARU remote temperature override setpoint setting.

NOTE: -1 will be returned if the ARU is not communicating.

Values are represented in whole number degrees.
Units are displayed in the scale…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.3.3.1.9
rARUStatusAruAlarmState mandatory
An ASCII string containing the 8 flags representing
the current alarm state of the ARU. If the state of
the ARU is unknown, this variable is set to 'UNKNOWN'.

The flags are numbered 1 to 8, read from left…
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.14.3.3.1.10
rARUStatusAruCommStatus mandatory
The state of communications to the device.
commNeverDiscovered(1) indicates there has never been communications with this device.
commsEstablished(2) indicates communication is normal and active with this device.
commsL…
Enumeration
Enumerated Values:
1commsNeverDiscovered
2commsEstablished
3commsLost
.1.3.6.1.4.1.318.1.1.14.3.3.1.11
rARUStatusAruTempOvrdStatus mandatory
Specifies whether the ARU is increasing airflow because
exhaust air temperature has exceeded the setting specified in the
rARUConfigAruTempOvrdSetpoint OID.
Enumeration
Enumerated Values:
1inactive
2active
.1.3.6.1.4.1.318.1.1.14.3.3.1.12
rARUStatusAruMasterControl mandatory
This is the master on/off control for the ARU.
Enumeration
Enumerated Values:
1aruOn
2aruOff
.1.3.6.1.4.1.318.1.1.14.3.3.1.13
rARUStatusAruTotalAirflow mandatory
The total airflow provided by the aru. Specified in cfm (cubic feet per minute).
Can be converted to metric values using the conversion factor:
1 cfm = 1.70 m^3/hr (cubic meters per hour).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.3.3.1.14

rARUFanStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.14.4.1 · 1 row entry · 11 columns
Allows for query of the individual devices.
The number of entries is contained in the
rARUStatusAruDeviceCount OID.
rARUFanStatusEntry entry .1.3.6.1.4.1.318.1.1.14.4.1.1
The device to query.
Indexes
rARUFanStatusAruIndex rARUFanStatusFanIndex
Column Syntax OID
rARUFanStatusAruIndex mandatory
The index to the ARU entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.4.1.1.1
rARUFanStatusNominalFanSpeed mandatory
The nominal rotational speed (RPM) of the fans when they are
operating at the 100% level.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.4.1.1.2
rARUFanStatusSelectedFanLevel mandatory
The currently selected ARU speed level,
specified in percent of full capacity.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.4.1.1.3
rARUFanStatusReplacementThreshold mandatory
Threshold above which a run hour alarm will exist, indicating
that it might be time to proactively replace a fan.
Enumerationr/w
Enumerated Values:
1disabled
2khr20
3khr25
4khr30
5khr35
6khr40
7khr50
.1.3.6.1.4.1.318.1.1.14.4.1.1.4
rARUFanStatusFanIndex mandatory
The index to an individual fan table entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.4.1.1.5
rARUFanStatusFanOperatingStatus mandatory
The current operating state of the fan.
Enumeration
Enumerated Values:
1unknown
2off
3onOk
4onDegraded
5offFailed
.1.3.6.1.4.1.318.1.1.14.4.1.1.6
rARUFanStatusFanRpmSpeed mandatory
The current rotational speed of the fan,
specified in rotations per minute (RPM).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.4.1.1.7
rARUFanStatusFanFlowRate mandatory
The flow rate provided by the fan, based on its measured rotational speed.
Specified in cfm (cubic feet per minute). Can be converted to metric values
using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per h…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.4.1.1.8
rARUFanStatusFanInServiceDate mandatory
The installation/replacement date of the fan.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.14.4.1.1.9
rARUFanStatusFanRunhourCounter mandatory
The total time for which the fan has been running.
Specified in 10ths of hours.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.4.1.1.10
rARUFanStatusFanRunhourReset mandatory
Writing yes to this This OID will reset a fan's total run hour counter,
which is shown in the rARUFanStatusFanRunhourCounter OID.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.1.14.4.1.1.11

rARUPowerStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.14.5.1 · 1 row entry · 4 columns
Allows for query of the individual ARUs accessible from this IP address.
The number of entries is contained in the rARUStatusAruDeviceCount OID.
rARUPowerStatusEntry entry .1.3.6.1.4.1.318.1.1.14.5.1.1
The device to query.
Indexes
rARUPowerStatusAruIndex
Column Syntax OID
rARUPowerStatusAruIndex mandatory
The index to the ARU entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.5.1.1.1
rARUPowerStatusPrimaryAcPresent mandatory
Indicates whether or not line voltage is present on AC input 1.
Enumeration
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.1.14.5.1.1.2
rARUPowerStatusAuxiliaryAcPresent mandatory
Indicates whether or not line voltage is present on AC input 2.
Enumeration
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.1.14.5.1.1.3
rARUPowerStatusRedundantAcConfig mandatory
Indicates whether or not a dual cord is in use.
When this setting is set to dualCord (2), aruRedundantPowerLostAlarm
traps will be generated when either primary or auxiliary input
voltage is not present. When this setti…
Enumerationr/w
Enumerated Values:
1singleCord
2dualCord
.1.3.6.1.4.1.318.1.1.14.5.1.1.4

rARUSensorsStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.14.6.2 · 1 row entry · 3 columns
Allows for getting environmental sensor status information.
rARUSensorsStatusEntry entry .1.3.6.1.4.1.318.1.1.14.6.2.1
The unit to get data from.
Indexes
rARUSensorsStatusAruIndex rARUSensorsStatusSensorNumber
Column Syntax OID
rARUSensorsStatusAruIndex mandatory
The index to the ARU entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.2.1.1
rARUSensorsStatusSensorNumber mandatory
The number of the sensor on the device.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.2.1.2
rARUSensorsTemperature mandatory
The sensor's current temperature reading. The temperature scale
is based on the system preferences configuration.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.2.1.3

rARUSensorsConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.14.6.4 · 1 row entry · 17 columns
Allows for getting configuration information from
environmental sensors attached to the device.
rARUSensorsConfigEntry entry .1.3.6.1.4.1.318.1.1.14.6.4.1
The unit to get data from.
Indexes
rARUSensorsConfigAruIndex rARUSensorsConfigSensorNumber
Column Syntax OID
rARUSensorsConfigAruIndex mandatory
The index to the ARU entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.1
rARUSensorsConfigSensorNumber mandatory
The number of the sensor on the device.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.2
rARUSensorsName mandatory
A descriptive name for the sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.14.6.4.1.3
rARUSensorsLocation mandatory
The location of the sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.14.6.4.1.4
rARUSensorsTempMaxThresh mandatory
The temperature at which a maximum temperature threshold
violation alarm will be generated for this sensor.
The temperature scale is based on the system preferences
configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.5
rARUSensorsTempHighThresh mandatory
The temperature at which a high temperature threshold
violation alarm will be generated for this sensor.
The temperature scale is based on the system preferences
configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.6
rARUSensorsTempLowThresh mandatory
The temperature at which a low temperature threshold
violation alarm will be generated for this sensor.
The temperature scale is based on the system preferences
configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.7
rARUSensorsTempMinThresh mandatory
The temperature at which a min temperature threshold
violation alarm will be generated for this sensor.
The temperature scale is based on the system preferences
configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.8
rARUSensorsTempThreshHysteresis mandatory
The change in temperature required to cause a
temperature alarm to change from an active to an
inactive state. The temperature scale is based on
the system preferences configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.9
rARUSensorsTempShortDecRateThreshValue mandatory
The value of the temperature short-term decreasing rate
time that will cause an alarm to be generated.
The temperature scale is based on the system preferences
configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.10
rARUSensorsTempShortDecRateThreshTime mandatory
The time over which the temperature may not decrease
beyond the value specified by the temperature short-term
decreasing rate threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.11
rARUSensorsTempShortIncRateThreshValue mandatory
The value of the temperature short-term increasing rate
time that will cause an alarm to be generated.
The temperature scale is based on the system preferences
configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.12
rARUSensorsTempShortIncRateThreshTime mandatory
The time over which the temperature may not increase
beyond the value specified by the temperature short-term
increasing rate threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.13
rARUSensorsTempLongDecRateThreshValue mandatory
The value of the temperature long-term decreasing rate
time that will cause an alarm to be generated.
The temperature scale is based on the system preferences
configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.14
rARUSensorsTempLongDecRateThreshTime mandatory
The time over which the temperature may not decrease
beyond the value specified by the temperature long-term
decreasing rate threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.15
rARUSensorsTempLongIncRateThreshValue mandatory
The value of the temperature long-term increasing rate
time that will cause an alarm to be generated.
The temperature scale is based on the system preferences
configuration.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.16
rARUSensorsTempLongIncRateThreshTime mandatory
The time over which the temperature may not increase
beyond the value specified by the temperature long-term
increasing rate threshold value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.14.6.4.1.17
.1.3.6.1.4.1.318.1.1.15.3.1.4 · 1 row entry · 3 columns
A list of input voltage table entries. The number of
entries are the phase entries.
The number of entries is contained in the
xPDUMainInputVoltageTableSize OID.
xPDUMainInputVoltagePhaseEntry entry .1.3.6.1.4.1.318.1.1.15.3.1.4.1
An entry containing information applicable to a
particular main input voltage phase.
Indexes
xPDUMainInputVoltagePhaseIndex
Column Syntax OID
xPDUMainInputVoltagePhaseIndex mandatory
Description of each input phase entry in the table.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.15.3.1.4.1.1
xPDUMainInputVoltageLtoL mandatory
Line-to-line PDU input voltage when an isolation transformer is present,
or -1 if no transformer present in this PDU. Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.1.4.1.2
xPDUMainInputVoltageLtoN mandatory
Line-to-neutral PDU input voltage when an isolation transformer is not present,
or -1 if a transformer is present in this PDU. Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.1.4.1.3
.1.3.6.1.4.1.318.1.1.15.3.2.4 · 1 row entry · 3 columns
A list of output table entries.  The number of
entries are the phase entries.
The number of entries is contained in the
xPDUBypassInputVoltagePhaseTableSize OID.
xPDUBypassInputVoltagePhaseEntry entry .1.3.6.1.4.1.318.1.1.15.3.2.4.1
An entry containing information applicable to a
particular bypass input voltage phase.
Indexes
xPDUBypassInputVoltagePhaseIndex
Column Syntax OID
xPDUBypassInputVoltagePhaseIndex mandatory
Index of each bypass input phase entry in the table.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.15.3.2.4.1.1
xPDUBypassInputVoltageLtoL mandatory
Line-to-line bypass input voltage, or -1 if no bypass
feed is present in this PDU. Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.2.4.1.2
xPDUBypassInputVoltageLtoN mandatory
Line-to-neutral bypass input voltage, or -1 if no bypass
feed is present in this PDU. Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.2.4.1.3
.1.3.6.1.4.1.318.1.1.15.3.3.2 · 1 row entry · 2 columns
A list of UPS input table entries.  The number of
entries are the phase entries.
The number of entries is contained in the
xPDUUPSInputVoltagePhaseTableSize OID.
xPDUUPSInputVoltagePhaseEntry entry .1.3.6.1.4.1.318.1.1.15.3.3.2.1
An entry containing information applicable to a
particular UPS input voltage phase.
Indexes
xPDUUPSInputVoltagePhaseIndex
Column Syntax OID
xPDUUPSInputVoltagePhaseIndex mandatory
Description of each UPS input phase entry in the table.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.15.3.3.2.1.1
xPDUUPSInputVoltageLtoNPresent mandatory
Indicates whether or not voltage is present at the UPS feed.
Enumeration
Enumerated Values:
1notPresent
2present
3unknown
.1.3.6.1.4.1.318.1.1.15.3.3.2.1.2
.1.3.6.1.4.1.318.1.1.15.3.4.14 · 1 row entry · 7 columns
A list of system output table entries.
The number of entries is contained in the
xPDUSystemOutputTableSize OID.
xPDUSystemOutputPhaseEntry entry .1.3.6.1.4.1.318.1.1.15.3.4.14.1
An entry containing information applicable to a
particular system output phase.
Indexes
xPDUSystemOutputPhaseIndex
Column Syntax OID
xPDUSystemOutputPhaseIndex mandatory
Description of each output phase entry in the table.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.15.3.4.14.1.1
xPDUSystemOutputVoltageLtoL mandatory
Line-to-line system output voltage available at the circuit panel.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.4.14.1.2
xPDUSystemOutputVoltageLtoN mandatory
Line-to-neutral system output voltage available at the circuit panel.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.4.14.1.3
xPDUSystemOutputPhaseCurrent mandatory
System load current per phase. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.4.14.1.4
xPDUSystemOutputPower mandatory
System output power per phase. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.4.14.1.5
xPDUSystemOutputApparentPower mandatory
System output power per phase. Measured in tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.4.14.1.6
xPDUSystemOutputPowerFactor mandatory
Indicates the Power Factor of the system output per phase.
A value of 100 representing a unity Power Factor (1.00).
Measured in hundredths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.3.4.14.1.7

xPDUSystemBreakerTable

table mandatory
.1.3.6.1.4.1.318.1.1.15.4.1.2 · 1 row entry · 3 columns
A list of system breaker entries.
The number of entries is contained in the
xPDUSystemBreakerTableSize OID.
xPDUSystemBreakerEntry entry .1.3.6.1.4.1.318.1.1.15.4.1.2.1
An entry containing information applicable to a
particular system breaker.
Indexes
xPDUSystemBreakerTableIndex
Column Syntax OID
xPDUSystemBreakerTableIndex mandatory
Index of system breaker entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.4.1.2.1.1
xPDUSystemBreakerDescription mandatory
A brief description of the system breakers.
OctetString
Constraints:
range: 0-79
.1.3.6.1.4.1.318.1.1.15.4.1.2.1.2
xPDUSystemBreakerPosition mandatory
Indicates whether this breaker is open(1) or closed(2).
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.15.4.1.2.1.3

xPDUBranchBreakerTable

table mandatory
.1.3.6.1.4.1.318.1.1.15.4.2.3 · 1 row entry · 11 columns
A list of branch breaker table entries. The
number of entries is given by the value of xPDUBranchBreakerTableSize
The number of entries is contained in the xPDUBranchBreakerTableSize OID.
xPDUBranchBreakerEntry entry .1.3.6.1.4.1.318.1.1.15.4.2.3.1
An entry containing information applicable to a
particular branch breaker (panel position).
Indexes
xPDUBranchBreakerTableIndex
Column Syntax OID
xPDUBranchBreakerTableIndex mandatory
Index of branch breaker entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.1
xPDUBranchBreakerRating mandatory
Indicates current rating of this breaker.
0=Breaker is not present.
1=Earth leakage connection.
2=Neutral connection.
A value greater than 2 indicates breaker current rating in Amps.
A value above 60 Amp will signify a …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.2
xPDUBranchBreakerRDPFeed mandatory
Indicates that a breaker position is feeding a remote
distribution panel.
Enumeration
Enumerated Values:
1remoteDistribution
2noRemoteDistribution
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.3
xPDUBranchBreakerTieIndicator mandatory
Indicates whether or not the breaker in this position
is logically associated with the breaker immediately below it.
This setting is used grouping the breakers feeding
a multi-pole branch circuit.
Note: When setting an …
Enumerationr/w
Enumerated Values:
1breakerUnTied
2breakerTied
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.4
xPDUBranchBreakerCurrent mandatory
Indicates the branch current in tenths of Amps or -1 when not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.5
xPDUBranchBreakerOverCurrentThreshold mandatory
Threshold above which a branch circuit high current
condition will be generated.
Specified as a percent of the branch breaker rating.
A value of zero indicates that the threshold is disabled.
Note: When setting branch c…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.6
xPDUBranchBreakerUnderCurrentThreshold mandatory
Threshold below which a branch circuit low current
condition will be generated.
Specified as a percent of the branch breaker rating.
A value of zero indicates that the threshold is disabled.
Note: When setting branch ci…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.7
xPDUBranchBreakerMaxCurrentThreshold mandatory
Threshold above which a branch circuit maximum current
condition will be generated.
Specified as a percent of the branch breaker rating.
A value of zero indicates that the threshold is disabled.
Note: When setting branc…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.8
xPDUBranchBreakerMinCurrentThreshold mandatory
Threshold below which a branch circuit minimum current
condition will be generated.
Specified as a percent of the branch breaker rating.
A value of zero indicates that the threshold is disabled.
Note: When setting branc…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.9
xPDUBranchBreakerName mandatory
The description of the purpose/use of the breaker.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.10
xPDUBranchBreakerLocation mandatory
The description of the location of the breaker.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.11

xPDUInputContactTable

table mandatory
.1.3.6.1.4.1.318.1.1.15.5.3 · 1 row entry · 4 columns
A list of contacts supported by the PDU.
The number of entries is contained in the
xPDUInputContactTableSize OID.
xPDUInputContactEntry entry .1.3.6.1.4.1.318.1.1.15.5.3.1
A contact entry containing information for a given contact.
Indexes
xPDUInputContactNumber
Column Syntax OID
xPDUInputContactNumber mandatory
An index identifying the contact on the PDU.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.5.3.1.1
xPDUInputContactName mandatory
The description of the purpose/use of the contact.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.15.5.3.1.2
xPDUInputContactNormalState mandatory
The normal operating position of the contact.
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.15.5.3.1.3
xPDUInputContactCurrentState mandatory
This value indicates the current state of the contact.
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.15.5.3.1.4

xPDUOutputRelayTable

table mandatory
.1.3.6.1.4.1.318.1.1.15.6.3 · 1 row entry · 4 columns
A list of output relays supported by the PDU.
The number of entries is contained in the
xPDUOutputRelayTableSize OID.
xPDUOutputRelayEntry entry .1.3.6.1.4.1.318.1.1.15.6.3.1
A output relay entry containing information for a given contact.
Indexes
xPDUOutputRelayNumber
Column Syntax OID
xPDUOutputRelayNumber mandatory
An index identifying the output relay on the PDU.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.15.6.3.1.1
xPDUOutputRelayName mandatory
The description of the purpose/use of the output relay.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.15.6.3.1.2
xPDUOutputRelayNormalState mandatory
The normal operating position of the output relay.
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.15.6.3.1.3
xPDUOutputRelayCurrentState mandatory
This value indicates the current state of the output relay.
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.15.6.3.1.4

battManUnitCalibTable

table mandatory
.1.3.6.1.4.1.318.1.1.16.3.2 · 1 row entry · 4 columns
Allows for getting calibration information from each unit in the system.
battManUnitCalibEntry entry .1.3.6.1.4.1.318.1.1.16.3.2.1
The unit to get data from.
Indexes
battManUnitCalibIndex
Column Syntax OID
battManUnitCalibIndex mandatory
Index of unit calibration entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.3.2.1.1
battManUnitSerialNumber mandatory
The serial number of the unit.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.16.3.2.1.2
battManBatteryVoltageZeroCalib mandatory
The unit battery voltage zero calibration in millivolts.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.3.2.1.3
battManBatteryVoltageSpanCalib mandatory
The unit battery voltage span calibration in hundredths of percent.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.3.2.1.4
.1.3.6.1.4.1.318.1.1.16.4.2 · 1 row entry · 4 columns
Allows for getting calibration information from each string in the system.
battManStringCalibEntry entry .1.3.6.1.4.1.318.1.1.16.4.2.1
The string to get data from.
Indexes
battManStringCalibIndex
Column Syntax OID
battManStringCalibIndex mandatory
Index of string calibration entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.4.2.1.1
battManDCCurrentZeroCalib mandatory
The string DC current zero calibration in tenths of amps.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.4.2.1.2
battManACCurrentZeroCalib mandatory
The string AC current zero calibration in tenths of amps.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.4.2.1.3
battManProbeRange mandatory
The string probe range in amps.
Enumerationr/w
Enumerated Values:
1amps1000
2amps500
3amps100
4amps200
5amps2000
.1.3.6.1.4.1.318.1.1.16.4.2.1.4
.1.3.6.1.4.1.318.1.1.16.5.2 · 1 row entry · 2 columns
Allows for getting calibration information from each battery in String 1.
battManString1BatteryCalibEntry entry .1.3.6.1.4.1.318.1.1.16.5.2.1
The string to get data from.
Indexes
battManString1BatteryCalibIndex
Column Syntax OID
battManString1BatteryCalibIndex mandatory
Index of battery calibration entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.5.2.1.1
battManString1BatteryInterTierOhmicValue mandatory
The battery inter-tier ohmic value in ohms. This corresponds to the ohmic
value for the positive terminal of the battery.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.5.2.1.2
.1.3.6.1.4.1.318.1.1.16.5.4 · 1 row entry · 2 columns
Allows for getting calibration information from each battery in String 2.
battManString2BatteryCalibEntry entry .1.3.6.1.4.1.318.1.1.16.5.4.1
The string to get data from.
Indexes
battManString2BatteryCalibIndex
Column Syntax OID
battManString2BatteryCalibIndex mandatory
Index of battery calibration entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.5.4.1.1
battManString2BatteryInterTierOhmicValue mandatory
The battery inter-tier ohmic value in ohms.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.5.4.1.2

battManStringTable

table mandatory
.1.3.6.1.4.1.318.1.1.16.9.2 · 1 row entry · 13 columns
Allows for getting information from each string
in the system.
battManStringEntry entry .1.3.6.1.4.1.318.1.1.16.9.2.1
The string to get data from.
Indexes
battManStringIndex
Column Syntax OID
battManStringIndex mandatory
Index of string entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.9.2.1.1
battManStringCurrent mandatory
The string current in tenths of amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.9.2.1.2
battManStringRippleCurrent mandatory
The string ripple current in tenths of amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.9.2.1.3
battManStringChargerHighVoltageAlarm mandatory
When set to alarm(2), indicates that the string charger has a high voltage alarm.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.9.2.1.4
battManStringChargerLowVoltageAlarm mandatory
When set to alarm(2), indicates that the string charger has a low voltage alarm.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.9.2.1.5
battManStringCurrentProbeDisconnected mandatory
When set to alarm(2), indicates that the string charger probe is disconnected.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.9.2.1.6
battManStringOnBattery mandatory
When set to alarm(2), indicates that the string is in the on-battery state.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.9.2.1.7
battManStringHighRippleCurrent mandatory
When set to alarm(2), indicates that the string has a high ripple current.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.9.2.1.8
battManStringVoltage mandatory
The sum of the voltages for all of the batteries on a
string in millivolts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.9.2.1.9
battManStringDischargeLess5Seconds mandatory
The number of recorded discharges lasting less than
5 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.9.2.1.10
battManStringDischarge5to10Seconds mandatory
The number of recorded discharges lasting between 5
and 10 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.9.2.1.11
battManStringDischarge10to60Seconds mandatory
The number of recorded discharges lasting between 10
and 60 seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.9.2.1.12
battManStringDischargeMore60Seconds mandatory
The number of recorded discharges lasting more than
60 seconds (1 minute).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.9.2.1.13
.1.3.6.1.4.1.318.1.1.16.10.2 · 1 row entry · 14 columns
Allows for getting information from each string
in the system.
battManString1BatteryEntry entry .1.3.6.1.4.1.318.1.1.16.10.2.1
The string to get data from.
Indexes
battManString1BatteryIndex
Column Syntax OID
battManString1BatteryIndex mandatory
Index of string entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.10.2.1.1
battManString1BatteryVoltage mandatory
The battery voltage in millivolts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.10.2.1.2
battManString1BatteryLowestVoltage mandatory
The lowest battery discharge voltage during the last power event in millivolts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.10.2.1.3
battManString1BatteryCellShorted mandatory
When set to alarm(2), indicates that a battery cell is shorted.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.4
battManString1BatteryOpenFuseOrConnection mandatory
When set to alarm(2), indicates that a fuse or connection is open.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.5
battManString1BatteryLowCapacity mandatory
When set to alarm(2), indicates a battery has low capacity.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.6
battManString1BatteryHighOhmicValue mandatory
When set to alarm(2), indicates a battery has a high ohmic value.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.7
battManString1BatteryThermalRunaway mandatory
When set to alarm(2), indicates a battery has a thermal runaway condition.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.8
battManString1BatteryDryout mandatory
When set to alarm(2), indicates a battery has a dryout condition.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.9
battManString1BatteryUserHighVoltageAlarm mandatory
When set to alarm(2), indicates a battery has violated
the user level high voltage limit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.10
battManString1BatteryUserLowVoltageAlarm mandatory
When set to alarm(2), indicates a battery has violated
the user level low voltage limit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.11
battManString1BatteryChemHighVoltageAlarm mandatory
When set to alarm(2), indicates a battery has violated
the chemistry level high voltage limit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.12
battManString1BatteryChemLowVoltageAlarm mandatory
When set to alarm(2), indicates a battery has violated
the chemistry level low voltage limit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.13
battManString1BatteryOpenCell mandatory
When set to alarm(2), indicates the battery has an open
cell or an inter-connection is abnormal.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.2.1.14
.1.3.6.1.4.1.318.1.1.16.10.4 · 1 row entry · 14 columns
Allows for getting information from each string
in the system.
battManString2BatteryEntry entry .1.3.6.1.4.1.318.1.1.16.10.4.1
The string to get data from.
Indexes
battManString2BatteryIndex
Column Syntax OID
battManString2BatteryIndex mandatory
Index of string entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.10.4.1.1
battManString2BatteryVoltage mandatory
The battery voltage in millivolts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.10.4.1.2
battManString2BatteryLowestVoltage mandatory
The lowest battery discharge voltage during the last power event in millivolts DC.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.10.4.1.3
battManString2BatteryCellShorted mandatory
When set to alarm(2), indicates that a battery cell is shorted.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.4
battManString2BatteryOpenFuseOrConnection mandatory
When set to alarm(2), indicates that a fuse or connection is open.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.5
battManString2BatteryLowCapacity mandatory
When set to alarm(2), indicates a battery has low capacity.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.6
battManString2BatteryHighOhmicValue mandatory
When set to alarm(2), indicates a battery has a high ohmic value.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.7
battManString2BatteryThermalRunaway mandatory
When set to alarm(2), indicates a battery has a thermal runaway condition.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.8
battManString2BatteryDryout mandatory
When set to alarm(2), indicates a battery has a dryout condition.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.9
battManString2BatteryUserHighVoltageAlarm mandatory
When set to alarm(2), indicates a battery has violated
the user level high voltage limit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.10
battManString2BatteryUserLowVoltageAlarm mandatory
When set to alarm(2), indicates a battery has violated
the user level low voltage limit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.11
battManString2BatteryChemHighVoltageAlarm mandatory
When set to alarm(2), indicates a battery has violated
the chemistry level high voltage limit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.12
battManString2BatteryChemLowVoltageAlarm mandatory
When set to alarm(2), indicates a battery has violated
the chemistry level low voltage limit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.13
battManString2BatteryOpenCell mandatory
When set to alarm(2), indicates the battery has an open
cell or an inter-connection is abnormal.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.10.4.1.14
.1.3.6.1.4.1.318.1.1.16.11.2 · 1 row entry · 6 columns
Allows for getting information from each contact
in the system.
battManInputContactEntry entry .1.3.6.1.4.1.318.1.1.16.11.2.1
The contact to get data from.
Indexes
battManInputContactIndex
Column Syntax OID
battManInputContactIndex mandatory
Index of contact entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.11.2.1.1
battManInputContactName mandatory
The name of the input contact.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.16.11.2.1.2
battManInputContactAlarmState mandatory
When set to alarm(2), indicates that the alarm condition is active for this contact.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.11.2.1.3
battManInputContactState mandatory
When set to open(1), the input contact is in the open state.
When set to closed(2), the input contact is in the closed state.
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.16.11.2.1.4
battManInputContactNormalState mandatory
When set to open(1), the input contact is normally open.
When set to closed(2), the input contact is normally closed.
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.16.11.2.1.5
battManInputContactAlarmDelay mandatory
The input contact alarm delay time in seconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.11.2.1.6
.1.3.6.1.4.1.318.1.1.16.13.3 · 1 row entry · 2 columns
Allows for getting ohmic value information from each battery in String 1.
battManString1OhmicValueEntry entry .1.3.6.1.4.1.318.1.1.16.13.3.1
The string to get data from.
Indexes
battManString1OhmicValueIndex
Column Syntax OID
battManString1OhmicValueIndex mandatory
The battery number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.3.1.1
battManString1OhmicValueData mandatory
The battery inter-tier ohmic value in tenths of milli-Ohms.
Note: Zero or negative values are invalid and may indicate
faulty calibration of ohmic value correction factors.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.3.1.2
.1.3.6.1.4.1.318.1.1.16.13.5 · 1 row entry · 2 columns
Allows for getting response test change information from each battery in String 1.
battManString1ResponseTestChangeEntry entry .1.3.6.1.4.1.318.1.1.16.13.5.1
The string to get data from.
Indexes
battManString1ResponseTestChangeIndex
Column Syntax OID
battManString1ResponseTestChangeIndex mandatory
Index of the entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.5.1.1
battManString1ResponseTestChangeData mandatory
The battery response test change in percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.5.1.2
.1.3.6.1.4.1.318.1.1.16.13.8 · 1 row entry · 2 columns
Allows for getting ohmic value information from each battery in String 2.
battManString2OhmicValueEntry entry .1.3.6.1.4.1.318.1.1.16.13.8.1
The string to get data from.
Indexes
battManString2OhmicValueIndex
Column Syntax OID
battManString2OhmicValueIndex mandatory
Index of battery calibration entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.8.1.1
battManString2OhmicValueData mandatory
The battery inter-tier ohmic value in ohms.
Note: Zero or negative values are invalid and may indicate
faulty calibration of ohmic value correction factors.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.8.1.2
.1.3.6.1.4.1.318.1.1.16.13.10 · 1 row entry · 2 columns
Allows for getting response test change information from each battery in String 2.
battManString2ResponseTestChangeEntry entry .1.3.6.1.4.1.318.1.1.16.13.10.1
The string to get data from.
Indexes
battManString2ResponseTestChangeIndex
Column Syntax OID
battManString2ResponseTestChangeIndex mandatory
Index of the entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.10.1.1
battManString2ResponseTestChangeData mandatory
The battery response test change in percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.10.1.2
.1.3.6.1.4.1.318.1.1.16.13.12 · 1 row entry · 2 columns
Allows for getting response test current information from each battery
in String 1.
battManString1ResponseTestCurrentEntry entry .1.3.6.1.4.1.318.1.1.16.13.12.1
The string to get data from.
Indexes
battManString1ResponseTestCurrentIndex
Column Syntax OID
battManString1ResponseTestCurrentIndex mandatory
Index of the entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.12.1.1
battManString1ResponseTestCurrentData mandatory
The battery response test current in milliamps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.12.1.2
.1.3.6.1.4.1.318.1.1.16.13.14 · 1 row entry · 2 columns
Allows for getting response test current information from each battery
in String 2.
battManString2ResponseTestCurrentEntry entry .1.3.6.1.4.1.318.1.1.16.13.14.1
The string to get data from.
Indexes
battManString2ResponseTestCurrentIndex
Column Syntax OID
battManString2ResponseTestCurrentIndex mandatory
Index of the entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.14.1.1
battManString2ResponseTestCurrentData mandatory
The battery response test current in milliamps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.14.1.2
.1.3.6.1.4.1.318.1.1.16.13.16 · 1 row entry · 2 columns
Allows for getting response test current benchmark information from
each battery in String 1.
battManString1ResponseTestCurrentBenchmarkEntry entry .1.3.6.1.4.1.318.1.1.16.13.16.1
The string to get data from.
Indexes
battManString1ResponseTestCurrentBenchmarkIndex
Column Syntax OID
battManString1ResponseTestCurrentBenchmarkIndex mandatory
Index of the entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.16.1.1
battManString1ResponseTestCurrentBenchmarkData mandatory
The battery response test current benchmark in milliamps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.16.1.2
.1.3.6.1.4.1.318.1.1.16.13.18 · 1 row entry · 2 columns
Allows for getting response test current benchmark information from
each battery in String 2.
battManString2ResponseTestCurrentBenchmarkEntry entry .1.3.6.1.4.1.318.1.1.16.13.18.1
The string to get data from.
Indexes
battManString2ResponseTestCurrentBenchmarkIndex
Column Syntax OID
battManString2ResponseTestCurrentBenchmarkIndex mandatory
Index of the entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.18.1.1
battManString2ResponseTestCurrentBenchmarkData mandatory
The battery response test current benchmark in milliamps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.13.18.1.2

battManUnitStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.16.14.2 · 1 row entry · 6 columns
Allows for getting status information from each unit in the system.
battManUnitStatusEntry entry .1.3.6.1.4.1.318.1.1.16.14.2.1
The unit to get data from.
Indexes
battManUnitStatusIndex
Column Syntax OID
battManUnitStatusIndex mandatory
Index of unit status entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.14.2.1.1
battManUnitStatusSerialNumber mandatory
The battery manager unit serial number character string.
This value is set at the factory.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.16.14.2.1.2
battManUnitHardwareRev mandatory
The battery manager unit hardware revision.
This value is set at the factory.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.14.2.1.3
battManUnitFirmwareRev mandatory
The battery manager unit firmware revision.
This value is set at the factory and can change with firmware update.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.16.14.2.1.4
battManUnitCommLoss mandatory
When set to alarm(2), indicates the system has lost
communication with the unit.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.14.2.1.5
battManUnitRelayStuck mandatory
When set to alarm(2), indicates the unit monitor relay
is stuck.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.16.14.2.1.6

xATSSwitchTimersTable

table mandatory
.1.3.6.1.4.1.318.1.1.17.3.3.2 · 1 row entry · 6 columns
A list of timers supported by ATS.
The number of entries is contained in the xATSSwitchTimersTableSize OID.
xATSSwitchTimersEntry entry .1.3.6.1.4.1.318.1.1.17.3.3.2.1
An entry containing information about an individual ATS timer.
Indexes
xATSSwitchTimersIndex
Column Syntax OID
xATSSwitchTimersIndex mandatory
Index of timer entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.3.3.2.1.1
xATSSwitchTimersName mandatory
Name of the individual timer.Refer to ATS operation manual,
or on-line help, for detailed descriptions of ATS timers.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.17.3.3.2.1.2
xATSSwitchTimersAbort mandatory
This aborts the individual timer.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.1.17.3.3.2.1.3
xATSSwitchTimersStatus mandatory
The status of the individual timer. Designates whether this timer
entry is currently running or inactive.
Enumeration
Enumerated Values:
1inactive
2active
.1.3.6.1.4.1.318.1.1.17.3.3.2.1.4
xATSSwitchTimersRemainingTime mandatory
The time remaining for this timer entry.
Specified in seconds.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.3.3.2.1.5
xATSSwitchTimersDelaySetting mandatory
The delay settings associated with this timer entry.
When this timer entry is active, the timer value must exceed this setting
before the ATS behavior associated with this timer is executed.
Refer to ATS operation manua…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.3.3.2.1.6
.1.3.6.1.4.1.318.1.1.17.3.4.2 · 1 row entry · 4 columns
A list of blocking maps supported by the ATS.
The number of entries is contained in the xATSSwitchBlockMapTableSize OID.
xATSSwitchBlockMapEntry entry .1.3.6.1.4.1.318.1.1.17.3.4.2.1
An entry containing information about a specific ATS blocking map.
Indexes
xATSSwitchBlockMapIndex
Column Syntax OID
xATSSwitchBlockMapIndex mandatory
Index of blocking map entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.3.4.2.1.1
xATSSwitchBlockMapName mandatory
A string describing the ATS action to be blocked.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.17.3.4.2.1.2
xATSSwitchBlockMapStatus mandatory
Represents the status of this blocking map entry, in bit-mapped format.
A non-zero value indicates that this entry's ATS action is currently being blocked.
The bit(s) set indicate which input(s) are causing the blocking…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.3.4.2.1.3
xATSSwitchBlockMapSetting mandatory
This setting designates the inputs that block the ATS action
The mapping is specified as a bit-field, where each bit set indicates
the input that blocks the ATS action associated with the entry.

bit 0 - C…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.3.4.2.1.4
.1.3.6.1.4.1.318.1.1.17.3.5.2 · 1 row entry · 4 columns
A list of statistics supported by ATS.
The number of entries is contained in the xATSSwitchStatisticsTableSize OID.
xATSSwitchStatisticsEntry entry .1.3.6.1.4.1.318.1.1.17.3.5.2.1
An entry containing information about an individual ATS statistic.
Indexes
xATSSwitchStatisticsIndex
Column Syntax OID
xATSSwitchStatisticsIndex mandatory
Index of ATS statistics entries in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.3.5.2.1.1
xATSSwitchStatisticsName mandatory
This is the name of the ATS statistic associated with this entry.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.17.3.5.2.1.2
xATSSwitchStatisticsValue mandatory
This is the value of the ATS statistic associated with this entry.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.17.3.5.2.1.3
xATSSwitchStatisticsReset mandatory
This will reset the individual ATS statistic associated with this entry.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.1.17.3.5.2.1.4

xATSSource1PhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.17.4.1.7 · 1 row entry · 3 columns
A list of voltage table entries for source 1. The number of
entries are the phase entries. The number of entries is contained in the
xATSSource1TableSize OID.
xATSSource1PhaseEntry entry .1.3.6.1.4.1.318.1.1.17.4.1.7.1
An entry containing information applicable to a
particular input voltage phase at the source 1 input of the ATS.
Indexes
xATSSource1Index
Column Syntax OID
xATSSource1Index mandatory
Description of each phase utilized at source 1.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.17.4.1.7.1.1
xATSSource1VoltageLtoL mandatory
Source 1 line-to-line input voltage.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.1.7.1.2
xATSSource1VoltageLtoN mandatory
Source 1 line-to-neutral input voltage.
Measured in tenths of Volts. -1 for a 3-wire service type.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.1.7.1.3

xATSSource2PhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.17.4.2.7 · 1 row entry · 3 columns
A list of voltage table entries for the source 2. The number of
entries are the phase entries. The number of entries is contained in the
xATSSource2TableSize OID.
xATSSource2PhaseEntry entry .1.3.6.1.4.1.318.1.1.17.4.2.7.1
An entry containing information applicable to a
particular input voltage phase at the source 2 input of the ATS.
Indexes
xATSSource2Index
Column Syntax OID
xATSSource2Index mandatory
Description of each phase utilized at the source 2.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.17.4.2.7.1.1
xATSSource2VoltageLtoL mandatory
Source 2 line-to-line input voltage.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.2.7.1.2
xATSSource2VoltageLtoN mandatory
Source 2 line-to-neutral input voltage.
Measured in tenths of Volts. -1 for a 3-wire service type.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.2.7.1.3
.1.3.6.1.4.1.318.1.1.17.4.3.12 · 1 row entry · 7 columns
A list of system output table entries.
The number of entries is contained in the xATSSystemOutputTableSize OID.
xATSSystemOutputPhaseEntry entry .1.3.6.1.4.1.318.1.1.17.4.3.12.1
An entry containing information applicable to a
particular system output phase.
Indexes
xATSSystemOutputPhaseIndex
Column Syntax OID
xATSSystemOutputPhaseIndex mandatory
Description of each system output phase utilized in this device.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.17.4.3.12.1.1
xATSSystemOutputVoltageLtoL mandatory
Line-to-line system output voltage available at the circuit panel.
Measured in tenths of Volts. -1 if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.3.12.1.2
xATSSystemOutputVoltageLtoN mandatory
Line-to-neutral system output voltage available at the circuit panel.
Measured in tenths of Volts. -1 for a 3-wire service type or if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.3.12.1.3
xATSSystemOutputPhaseCurrent mandatory
System load current per phase. Measured in Amps.
-1 if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.3.12.1.4
xATSSystemOutputPower mandatory
System output power per phase. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.3.12.1.5
xATSSystemOutputApparentPower mandatory
system output power per phase. Measured in tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.3.12.1.6
xATSSystemOutputPowerFactor mandatory
indicates the power factor of the system output per phase.
A value of 100 representing a unity power factor (1.00).
Measured in hundredths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.4.3.12.1.7

xATSInputContactTable

table mandatory
.1.3.6.1.4.1.318.1.1.17.6.3 · 1 row entry · 4 columns
A list of contacts supported by the ATS.
The number of entries is contained in the
xATSInputContactTableSize OID.
xATSInputContactEntry entry .1.3.6.1.4.1.318.1.1.17.6.3.1
A contact entry containing information for a given contact.
Indexes
xATSInputContactNumber
Column Syntax OID
xATSInputContactNumber mandatory
An index identifying the contact on the ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.6.3.1.1
xATSInputContactName mandatory
The description of the purpose/use of the contact.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.17.6.3.1.2
xATSInputContactNormalState mandatory
The normal operating position of the contact.
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.17.6.3.1.3
xATSInputContactCurrentState mandatory
This value indicates the current state of the contact.
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.17.6.3.1.4

xATSOutputRelayTable

table mandatory
.1.3.6.1.4.1.318.1.1.17.7.3 · 1 row entry · 4 columns
A list of output relays supported by the ATS.
The number of entries is contained in the
xATSOutputRelayTableSize OID.
xATSOutputRelayEntry entry .1.3.6.1.4.1.318.1.1.17.7.3.1
A output relay entry containing information for a given contact.
Indexes
xATSOutputRelayNumber
Column Syntax OID
xATSOutputRelayNumber mandatory
An index identifying the output relay on the ATS.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.17.7.3.1.1
xATSOutputRelayName mandatory
The description of the purpose/use of the output relay.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.17.7.3.1.2
xATSOutputRelayNormalState mandatory
The normal operating position of the output relay.
Enumerationr/w
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.17.7.3.1.3
xATSOutputRelayCurrentState mandatory
This value indicates the current state of the output relay.
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.17.7.3.1.4
.1.3.6.1.4.1.318.1.1.18.1.4.6 · 1 row entry · 7 columns
A list of generator output table entries.
The number of entries is contained in the xATSGeneratorOutputTableSize OID.
xATSGeneratorOutputPhaseEntry entry .1.3.6.1.4.1.318.1.1.18.1.4.6.1
An entry containing information applicable to a
particular generator output phase.
Indexes
xATSGeneratorOutputPhaseIndex
Column Syntax OID
xATSGeneratorOutputPhaseIndex mandatory
Description of each generator output phase utilized in this device.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.18.1.4.6.1.1
xATSGeneratorOutputVoltageLtoL mandatory
Line-to-line generator output voltage.
Measured in Volts, or -1 if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.18.1.4.6.1.2
xATSGeneratorOutputVoltageLtoN mandatory
Line-to-neutral generator output voltage.
Measured in volts, or -1 if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.18.1.4.6.1.3
xATSGeneratorOutputPhaseCurrent mandatory
Generator load current per phase.
Measured in Amps, or -1 if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.18.1.4.6.1.4
xATSGeneratorOutputPower mandatory
Generator output power per phase.
Measured in tenths of kW, or -1 if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.18.1.4.6.1.5
xATSGeneratorOutputApparentPower mandatory
Generator output power per phase.
Measured in tenths of kVA, or -1 if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.18.1.4.6.1.6
xATSGeneratorOutputPowerFactor mandatory
Indicates the load power factor of the generator output per phase.
A value of 100 representing a unity power factor (1.00),
or -1 if not available.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.18.1.4.6.1.7

cpsCardIdentTable

table mandatory
.1.3.6.1.4.1.318.1.1.19.1.1.4.2 · 1 row entry · 5 columns
A table of PCMCIA card identifications.
cpsCardIdentEntry entry .1.3.6.1.4.1.318.1.1.19.1.1.4.2.1
Identification information for a PCMCIA card.
Indexes
cpsCardIdentIndex
Column Syntax OID
cpsCardIdentIndex mandatory
Number to identify the socket Card.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.1
cpsCardIdentProd mandatory
Product identification string.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.2
cpsCardIdentMan mandatory
Manufacturer ID code.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.3
cpsCardIdentFunc mandatory
Function ID code.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.4
cpsCardIdentPCI mandatory
PCI ID
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.5

cpsCardConfTable

table mandatory
.1.3.6.1.4.1.318.1.1.19.1.1.4.3 · 1 row entry · 8 columns
A table of socket configuration information.
cpsCardConfEntry entry .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1
Configuration information for a socket.
Indexes
cpsCardConfIndex
Column Syntax OID
cpsCardConfIndex mandatory
Number to identify the socket PCMCIA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.1
cpsCardConfPower mandatory
Power Settings.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.2
cpsCardConfType mandatory
Interface Type.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.3
cpsCardConfInter mandatory
Interrupt number.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.4
cpsCardConfFunc mandatory
Function.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.5
cpsCardConfCardv mandatory
Card values.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.6
cpsCardConfPort1 mandatory
I/O Port 1.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.7
cpsCardConfPort2 mandatory
I/O Port 2.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.8

cpsCardStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.19.1.1.4.4 · 1 row entry · 3 columns
A table of current socket status information.
cpsCardStatusEntry entry .1.3.6.1.4.1.318.1.1.19.1.1.4.4.1
Current status information for a socket.
Indexes
cpsCardStatusIndex
Column Syntax OID
cpsCardStatusIndex mandatory
Number to identify the socket PCMCIA.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.1
cpsCardStatusCard mandatory
Current Card State.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.2
cpsCardStatusFunc mandatory
Current Function.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.3

cpsSerialGroupTable

table mandatory
.1.3.6.1.4.1.318.1.1.19.1.2.6.1.11 · 1 row entry · 3 columns
cpsSerialGroupEntry entry .1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1
Indexes
cpsSerialGroupIndex
Column Syntax OID
cpsSerialGroupIndex mandatory
Number to identify the group.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.1
cpsSerialGroupName mandatory
The group name.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.2
cpsSerialGroupUsers mandatory
The user's names.
OctetStringr/w
Constraints:
range: 0-80
.1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.3

cpsSerialPortTable

table mandatory
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1 · 1 row entry · 58 columns
This is the specific configuration per serial port.
cpsSerialPortEntry entry .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1
One particular serial port configuration.
Indexes
cpsSerialPortNumber
Column Syntax OID
cpsSerialPortNumber mandatory
Number to identify the serial port. Value 0 is ALL.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.1
cpsSerialPortTty mandatory
The device name for the serial port.
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.2
cpsSerialPortName mandatory
Alias name given to the server connected to the serial port.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.3
cpsSerialPortSpeed mandatory
The speed of the serial port.
Supported values are:
50, 75, 110, 134, 150, 200, 300, 600,
1200, 1800, 2400, 4800, 9600, 14400, 19200,
28800, 38400, 57600, 115200, 230400, and 460800
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.4
cpsSerialPortDataSize mandatory
The data size for the serial port.
Integer32r/w
Constraints:
range: 4-8
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.5
cpsSerialPortStopBits mandatory
The number of stop bits for the serial port.
Integer32r/w
Constraints:
range: 0-2
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.6
cpsSerialPortParity mandatory
The parity for the serial port.
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.7
cpsSerialPortFlowCtrl mandatory
The flow control for the serial port.
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.8
cpsSerialPortDTRdelay mandatory
This specifies how long (in milliseconds) a DTR signal
will be turned off before it is turned on again.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.9
cpsSerialPortDCDCtrl mandatory
DCD signal controls the connection request.
0 will indicate nocontrol,
1 will indicate control.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.10
cpsSerialPortLogUtmp mandatory
Update the login records in /var/run/utmp file.
0 will indicate inactive,
1 will indicate active.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.11
cpsSerialPortLogWtmp mandatory
Update the login records in /var/run/wtmp file.
0 will indicate inactive,
1 will indicate active.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.12
cpsSerialPortLogform mandatory
This is the format to write the login record.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.13
cpsSerialPortAuthtype mandatory
Authentication type.
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.14
cpsSerialPortAuthSrv1 mandatory
IP address of the primary authentication server.
RFC1155-SMIIpAddressr/w
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.15
cpsSerialPortAccSrv1 mandatory
IP address of the primary accounting server.
RFC1155-SMIIpAddressr/w
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.16
cpsSerialPortAuthTmo mandatory
This is the timeout (in seconds) for the authentication
query to be answered.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.17
cpsSerialPortAuthRetr mandatory
This defines the number of times each server is tried
before another is contacted.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.18
cpsSerialPortAuthSrv2 mandatory
IP address of the secondary authentication server.
RFC1155-SMIIpAddressr/w
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.19
cpsSerialPortAccSrv2 mandatory
IP address of the secondary accounting server.
RFC1155-SMIIpAddressr/w
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.20
cpsSerialPortAuthSecret mandatory
This is the shared secret with authentication servers.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.21
cpsSerialPortAuthRadP mandatory
Radius state.
0 will indicate inactive,
1 will indicate active.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.22
cpsSerialPortAuthAcc mandatory
Access restriction.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.23
cpsSerialPortProtocol mandatory
Defines the serial port's protocol.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.24
cpsSerialPortRemoteIP mandatory
This is the default IP address of the serial port.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.25
cpsSerialPortSocketPort mandatory
This defines an alternative labeling system for the serial port.
OctetStringr/w
Constraints:
range: 0-10
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.26
cpsSerialPortRemHost mandatory
The IP address of the host to which the serial port will connect.
RFC1155-SMIIpAddressr/w
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.27
cpsSerialPortBanner mandatory
This defines the banner.
OctetStringr/w
Constraints:
range: 0-250
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.28
cpsSerialPortPrompt mandatory
This defines the login prompt to the serial port.
OctetStringr/w
Constraints:
range: 0-250
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.29
cpsSerialPortTermType mandatory
This defines the terminal type.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.30
cpsSerialPortAutomUsr mandatory
This defines the automatic user.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.31
cpsSerialPortNetMask mandatory
The network mask used in dial in connection.
RFC1155-SMIIpAddressr/w
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.32
cpsSerialPortPppMtu mandatory
The PPP MTU - dial in connection.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.33
cpsSerialPortPppMru mandatory
The PPP MRU - dial in connection.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.34
cpsSerialPortPppOptions mandatory
The PPP options when the PPP session is autodetected.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.35
cpsSerialPortPppFoption mandatory
The PPP forced options when the user has already been authenticated.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.36
cpsSerialPortModemChat mandatory
The initchat send to modem connected.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.37
cpsSerialPortSttyCmd mandatory
The tty settings after socket connection is established.
OctetStringr/w
Constraints:
range: 0-180
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.38
cpsSerialPortSockTx mandatory
Defines the delay (in milliseconds) before transmission to
the Ethernet of data received through a serial port.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.39
cpsSerialPortSockPoll mandatory
Keep-alive timer (milliseconds) for the TCP connection.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.40
cpsSerialPortSockIdle mandatory
The idle timeout in seconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.41
cpsSerialPortDBsize mandatory
Maximum size of the data buffering file.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.42
cpsSerialPortDBtime mandatory
Timestamp in data buffering.
0 will indicate inactive,
1 will indicate active.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.43
cpsSerialPortDBmode mandatory
Data buffering mode : circ or line.
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.44
cpsSerialPortDBsyslog mandatory
Size of the data buffer sent to syslog.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.45
cpsSerialPortDBmenu mandatory
Menu type for data buffering.
0 will indicate display Menu,
1 will indicate inactive,
2 will indicate DB,
3 will indicate Parc.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.46
cpsSerialPortDBalarm mandatory
Alarm generation status.
0 will indicate inactive,
1 will indicate active.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.47
cpsSerialPortSSHbreak mandatory
Break sequence - ssh session.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.48
cpsSerialPortSniffSess mandatory
Sniff session type.
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.49
cpsSerialPortSniffAdm mandatory
List of admin users allowed to sniff session.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.50
cpsSerialPortSniffEsc mandatory
Escape sequence used in sniff session.
OctetStringr/w
Constraints:
range: 0-6
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.51
cpsSerialPortSniffMsess mandatory OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.52
cpsSerialPortTelnetMode mandatory
Mode negotiated by client telnet with the server.
0 will indicate text,
1 will indicate binary.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.53
cpsSerialPortSysBufSess mandatory
Syslog Buffering at all times.
0 will indicate yes,
1 will indicate no.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.54
cpsSerialPortLFSuppress mandatory
LF suppression in socket_server session.
0 will indicate inactive,
1 will indicate active.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.55
cpsSerialPortAutoInput mandatory
Input string used for auto answer.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.56
cpsSerialPortAutoOutput mandatory
Output string used for auto answer.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.57
cpsSerialPortBreakInterval mandatory
The break interval in milliseconds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.58

cpsInfoSerialPortTable

table mandatory
.1.3.6.1.4.1.318.1.1.19.1.3.1 · 1 row entry · 16 columns
This is the information of the specific serial port.
cpsInfoSerialPortEntry entry .1.3.6.1.4.1.318.1.1.19.1.3.1.1
One particular serial port.
Indexes
cpsInfoSerialPortNumber
Column Syntax OID
cpsInfoSerialPortNumber mandatory
Number to identify the serial port.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.1
cpsInfoSerialPortTty mandatory
The device name for the serial port.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.2
cpsInfoSerialPortName mandatory
Alias name given to the server connected to the serial port.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.3
cpsInfoSerialPortSpeed mandatory
The speed for serial port.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.4
cpsInfoSerialPortTxBytes mandatory
The number of transmitted bytes by the serial port.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.5
cpsInfoSerialPortRXBytes mandatory
The number of received bytes by the serial port.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.6
cpsInfoSerialPortErrFrame mandatory
The number of frame errors.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.7
cpsInfoSerialPortErrParity mandatory
The number of parity errors.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.8
cpsInfoSerialPortErrBreaks mandatory
The number of breaks errors.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.9
cpsInfoSerialPortErrOverrun mandatory
The number of overrun errors.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.10
cpsInfoSerialPortSigDTR mandatory
The state of the DTR signal.
0 will indicate down,
1 will indicate up.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.11
cpsInfoSerialPortSigCD mandatory
The state of the DCD signal.
0 will indicate down,
1 will indicate up.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.12
cpsInfoSerialPortSigDSR mandatory
The state of the DSR signal.
0 will indicate down,
1 will indicate up.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.13
cpsInfoSerialPortSigRTS mandatory
The state of the RTS signal.
0 will indicate down,
1 will indicate up.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.14
cpsInfoSerialPortSigCTS mandatory
The state of the CTS signal.
0 will indicate down,
1 will indicate up.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.15
cpsInfoSerialPortSigRI mandatory
The state of the RI signal.
0 will indicate down,
1 will indicate up.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.19.1.3.1.1.16
.1.3.6.1.4.1.318.1.1.22.1.2 · 1 row entry · 6 columns
Allows for getting information about the modular
distribution metering equipment.
isxModularDistInfoEntry entry .1.3.6.1.4.1.318.1.1.22.1.2.1
An entry containing information about an individual metering segment.
Indexes
isxModularDistInfoSegmentIndex
Column Syntax OID
isxModularDistInfoSegmentIndex mandatory
The index of the metering segment.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.1.2.1.1
isxModularDistInfoMeterModelNumber mandatory
The model number of the metering board for this segment.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.1.2.1.2
isxModularDistInfoMeterSerialNumber mandatory
The serial number of the metering board for this segment.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.1.2.1.3
isxModularDistInfoMeterDateOfManufacture mandatory
The date of manufacture for the metering board for this segment,
in the format mm/dd/yyyy.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.1.2.1.4
isxModularDistInfoMeterFirmwareRev mandatory
The firmware revision number of the metering board for this segment.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.1.2.1.5
isxModularDistInfoMeterHardwareRev mandatory
The hardware revision number of the metering board for this segment.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.1.2.1.6
.1.3.6.1.4.1.318.1.1.22.2.2 · 1 row entry · 6 columns
Allows for getting basic information about the distribution modules
installed in the system.
isxModularDistModuleInfoEntry entry .1.3.6.1.4.1.318.1.1.22.2.2.1
An entry containing information about a specific distribution module.
Indexes
isxModularDistModuleInfoModIndex
Column Syntax OID
isxModularDistModuleInfoModIndex mandatory
The number of the distribution module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.2.1.1
isxModularDistModuleInfoAlarmStatus mandatory
The status of this module. This reflects the indicator lamp(s) on the front of the module.
A value of notPresent indicates that the module is not installed.
A value of unknown indicates that there is no communication wi…
Enumeration
Enumerated Values:
1normal
2warning
3critical
4notPresent
5unknown
.1.3.6.1.4.1.318.1.1.22.2.2.1.2
isxModularDistModuleInfoModelNumber mandatory
The model number of the distribution module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.2.2.1.3
isxModularDistModuleInfoSerialNumber mandatory
The serial number of the distribution module.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.2.2.1.4
isxModularDistModuleInfoDateOfManufacture mandatory
The date that the distribution module was manufactured.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.2.2.1.5
isxModularDistModuleInfoNumCables mandatory
The number of cables provided by this distribution module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.2.1.6
.1.3.6.1.4.1.318.1.1.22.2.4 · 1 row entry · 11 columns
Allows for getting operational information about the distribution modules.
isxModularDistModuleBreakerEntry entry .1.3.6.1.4.1.318.1.1.22.2.4.1
An entry containing information about a specific distribution modules and circuit breakers.
Indexes
isxModularDistModuleBreakerModIndex isxModularDistModuleBreakerPhaseIndex
Column Syntax OID
isxModularDistModuleBreakerModIndex mandatory
The distribution module number.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.4.1.1
isxModularDistModuleBreakerPhaseIndex mandatory
The index to an individual breaker in the distribution module. The index also corresponds
to the system phase to which the breaker is attached.
Enumeration
Enumerated Values:
1phaseL1
2phaseL2
3phaseL3
.1.3.6.1.4.1.318.1.1.22.2.4.1.2
isxModularDistModuleBreakerAlarmStatus mandatory
This is a bit map representing the active alarms for this breaker:

b0 - Minimum current threshold exceeded (critical)
b1 - Low current threshold exceeded (warning)
b2 - High current threshold exceeded (wa…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.4.1.3
isxModularDistModuleBreakerRating mandatory
The current rating of the breaker.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.4.1.4
isxModularDistModuleBreakerPhysicalGroup mandatory
Numeric value used to indicate that a breaker is a part of a multi-pole breaker.
Breakers within a distribution module, with equivalent physical group numbers,
may have their handles physically tied together.
A value of…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.4.1.5
isxModularDistModuleBreakerCableNum mandatory
Numeric value used to indicate the distribution cable to which
this breaker is connected. These distribution cables are described
in the table isxModularDistModuleOutputTable,
and indexed by the OID isxModularDistModule…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.4.1.6
isxModularDistModuleBreakerPosition mandatory
The physical status of this breaker pole, either closed or open (including tripped).
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.22.2.4.1.7
isxModularDistModuleBreakerPositionAlarms mandatory
Enable or disable breaker position alarms for this circuit breaker.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.2.4.1.8
isxModularDistModuleBreakerCurrent mandatory
The current flowing though this breaker. Measured in tenths of amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.4.1.9
isxModularDistModuleBreakerPercent mandatory
The loading on this breaker as a percentage of the breaker's current rating.
Expressed in tenths of percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.4.1.10
isxModularDistModuleBreakerPower mandatory
The power being supplied through this breaker. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.4.1.11
.1.3.6.1.4.1.318.1.1.22.2.6 · 1 row entry · 23 columns
Allows for getting and setting information related to the
load equipment being fed by the distribution modules in the ISX
Modular Distribution System.
isxModularDistModuleOutputEntry entry .1.3.6.1.4.1.318.1.1.22.2.6.1
An entry containing information about a specific distribution module
and its output distribution cables.
Indexes
isxModularDistModuleOutputModIndex isxModularDistModuleOutputCordIndex
Column Syntax OID
isxModularDistModuleOutputModIndex mandatory
The number of the distribution module supplying power to the load equipment.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.1
isxModularDistModuleOutputNumCables mandatory
The number of distribution cables provided by this module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.2
isxModularDistModuleOutputCordIndex mandatory
The index of an individual distribution cable supplied by this module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.3
isxModularDistModuleOutputName mandatory
A string describing the load equipment being supplied by this distribution cable.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.2.6.1.4
isxModularDistModuleOutputLocation mandatory
A string describing the location of equipment being supplied by distribution cable.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.2.6.1.5
isxModularDistModuleOutputStatus mandatory
This reflects the worse case severity for alarms associated with this distribution cable.
A value of notPresent indicates that the cable does not exist for this module.
A value of unknown indicates that the there is no …
Enumeration
Enumerated Values:
1normal
2warning
3critical
4notPresent
6unknown
.1.3.6.1.4.1.318.1.1.22.2.6.1.6
isxModularDistModuleOutputAlarmGeneration mandatory
Enable or disable all alarm generation related to this distribution cable.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.2.6.1.7
isxModularDistModuleOutputBreakerMap mandatory
This is a bit map representing the breaker poles within the
module that are associated with this distribution cable.
The following 3 bits are used to indicate the indices of
the breakers feeding the cable:
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.8
isxModularDistModuleOutputThresholdMin mandatory
When the current drops below this value a critical alarm will exist.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.9
isxModularDistModuleOutputThresholdLow mandatory
When the current drops below this value a warning alarm will exist.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.10
isxModularDistModuleOutputThresholdHigh mandatory
When the current exceeds this value a warning alarm will exist.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.11
isxModularDistModuleOutputThresholdMax mandatory
When the current exceeds this value a critical alarm will exist.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.12
isxModularDistModuleOutputAlarmMinEnable mandatory
Enable or disable minimum current alarm generation for this distribution cable.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.2.6.1.13
isxModularDistModuleOutputAlarmLowEnable mandatory
Enable or disable low current alarm generation for this distribution cable.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.2.6.1.14
isxModularDistModuleOutputAlarmHighEnable mandatory
Enable or disable high current alarm generation for this distribution cable.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.2.6.1.15
isxModularDistModuleOutputAlarmMaxEnable mandatory
Enable or disable maximum current alarm generation for this distribution cable.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.2.6.1.16
isxModularDistModuleOutputCableLength mandatory
The length of this distribution cable. Specified in tenths of meters.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.17
isxModularDistModuleOutputConnectorType mandatory
A string describing the connector on the end of this distribution cable.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.2.6.1.18
isxModularDistModuleOutputAvailableVoltages mandatory
This is a bit map representing the voltages that are available at the connector.
6 bits are used to indicate the following:

b0 - L1
b1 - L2
b2 - L3
b3 - L1-2
b4 - L2-3
b5 - L3-1
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.19
isxModularDistModuleOutputTotalPower mandatory
The total power being consumed by the load equipment supplied by this distribution cable.
Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.20
isxModularDistModuleOutputKwhUsage mandatory
The total energy consumed by the load equipment fed by this distribution cable.
This is the total since the date specified in the isxModularDistModuleOutputKwhResetDate
OID, and may be cleared using the isxModularDistMo…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.2.6.1.21
isxModularDistModuleOutputKwhReset mandatory
Writing yes to this OID will reset the total kWh usage shown
in the isxModularDistModuleOutputKwhUsage OID.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.22.2.6.1.22
isxModularDistModuleOutputKwhResetDate mandatory
The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.2.6.1.23
.1.3.6.1.4.1.318.1.1.22.3.2 · 1 row entry · 20 columns
Allows for getting information about distribution subfeed breakers.
isxModularDistSubFeedInfoEntry entry .1.3.6.1.4.1.318.1.1.22.3.2.1
An entry containing information about a specific distribution subfeed.
Indexes
isxModularDistSubFeedInfoSubIndex
Column Syntax OID
isxModularDistSubFeedInfoSubIndex mandatory
The index of an individual subfeed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.2.1.1
isxModularDistSubFeedInfoName mandatory
A string describing the load equipment being supplied by this subfeed.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.3.2.1.2
isxModularDistSubFeedInfoLocation mandatory
A string describing the location of the equipment being supplied by this subfeed.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.3.2.1.3
isxModularDistSubFeedInfoBreakerRating mandatory
The current rating of this subfeed breaker.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.2.1.4
isxModularDistSubFeedInfoBreakerPosition mandatory
The operational status of this breaker, either closed or open (including tripped).
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.318.1.1.22.3.2.1.5
isxModularDistSubFeedInfoAlarmStatus mandatory
The worst case alarm status for this subfeed.
Enumeration
Enumerated Values:
1normal
2warning
3critical
.1.3.6.1.4.1.318.1.1.22.3.2.1.6
isxModularDistSubFeedInfoAlarmGeneration mandatory
Enable or disable all alarm generation related to this subfeed.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.3.2.1.7
isxModularDistSubFeedInfoThresholdMin mandatory
When the current drops below this value a critical alarm will exist.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.2.1.8
isxModularDistSubFeedInfoThresholdLow mandatory
When the current drops below this value a warning alarm will exist.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.2.1.9
isxModularDistSubFeedInfoThresholdHigh mandatory
When the current exceeds this value a warning alarm will exist.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.2.1.10
isxModularDistSubFeedInfoThresholdMax mandatory
When the current exceeds this value a critical alarm will exist.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.2.1.11
isxModularDistSubFeedInfoAlarmMinEnable mandatory
Enable or disable minimum current alarm generation for this subfeed.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.3.2.1.12
isxModularDistSubFeedInfoAlarmLowEnable mandatory
Enable or disable low current alarm generation for this subfeed.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.3.2.1.13
isxModularDistSubFeedInfoAlarmHighEnable mandatory
Enable or disable high current alarm generation for this subfeed.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.3.2.1.14
isxModularDistSubFeedInfoAlarmMaxEnable mandatory
Enable or disable maximum current alarm generation for this subfeed.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.3.2.1.15
isxModularDistSubFeedInfoBreakerAlarmEnable mandatory
Enable or disable breaker position alarms for this subfeed.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.22.3.2.1.16
isxModularDistSubFeedInfoTotalPower mandatory
The total power being supplied by this subfeed. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.2.1.17
isxModularDistSubFeedInfoKwhUsage mandatory
The total energy consumed by the load equipment fed by this subfeed.
This is the total since the date specified in the isxModularDistSubFeedInfoKwhResetDate
OID, and may be cleared using the isxModularDistSubFeedInfoKwh…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.2.1.18
isxModularDistSubFeedInfoKwhReset mandatory
Writing yes to this OID will reset the total kWh usage shown
in the isxModularDistSubFeedInfoKwhUsage OID.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.22.3.2.1.19
isxModularDistSubFeedInfoKwhResetDate mandatory
The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.22.3.2.1.20
.1.3.6.1.4.1.318.1.1.22.3.4 · 1 row entry · 6 columns
Allows for getting subfeed phase loading information.
isxModularDistSubFeedLoadingEntry entry .1.3.6.1.4.1.318.1.1.22.3.4.1
An entry containing data for an individual subfeed.
Indexes
isxModularDistSubFeedLoadingSubIndex isxModularDistSubFeedLoadingPhaseIndex
Column Syntax OID
isxModularDistSubFeedLoadingSubIndex mandatory
The index of an individual subfeed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.4.1.1
isxModularDistSubFeedLoadingPhaseIndex mandatory
Description of each input phase entry in the table.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.22.3.4.1.2
isxModularDistSubFeedLoadingAlarmStatus mandatory
This is a bit map representing the active alarms for this subfeed:

b0 - Minimum current threshold exceeded (critical)
b1 - Low current threshold exceeded (warning)
b2 - High current threshold exceeded (wa…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.4.1.3
isxModularDistSubFeedLoadingCurrent mandatory
The current flowing though this subfeed phase. Measured in tenths of amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.4.1.4
isxModularDistSubFeedLoadingPercent mandatory
The loading on this subfeed phase as a percentage of the subfeed's current rating.
Expressed in tenths of percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.4.1.5
isxModularDistSubFeedLoadingPower mandatory
The power being supplied by this subfeed phase. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.3.4.1.6
.1.3.6.1.4.1.318.1.1.22.4.1.15 · 1 row entry · 4 columns
Allows for getting the system output voltage information.
isxModularDistSysVoltageEntry entry .1.3.6.1.4.1.318.1.1.22.4.1.15.1
An entry containing data for an individual system output phase.
Indexes
isxModularDistSysVoltagePhaseIndex
Column Syntax OID
isxModularDistSysVoltagePhaseIndex mandatory
Description of each phase entry in the table.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.22.4.1.15.1.1
isxModularDistSysVoltageAlarmStatus mandatory
This is a bit map representing the active alarms for this output phase:

b0 - Minimum voltage threshold exceeded (critical)
b1 - Low voltage threshold exceeded (warning)
b2 - High voltage threshold exceede…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.4.1.15.1.2
isxModularDistSysVoltageLtoN mandatory
Line-to-neutral system output voltage available at the distribution panel.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.4.1.15.1.3
isxModularDistSysVoltageLtoL mandatory
Line-to-line system output voltage available at the distribution panel.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.4.1.15.1.4
.1.3.6.1.4.1.318.1.1.22.4.2.11 · 1 row entry · 4 columns
Allows for getting the total system phase current information.
isxModularDistSysCurrentEntry entry .1.3.6.1.4.1.318.1.1.22.4.2.11.1
An entry containing data for an individual system output phase.
Indexes
isxModularDistSysCurrentPhaseIndex
Column Syntax OID
isxModularDistSysCurrentPhaseIndex mandatory
Description of each phase entry in the table.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.22.4.2.11.1.1
isxModularDistSysCurrentAlarmStatus mandatory
This is a bit map representing the active alarms for this output phase:

b0 - Minimum current threshold exceeded (critical)
b1 - Low current threshold exceeded (warning)
b2 - High current threshold exceede…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.4.2.11.1.2
isxModularDistSysCurrentAmps mandatory
The current flowing though this system output phase. Measured in tenths of amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.4.2.11.1.3
isxModularDistSysCurrentPercent mandatory
The loading on this system output phase as a percentage of the panel current rating.
Expressed in tenths of percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.4.2.11.1.4
.1.3.6.1.4.1.318.1.1.22.4.3.5 · 1 row entry · 3 columns
Allows for getting the total system phase power loading information.
isxModularDistSysPowerEntry entry .1.3.6.1.4.1.318.1.1.22.4.3.5.1
An entry containing data for an individual system output phase.
Indexes
isxModularDistSysPowerPhaseIndex
Column Syntax OID
isxModularDistSysPowerPhaseIndex mandatory
Description of each phase entry in the table.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.318.1.1.22.4.3.5.1.1
isxModularDistSysPowerKw mandatory
The power being supplied by this system output phase. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.4.3.5.1.2
isxModularDistSysPowerKwhPhaseUsage mandatory
The energy consumed by the load equipment on this system output phase.
This is the total since the date specified in the isxModularDistSysPowerKwhResetDate
OID, and may be cleared using the isxModularDistSysPowerKwhRese…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.22.4.3.5.1.3

uioSensorStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.25.1.2 · 1 row entry · 10 columns
Allows for getting sensor status information.
uioSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.25.1.2.1
The unit from which to get data.
Indexes
uioSensorStatusPortID uioSensorStatusSensorID
Column Syntax OID
uioSensorStatusPortID mandatory
The ID of the port to which the sensor is attached.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.2.1.1
uioSensorStatusSensorID mandatory
The ID of the sensor.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.2.1.2
uioSensorStatusSensorName mandatory
The sensor name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.1.2.1.3
uioSensorStatusSensorLocation mandatory
The location of the sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.1.2.1.4
uioSensorStatusTemperatureDegF mandatory
The sensor's current temperature reading in degrees Fahrenheit.
-1 indicates an invalid reading due to lost communications.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.2.1.5
uioSensorStatusTemperatureDegC mandatory
The sensor's current temperature reading in degrees Celsius.
-1 indicates an invalid reading due to lost communications.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.2.1.6
uioSensorStatusHumidity mandatory
The sensor's current humidity reading in percent relative
humidity. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.2.1.7
uioSensorStatusViolationStatus mandatory
The violation status of the sensor. This integer should be interpreted
as a bit map, with each bit representing the presence or absence of
the specific alarm conditions listed below. The bit will be '1' if
the conditi…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.2.1.8
uioSensorStatusAlarmStatus mandatory
The alarm status of the sensor.
Enumeration
Enumerated Values:
1uioNormal
2uioWarning
3uioCritical
4sensorStatusNotApplicable
.1.3.6.1.4.1.318.1.1.25.1.2.1.9
uioSensorStatusCommStatus mandatory
The communications status of the sensor.
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.25.1.2.1.10

uioSensorConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.25.1.4 · 1 row entry · 22 columns
Allows for configuring the sensor.
uioSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.25.1.4.1
The sensor from which to get configuration.
Indexes
uioSensorConfigPortID uioSensorConfigSensorID
Column Syntax OID
uioSensorConfigPortID mandatory
The ID of the port to which the sensor is attached.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.1
uioSensorConfigSensorID mandatory
The ID of the sensor.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.2
uioSensorConfigSensorName mandatory
The sensor name.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.1.4.1.3
uioSensorConfigSensorLocation mandatory
The location of the sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.1.4.1.4
uioSensorConfigMinTemperatureThreshold mandatory
The minimum (critical) temperature alarm threshold for the
probe in degrees C. Must be lower than the low threshold to
ensure proper sensor alarm behavior.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.5
uioSensorConfigLowTemperatureThreshold mandatory
The low (warning) temperature alarm threshold for the probe
in degrees C. Must be higher than the minimum threshold and
lower than the high threshold to ensure proper sensor alarm
behavior.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.6
uioSensorConfigHighTemperatureThreshold mandatory
The high (warning) temperature alarm threshold for the probe
in degrees C. Must be lower than the maximum threshold and
higher than the low threshold to ensure proper sensor alarm
behavior.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.7
uioSensorConfigMaxTemperatureThreshold mandatory
The maximum (critical) temperature alarm threshold for the
probe in degrees C. Must be higher than the high threshold
to ensure proper sensor alarm behavior.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.8
uioSensorConfigTemperatureHysteresis mandatory
The number of degrees C beyond the temperature thresholds at
which an active temperature alarm will be cleared. This value
applies to all temperature thresholds.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.9
uioSensorConfigMinTemperatureEnable mandatory
The minimum temperature alarm enable/disable for the sensor.
1 - disabled
2 - enabled
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.25.1.4.1.10
uioSensorConfigLowTemperatureEnable mandatory
The low temperature alarm enable/disable for the sensor.
1 - disabled
2 - enabled
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.25.1.4.1.11
uioSensorConfigHighTemperatureEnable mandatory
The high temperature alarm enable/disable for the sensor.
1 - disabled
2 - enabled
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.25.1.4.1.12
uioSensorConfigMaxTemperatureEnable mandatory
The maximum temperature alarm enable/disable for the sensor.
1 - disabled
2 - enabled
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.25.1.4.1.13
uioSensorConfigMinHumidityThreshold mandatory
The minimum (critical) humidity alarm threshold for the
probe in percent relative humidity. Must be lower than the
low threshold to ensure proper sensor alarm behavior. -1 if
the sensor doesn't read humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.14
uioSensorConfigLowHumidityThreshold mandatory
The low (warning) humidity alarm threshold for the probe in
percent relative humidity. Must be higher than the minimum
threshold and lower than the high threshold to ensure proper
sensor alarm behavior. -1 if the sensor…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.15
uioSensorConfigHighHumidityThreshold mandatory
The high (warning) humidity alarm threshold for the probe in
percent relative humidity. Must be lower than the maximum
threshold and higher than the low threshold to ensure proper
sensor alarm behavior. -1 if the sensor…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.16
uioSensorConfigMaxHumidityThreshold mandatory
The maximum (critical) humidity alarm threshold for the
probe in percent relative humidity. Must be higher than the
high threshold to ensure proper sensor alarm behavior. -1 if
the sensor doesn't read humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.17
uioSensorConfigHumidityHysteresis mandatory
The number of percent relative humidity beyond the humidity
thresholds at which an active humidity alarm will be cleared.
This value applies to all humidity thresholds. -1 if the
sensor doesn't read humidity.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.1.4.1.18
uioSensorConfigMinHumidityEnable mandatory
The minimum humidity alarm enable/disable for the sensor.
1 - disabled (always set if the sensor doesn't read humidity)
2 - enabled
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.25.1.4.1.19
uioSensorConfigLowHumidityEnable mandatory
The low humidity alarm enable/disable for the sensor.
1 - disabled (always set if the sensor doesn't read humidity)
2 - enabled
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.25.1.4.1.20
uioSensorConfigHighHumidityEnable mandatory
The high humidity alarm enable/disable for the sensor.
1 - disabled (always set if the sensor doesn't read humidity)
2 - enabled
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.25.1.4.1.21
uioSensorConfigMaxHumidityEnable mandatory
The maximum humidity alarm enable/disable for the sensor.
1 - disabled (always set if the sensor doesn't read humidity)
2 - enabled
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.25.1.4.1.22
.1.3.6.1.4.1.318.1.1.25.2.2 · 1 row entry · 7 columns
Allows for getting input contact status information.
uioInputContactStatusEntry entry .1.3.6.1.4.1.318.1.1.25.2.2.1
The input contact from which to get data.
Indexes
uioInputContactStatusPortID uioInputContactStatusContactID
Column Syntax OID
uioInputContactStatusPortID mandatory
The ID of the port to which the input contact is attached.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.2.2.1.1
uioInputContactStatusContactID mandatory
The ID of the input contact on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.2.2.1.2
uioInputContactStatusContactName mandatory
The input contact name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.2.2.1.3
uioInputContactStatusContactLocation mandatory
The location of the input contact.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.2.2.1.4
uioInputContactStatusCurrentState mandatory
The current state of the input contact.
Enumeration
Enumerated Values:
1uioInputClosed
2uioInputOpen
3uioInputDisabled
4inputStateNotApplicable
.1.3.6.1.4.1.318.1.1.25.2.2.1.5
uioInputContactStatusAlarmStatus mandatory
The alarm status of the input contact.
Enumeration
Enumerated Values:
1uioNormal
2uioWarning
3uioCritical
4inputStatusNotApplicable
.1.3.6.1.4.1.318.1.1.25.2.2.1.6
uioInputContactStatusCommStatus mandatory
The communications status of the input contact.
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.25.2.2.1.7
.1.3.6.1.4.1.318.1.1.25.2.4 · 1 row entry · 7 columns
Allows for configuring the input contacts.
uioInputContactConfigEntry entry .1.3.6.1.4.1.318.1.1.25.2.4.1
The input contact from which to get configuration.
Indexes
uioInputContactConfigPortID uioInputContactConfigContactID
Column Syntax OID
uioInputContactConfigPortID mandatory
The ID of the port to which the input contact is attached.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.2.4.1.1
uioInputContactConfigContactID mandatory
The ID of the input contact on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.2.4.1.2
uioInputContactConfigContactName mandatory
The input contact name.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.2.4.1.3
uioInputContactConfigContactLocation mandatory
The location of the input contact.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.2.4.1.4
uioInputContactConfigEnable mandatory
Enable or disable this input contact.
1 - disabled
2 - enabled
Enumerationr/w
Enumerated Values:
1uioInputContactDisabled
2uioInputContactEnabled
.1.3.6.1.4.1.318.1.1.25.2.4.1.5
uioInputContactConfigNormalState mandatory
The normal (non-alarm) state of the input contact.
1 - normally open
2 - normally closed
Enumerationr/w
Enumerated Values:
1uioInputNormallyOpen
2uioInputNormallyClosed
.1.3.6.1.4.1.318.1.1.25.2.4.1.6
uioInputContactConfigSeverity mandatory
The severity of the alarm that this input contact will
generate in the abnormal state.
1 - critical severity
2 - warning severity
Enumerationr/w
Enumerated Values:
1uioInputCriticalSeverity
2uioInputWarningSeverity
.1.3.6.1.4.1.318.1.1.25.2.4.1.7
.1.3.6.1.4.1.318.1.1.25.3.2 · 1 row entry · 7 columns
Allows for getting output relay status information.
uioOutputRelayStatusEntry entry .1.3.6.1.4.1.318.1.1.25.3.2.1
The unit from which to get data.
Indexes
uioOutputRelayStatusPortID uioOutputRelayStatusRelayID
Column Syntax OID
uioOutputRelayStatusPortID mandatory
The ID of the port to which the output relay is attached.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.3.2.1.1
uioOutputRelayStatusRelayID mandatory
The ID of the output relay on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.3.2.1.2
uioOutputRelayStatusRelayName mandatory
The output relay name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.3.2.1.3
uioOutputRelayStatusRelayLocation mandatory
The location of the output relay.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.3.2.1.4
uioOutputRelayStatusCurrentState mandatory
The current state of the output relay.
Enumeration
Enumerated Values:
1uioOutputClosed
2uioOutputOpen
3outputStateNotApplicable
.1.3.6.1.4.1.318.1.1.25.3.2.1.5
uioOutputRelayStatusAlarmStatus mandatory
The alarm status of the output relay.
Enumeration
Enumerated Values:
1uioNormal
2uioWarning
3uioCritical
4inputStatusNotApplicable
.1.3.6.1.4.1.318.1.1.25.3.2.1.6
uioOutputRelayStatusCommStatus mandatory
The communications status of the output relay.
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.25.3.2.1.7
.1.3.6.1.4.1.318.1.1.25.3.4 · 1 row entry · 8 columns
Allows for configuring the output relay.
uioOutputRelayConfigEntry entry .1.3.6.1.4.1.318.1.1.25.3.4.1
The unit from which to get configuration.
Indexes
uioOutputRelayConfigPortID uioOutputRelayConfigRelayID
Column Syntax OID
uioOutputRelayConfigPortID mandatory
The ID of the port to which the output relay is attached.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.3.4.1.1
uioOutputRelayConfigRelayID mandatory
The ID of the output relay on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.3.4.1.2
uioOutputRelayConfigRelayName mandatory
The output relay name.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.3.4.1.3
uioOutputRelayConfigRelayLocation mandatory
The location of the output relay.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.3.4.1.4
uioOutputRelayConfigNormalState mandatory
The normal state of the output relay.
1 - normally open
2 - normally closed
Enumerationr/w
Enumerated Values:
1uioOutputNormallyOpen
2uioOutputNormallyClosed
.1.3.6.1.4.1.318.1.1.25.3.4.1.5
uioOutputRelayConfigControlState mandatory
Close or open the output relay for testing purposes. Always
returns 1 when read.
1 - close output relay
2 - open output relay
Enumerationr/w
Enumerated Values:
1uioOutputClose
2uioOutputOpen
.1.3.6.1.4.1.318.1.1.25.3.4.1.6
uioOutputRelayConfigDelay mandatory
The time a selected alarm condition must exist before the
output relay is activated. Valid values are whole seconds
from 0 to 65535.
RFC1155-SMITimeTicksr/w
Textual Convention: RFC1155-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.25.3.4.1.7
uioOutputRelayConfigHold mandatory
The minimum time the output relay remains activated after the
alarm occurs. Valid values are whole seconds from 0 to 65535.
RFC1155-SMITimeTicksr/w
Textual Convention: RFC1155-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.25.3.4.1.8
.1.3.6.1.4.1.318.1.1.25.4.2 · 1 row entry · 7 columns
Allows for getting fluid sensor status information.
uioSpotFluidSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.25.4.2.1
The unit from which to get data.
Indexes
uioSpotFluidSensorStatusPortID uioSpotFluidSensorStatusSensorID
Column Syntax OID
uioSpotFluidSensorStatusPortID mandatory
The ID of the port to which the fluid sensor is attached.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.4.2.1.1
uioSpotFluidSensorStatusSensorID mandatory
The ID of the fluid sensor on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.4.2.1.2
uioSpotFluidSensorStatusSensorName mandatory
The fluid sensor name.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.4.2.1.3
uioSpotFluidSensorStatusSensorLocation mandatory
The location of the fluid sensor.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.4.2.1.4
uioSpotFluidSensorStatusCurrentState mandatory
The current state of the fluid sensor.
Enumeration
Enumerated Values:
1uioFluidDetected
2uioNoFluid
3uioFluidStateNoCommunication
.1.3.6.1.4.1.318.1.1.25.4.2.1.5
uioSpotFluidSensorStatusAlarmStatus mandatory
The alarm status of the fluid sensor.
Enumeration
Enumerated Values:
1uioNormal
2uioCritical
3uioNoCommunication
4uioDisabled
.1.3.6.1.4.1.318.1.1.25.4.2.1.6
uioSpotFluidSensorStatusCommStatus mandatory
The communications status of the fluid sensor.
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.25.4.2.1.7
.1.3.6.1.4.1.318.1.1.25.4.4 · 1 row entry · 4 columns
Allows for configuring the fluid sensor.
uioSpotFluidSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.25.4.4.1
The unit from which to get configuration.
Indexes
uioSpotFluidSensorConfigPortID uioSpotFluidSensorConfigSensorID
Column Syntax OID
uioSpotFluidSensorConfigPortID mandatory
The ID of the port to which the fluid sensor is attached.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.4.4.1.1
uioSpotFluidSensorConfigSensorID mandatory
The ID of the fluid sensor on the module.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.25.4.4.1.2
uioSpotFluidSensorConfigSensorName mandatory
The fluid sensor name.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.4.4.1.3
uioSpotFluidSensorConfigSensorLocation mandatory
The location of the fluid sensor.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.25.4.4.1.4

rPDU2IdentTable

table mandatory
.1.3.6.1.4.1.318.1.1.26.2 · 1 row entry · 16 columns
A table of Rack PDU identification data
rPDU2IdentEntry entry .1.3.6.1.4.1.318.1.1.26.2.1
Identification data from Rack PDU being queried
Indexes
rPDU2IdentIndex
Column Syntax OID
rPDU2IdentIndex mandatory
The index to the Rack PDU identification table
entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.2.1.1
rPDU2IdentModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.2.1.2
rPDU2IdentName mandatory
A user-defined string identifying the Rack PDU
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.3
rPDU2IdentLocation mandatory
A user-defined string identifying the location
of the Rack PDU
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.4
rPDU2IdentHardwareRev mandatory
The Rack PDU hardware version
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.5
rPDU2IdentFirmwareRev mandatory
The Rack PDU firmware version
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.6
rPDU2IdentDateOfManufacture mandatory
The date the Rack PDU was manufactured
in mm/dd/yyyy format
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.7
rPDU2IdentModelNumber mandatory
The Rack PDU model number
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.8
rPDU2IdentSerialNumber mandatory
The Rack PDU serial number
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.9
rPDU2IdentContact mandatory
A user-defined string identifying the
person to contact regarding the Rack PDU
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.10
rPDU2IdentBootMonitorRev mandatory
The Rack PDU Boot Monitor version
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.11
rPDU2IdentLongDescription mandatory
The Rack PDU Long Description name
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.12
rPDU2IdentNMCSerialNumber mandatory
The Rack PDU Network Management Card (NMC) serial number
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.13
rPDU2IndentAppBuildDate mandatory
The Rack PDU Application build date
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.14
rPDU2IndentAOSBuildDate mandatory
The Rack PDU AOS build date
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.15
rPDU2IndentBootMonBuildDate mandatory
The Rack PDU Boot Monitor build date
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.2.1.16

rPDU2DeviceConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.26.4.1 · 1 row entry · 14 columns
A table of Rack PDU configuration data
rPDU2DeviceConfigEntry entry .1.3.6.1.4.1.318.1.1.26.4.1.1
Configuration data from Rack PDU being queried
Indexes
rPDU2DeviceConfigIndex
Column Syntax OID
rPDU2DeviceConfigIndex mandatory
The index to the Rack PDU table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.1.1.1
rPDU2DeviceConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.1.1.2
rPDU2DeviceConfigName mandatory
A user-defined string identifying the Rack PDU
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.1.1.3
rPDU2DeviceConfigLocation mandatory
A user-defined string identifying the location
of the Rack PDU
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.1.1.4
rPDU2DeviceConfigDisplayOrientation mandatory
Indicates the intended physical orientation
of the display.

displayNormal(1) indicates normal orientation
displayReverse(2) indicates upside down orientation
Enumerationr/w
Enumerated Values:
1displayNormal
2displayReverse
.1.3.6.1.4.1.318.1.1.26.4.1.1.5
rPDU2DeviceConfigColdstartDelay mandatory
The amount of delay, measured in seconds, between
when power is provided to the Rack PDU and when
the Rack PDU provides basic master power to the
outlets.
Allowed values are:
-1 - never apply power automatically.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.1.1.6
rPDU2DeviceConfigLowLoadPowerThreshold mandatory
User-defined low power draw alarm threshold,
measured in tenths of kilowatts. Models that do
not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.1.1.7
rPDU2DeviceConfigNearOverloadPowerThreshold mandatory
User-defined near power overload threshold,
measured in tenths of kilowatts. Models that do
not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.1.1.8
rPDU2DeviceConfigOverloadPowerThreshold mandatory
User-defined power overload threshold,
measured in tenths of kilowatts. Models that do
not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.1.1.9
rPDU2DeviceConfigDevicePeakPowerReset mandatory
Setting this OID to reset (2) will cause the existing peak power value
to be replaced by the current load power value.

Getting this OID will do nothing and return the noOperation(1) value.
Models that do …
Enumerationr/w
Enumerated Values:
1noOperation
2reset
3notSupported
.1.3.6.1.4.1.318.1.1.26.4.1.1.10
rPDU2DeviceConfigDeviceEnergyReset mandatory
Setting this OID to reset (2) will cause the device energy meter value
to be reset to zero.

Getting this OID in models that support this feature will do nothing
and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
3notSupported
.1.3.6.1.4.1.318.1.1.26.4.1.1.11
rPDU2DeviceConfigOutletsEnergyReset mandatory
Setting this OID to reset (2) will cause the all outlet energy meter values
to be reset to zero.

Getting this OID will do nothing and return the noOperation(1) value.

Models that do not sup…
Enumerationr/w
Enumerated Values:
1noOperation
2reset
3notSupported
.1.3.6.1.4.1.318.1.1.26.4.1.1.12
rPDU2DeviceConfigOutletsPeakLoadReset mandatory
Setting this OID to reset (2) will cause the all outlet peak load values
to be reset to zero.

Getting this OID will do nothing and return the noOperation(1) value.

Models that do not suppor…
Enumerationr/w
Enumerated Values:
1noOperation
2reset
3notSupported
.1.3.6.1.4.1.318.1.1.26.4.1.1.13
rPDU2DeviceConfigContact mandatory
A user-defined string identifying the
person to contact regarding the Rack PDU
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.1.1.14
.1.3.6.1.4.1.318.1.1.26.4.2 · 1 row entry · 13 columns
A table of Rack PDU properties
rPDU2DevicePropertiesEntry entry .1.3.6.1.4.1.318.1.1.26.4.2.1
Properties of the Rack PDU being queried
Indexes
rPDU2DevicePropertiesIndex
Column Syntax OID
rPDU2DevicePropertiesIndex mandatory
The index to the Rack PDU properties table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.1
rPDU2DevicePropertiesModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.2
rPDU2DevicePropertiesName mandatory
A user-defined string identifying the Rack PDU
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.2.1.3
rPDU2DevicePropertiesNumOutlets mandatory
The number of outlets on the Rack PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.4
rPDU2DevicePropertiesNumSwitchedOutlets mandatory
The number of switched outlets on the Rack PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.5
rPDU2DevicePropertiesNumMeteredOutlets mandatory
The number of metered outlets on the Rack PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.6
rPDU2DevicePropertiesNumPhases mandatory
The number of phases present in the Rack PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.7
rPDU2DevicePropertiesNumMeteredBanks mandatory
The number of metered banks present in the Rack PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.8
rPDU2DevicePropertiesMaxCurrentRating mandatory
The maximum current rating, measured in Amps, for
the Rack PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.9
rPDU2DevicePropertiesOrientation mandatory
Rack PDU orientation
Enumeration
Enumerated Values:
1horizontal
2vertical
3verticalISXv2
4verticalISXv3
.1.3.6.1.4.1.318.1.1.26.4.2.1.10
rPDU2DevicePropertiesOutletLayout mandatory
Getting this OID will return outlet layout for the device.

seqPhaseToNeutral(1) indicates outlet layout as follows:
1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
or for single phase SKUs, all outlets 1-N
Enumeration
Enumerated Values:
1seqPhaseToNeutral
2seqPhaseToPhase
3seqPhToNeu21PhToPh
4seqPhToPhGrouped
5seqPhToNGrouped
6seqPToN1516PToPGrouped
7seqPhToPh2xGrouped
8seqPhToN2xGrouped
9seqNotApplicable
10seqPhToNPhToPhPhToN
.1.3.6.1.4.1.318.1.1.26.4.2.1.11
rPDU2DevicePropertiesMaxPhaseCurrentRating mandatory
The maximum current rating, measured in Amps, for
the Rack PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.12
rPDU2DevicePropertiesDevicePowerRating mandatory
The maximum power rating, measured in tenths of kilowatts, for
the Rack PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.2.1.13

rPDU2DeviceStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.26.4.3 · 1 row entry · 18 columns
A table of Rack PDU status information
rPDU2DeviceStatusEntry entry .1.3.6.1.4.1.318.1.1.26.4.3.1
Status information from the Rack PDU being queried
Indexes
rPDU2DeviceStatusIndex
Column Syntax OID
rPDU2DeviceStatusIndex mandatory
The index to the Rack PDU status table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.3.1.1
rPDU2DeviceStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.3.1.2
rPDU2DeviceStatusName mandatory
A user-defined string identifying the Rack PDU
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.3.1.3
rPDU2DeviceStatusLoadState mandatory
Indicates the present load status of the Rack PDU.
Models that do not support this feature will respond to this OID
with a value of notsupported (5).
Enumeration
Enumerated Values:
1lowLoad
2normal
3nearOverload
4overload
5notsupported
.1.3.6.1.4.1.318.1.1.26.4.3.1.4
rPDU2DeviceStatusPower mandatory
The power consumption of the Rack PDU load in hundredths of kilowatts.
Models that do not support this feature will respond to this OID
with a value of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.3.1.5
rPDU2DeviceStatusPeakPower mandatory
The peak power consumption of the Rack PDU load in hundredths of kilowatts.
Models that do not support this feature will respond to this OID with a value
of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.3.1.6
rPDU2DeviceStatusPeakPowerTimestamp mandatory
Indicates the date and time that peak power consumption occurred.
Models that do not support this feature will respond to this OID with string
'notsupported'.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.3.1.7
rPDU2DeviceStatusPeakPowerStartTime mandatory
Indicates the date and time of the last device peak power reset.
Models that do not support this feature will respond to this OID with string
'notsupported'.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.3.1.8
rPDU2DeviceStatusEnergy mandatory
A user resettable energy meter measuring Rack PDU load
energy consumption in tenths of kilowatt-hours. Models that do not
support this feature will respond to this OID
with a value of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.3.1.9
rPDU2DeviceStatusEnergyStartTime mandatory
Indicates the date and time of the last device energy
meter reset. Models that do not support this feature will
respond to this OID with string 'notsupported'.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.3.1.10
rPDU2DeviceStatusCommandPending mandatory
Indicates whether or not the device
is processing a pending command. If
the commandPendingUnknown (3) value is
returned, all devices powered by the
Rack PDU should be shut down. The
Rack PDU's power should then be cyc…
Enumeration
Enumerated Values:
1commandPending
2noCommandPending
3commandPendingUnknown
.1.3.6.1.4.1.318.1.1.26.4.3.1.11
rPDU2DeviceStatusPowerSupplyAlarm mandatory
Indicates a power supply alarm is active when value
equals alarm (2)
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.26.4.3.1.12
rPDU2DeviceStatusPowerSupply1Status mandatory
Indicates whether or not an alarm is active in Power
Supply 1
Enumeration
Enumerated Values:
1normal
2alarm
3notInstalled
.1.3.6.1.4.1.318.1.1.26.4.3.1.13
rPDU2DeviceStatusPowerSupply2Status mandatory
Indicates whether or not an alarm is active in Power
Supply 2
Enumeration
Enumerated Values:
1normal
2alarm
3notInstalled
.1.3.6.1.4.1.318.1.1.26.4.3.1.14
rPDU2DeviceStatusOutletsEnergyStartTime mandatory
Indicates the date and time of the last outlets energy
meter reset. Models that do not support this feature will
respond to this OID with string 'notsupported'.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.3.1.15
rPDU2DeviceStatusApparentPower mandatory
The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA).
Models that do not support this feature will respond to this OID
with a value of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.3.1.16
rPDU2DeviceStatusPowerFactor mandatory
The power factor of the Rack PDU load in hundredths. Models that do not support this feature
will respond to this OID with a value of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.3.1.17
rPDU2DeviceStatusNPSType mandatory
The device NPS status:
notNPS (1) indicates the Rack PDU is not in an NPS group.
host (2) indicates the Rack PDU has been designated as a host in an NPS group.
Only one Rack PDU in an NPS group is allowed to be the ho…
Enumeration
Enumerated Values:
1notNPS
2host
3guest
.1.3.6.1.4.1.318.1.1.26.4.3.1.18
.1.3.6.1.4.1.318.1.1.26.4.4 · 1 row entry · 4 columns
A table of Rack PDU control data
rPDU2DeviceControlEntry entry .1.3.6.1.4.1.318.1.1.26.4.4.1
Control data from Rack PDU being queried
Indexes
rPDU2DeviceControlIndex
Column Syntax OID
rPDU2DeviceControlIndex mandatory
The index to the Rack PDU control table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.4.1.1
rPDU2DeviceControlModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.4.4.1.2
rPDU2DeviceControlName mandatory
A user-defined string identifying the Rack PDU
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.4.4.1.3
rPDU2DeviceControlCommand mandatory
Setting this OID to immediateAllOn (1) will turn all outlets
on immediately.

Setting this OID to delayedAllOn (2) will turn all outlets on as
defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime
Enumerationr/w
Enumerated Values:
1immediateAllOn
2delayedAllOn
3immediateAllOff
4immediateAllReboot
5delayedAllReboot
6noCommandAll
7delayedAllOff
8cancelAllPendingCommands
.1.3.6.1.4.1.318.1.1.26.4.4.1.4

rPDU2PhaseConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.26.6.1 · 1 row entry · 8 columns
A table of Rack PDU phase configuration data
rPDU2PhaseConfigEntry entry .1.3.6.1.4.1.318.1.1.26.6.1.1
Configuration data from currently queried Rack
PDU phase
Indexes
rPDU2PhaseConfigIndex
Column Syntax OID
rPDU2PhaseConfigIndex mandatory
The index to the Rack PDU phase configuration
table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.1.1.1
rPDU2PhaseConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.1.1.2
rPDU2PhaseConfigNumber mandatory
The numeric phase ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.1.1.3
rPDU2PhaseConfigOverloadRestriction mandatory
This OID controls the behavior of a Switched Rack PDU
phase when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will alwa…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
4notSupported
.1.3.6.1.4.1.318.1.1.26.6.1.1.4
rPDU2PhaseConfigLowLoadCurrentThreshold mandatory
User-defined low load phase current
threshold in Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.1.1.5
rPDU2PhaseConfigNearOverloadCurrentThreshold mandatory
User-defined near phase overload warning
threshold in Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.1.1.6
rPDU2PhaseConfigOverloadCurrentThreshold mandatory
User-defined phase overload current
threshold in Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.1.1.7
rPDU2PhaseConfigPhasePeakCurrentReset mandatory
Setting this OID to reset (2) will cause the existing peak current value
to be replaced by the present load current value.

Getting this OID will do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.318.1.1.26.6.1.1.8
.1.3.6.1.4.1.318.1.1.26.6.2 · 1 row entry · 3 columns
A table of Rack PDU phase properties
rPDU2PhasePropertiesEntry entry .1.3.6.1.4.1.318.1.1.26.6.2.1
Properties of the currently queried Rack
PDU phase
Indexes
rPDU2PhasePropertiesIndex
Column Syntax OID
rPDU2PhasePropertiesIndex mandatory
The index to the Rack PDU phase properties
table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.2.1.1
rPDU2PhasePropertiesModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.2.1.2
rPDU2PhasePropertiesNumber mandatory
The numeric phase ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.2.1.3

rPDU2PhaseStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.26.6.3 · 1 row entry · 12 columns
A table of Rack PDU phase status data
rPDU2PhaseStatusEntry entry .1.3.6.1.4.1.318.1.1.26.6.3.1
Status data from currently queried Rack PDU
phase
Indexes
rPDU2PhaseStatusIndex
Column Syntax OID
rPDU2PhaseStatusIndex mandatory
The index to the Rack PDU phase status table
entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.1
rPDU2PhaseStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.2
rPDU2PhaseStatusNumber mandatory
The numeric phase ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.3
rPDU2PhaseStatusLoadState mandatory
Indicates the present load status of the Rack PDU
phase being queried
Enumeration
Enumerated Values:
1lowLoad
2normal
3nearOverload
4overload
.1.3.6.1.4.1.318.1.1.26.6.3.1.4
rPDU2PhaseStatusCurrent mandatory
Indicates the current draw, in tenths of Amps, of the load
on the Rack PDU phase being queried
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.5
rPDU2PhaseStatusVoltage mandatory
Indicates the Voltage, in Volts, of the Rack
PDU phase being queried. Models that do not support this
feature will respond to this OID with a value of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.6
rPDU2PhaseStatusPower mandatory
Indicates the load power, in hundredths of kilowatts (kW),
consumed on the Rack PDU phase being queried.
Models that do not support this feature will respond to this
OID with a value of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.7
rPDU2PhaseStatusApparentPower mandatory
Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA),
consumed on the Rack PDU phase being queried.
Models that do not support this feature will respond to this
OID with a value of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.8
rPDU2PhaseStatusPowerFactor mandatory
Indicates the load power factor, in hundredths,
of the Rack PDU phase being queried.
Models that do not support this feature will respond to
this OID with a value of -1.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.9
rPDU2PhaseStatusPeakCurrent mandatory
The peak current of the Rack PDU phase load in tenths of Amps
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.6.3.1.10
rPDU2PhaseStatusPeakCurrentTimestamp mandatory
Indicates the date and time that the peak current occurred
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.6.3.1.11
rPDU2PhaseStatusPeakCurrentStartTime mandatory
Indicates the date and time of the last phase peak current reset
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.6.3.1.12

rPDU2BankConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.26.8.1 · 1 row entry · 8 columns
A table of Rack PDU bank configuration data
rPDU2BankConfigEntry entry .1.3.6.1.4.1.318.1.1.26.8.1.1
Configuration data from currently queried
Rack PDU bank
Indexes
rPDU2BankConfigIndex
Column Syntax OID
rPDU2BankConfigIndex mandatory
The index to the Rack PDU bank configuration
table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.1.1.1
rPDU2BankConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.1.1.2
rPDU2BankConfigNumber mandatory
The numeric bank ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.1.1.3
rPDU2BankConfigOverloadRestriction mandatory
This OID controls the behavior of a Switched Rack PDU
bank when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will alway…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
4notSupported
.1.3.6.1.4.1.318.1.1.26.8.1.1.4
rPDU2BankConfigLowLoadCurrentThreshold mandatory
User-defined low load bank current
threshold in Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.1.1.5
rPDU2BankConfigNearOverloadCurrentThreshold mandatory
User-defined near bank overload current warning
threshold in Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.1.1.6
rPDU2BankConfigOverloadCurrentThreshold mandatory
User-defined bank overload current threshold
in Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.1.1.7
rPDU2BankConfigBankPeakCurrentReset mandatory
Setting this OID to reset (2) will cause the existing peak current value
to be replaced by the present load current value.

Getting this OID will do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.318.1.1.26.8.1.1.8
.1.3.6.1.4.1.318.1.1.26.8.2 · 1 row entry · 5 columns
A table of Rack PDU bank properties
rPDU2BankPropertiesEntry entry .1.3.6.1.4.1.318.1.1.26.8.2.1
Properties of the currently queried
Rack PDU bank
Indexes
rPDU2BankPropertiesIndex
Column Syntax OID
rPDU2BankPropertiesIndex mandatory
The index to the Rack PDU bank properties
table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.2.1.1
rPDU2BankPropertiesModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.2.1.2
rPDU2BankPropertiesNumber mandatory
The numeric bank ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.2.1.3
rPDU2BankPropertiesPhaseLayout mandatory
This OID describes the outlet phase connections on
the referenced bank as follows:

seqPhase1ToNeutral(1) indicates that bank outlets are
wired from Phase 1 to Neutral.

seqPhase2ToNeutral(2)…
Rpdu2OutletPhaseLayoutType
Textual Convention: Rpdu2OutletPhaseLayoutType Enumeration
Type Values:
1seqPhase1ToNeutral
2seqPhase2ToNeutral
3seqPhase3ToNeutral
4seqPhase1ToPhase2
5seqPhase2ToPhase3
6seqPhase3ToPhase1
.1.3.6.1.4.1.318.1.1.26.8.2.1.4
rPDU2BankPropertiesBreakerRating mandatory
If bank circuit breakers are present on the device, this OID will return
the rating of the breaker in Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.2.1.5

rPDU2BankStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.26.8.3 · 1 row entry · 8 columns
A table of Rack PDU bank status data
rPDU2BankStatusEntry entry .1.3.6.1.4.1.318.1.1.26.8.3.1
Status data from currently queried Rack PDU
bank
Indexes
rPDU2BankStatusIndex
Column Syntax OID
rPDU2BankStatusIndex mandatory
The index to the Rack PDU bank status
table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.3.1.1
rPDU2BankStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.3.1.2
rPDU2BankStatusNumber mandatory
The numeric bank ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.3.1.3
rPDU2BankStatusLoadState mandatory
Indicates the present load status of the Rack PDU
bank being queried
Enumeration
Enumerated Values:
1lowLoad
2normal
3nearOverload
4overload
.1.3.6.1.4.1.318.1.1.26.8.3.1.4
rPDU2BankStatusCurrent mandatory
Indicates the current draw, in tenths of Amps, of the load
on the Rack PDU bank being queried
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.3.1.5
rPDU2BankStatusPeakCurrent mandatory
The peak current of the Rack PDU bank load in tenths of Amps
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.8.3.1.6
rPDU2BankStatusPeakCurrentTimestamp mandatory
Indicates the date and time the bank peak current occurred
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.8.3.1.7
rPDU2BankStatusPeakCurrentStartTime mandatory
Indicates the date and time of the last bank peak current reset
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.8.3.1.8
.1.3.6.1.4.1.318.1.1.26.9.2.1 · 1 row entry · 8 columns
A table of Rack PDU switched outlet configuration data
rPDU2OutletSwitchedConfigEntry entry .1.3.6.1.4.1.318.1.1.26.9.2.1.1
Configuration data from currently queried
Rack PDU switched outlet
Indexes
rPDU2OutletSwitchedConfigIndex
Column Syntax OID
rPDU2OutletSwitchedConfigIndex mandatory
The index to the Rack PDU switched outlet
configuration table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.1.1.1
rPDU2OutletSwitchedConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.1.1.2
rPDU2OutletSwitchedConfigName mandatory
The user-defined switched outlet ID string
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.2.1.1.3
rPDU2OutletSwitchedConfigNumber mandatory
The numeric switched outlet ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.1.1.4
rPDU2OutletSwitchedConfigPowerOnTime mandatory
The amount of delay, in seconds, between when
power is provided to the Rack PDU and when
this switched outlet starts providing power.
Range -1...7200 where -1 = Never power on,
0 = immediate power on, and 1-7200 = secon…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.1.1.5
rPDU2OutletSwitchedConfigPowerOffTime mandatory
The amount of time, in seconds, this outlet will
delay powering off.
Range -1...7200 where -1 = Never power off,
0 = immediate power off, and 1-7200 = seconds to
delay.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.1.1.6
rPDU2OutletSwitchedConfigRebootDuration mandatory
After turning power off during a reboot sequence,
the amount of time to wait before turning power
to this outlet back on.
Range 5-60 seconds delay.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.1.1.7
rPDU2OutletSwitchedConfigExternalLink mandatory
User-defined external device web link.
Possible use cases could be the IP address of the external device
plugged into the outlet or its manufacturer web page for convenient
support such as user manuals, specifications…
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.2.1.1.8
.1.3.6.1.4.1.318.1.1.26.9.2.2 · 1 row entry · 6 columns
A table of Rack PDU switched outlet properties
rPDU2OutletSwitchedPropertiesEntry entry .1.3.6.1.4.1.318.1.1.26.9.2.2.1
Properties of the currently queried Rack PDU
switched outlet
Indexes
rPDU2OutletSwitchedPropertiesIndex
Column Syntax OID
rPDU2OutletSwitchedPropertiesIndex mandatory
The index to the Rack PDU switched outlet
properties table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.2.1.1
rPDU2OutletSwitchedPropertiesModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.2.1.2
rPDU2OutletSwitchedPropertiesName mandatory
The user-defined switched outlet ID string
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.2.2.1.3
rPDU2OutletSwitchedPropertiesNumber mandatory
The numeric switched outlet ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.2.1.4
rPDU2OutletSwitchedPropertiesPhaseLayout mandatory
This OID describes the phase connections of
the referenced outlet as follows:

seqPhase1ToNeutral(1) indicates that the outlet is
wired from Phase 1 to Neutral.

seqPhase2ToNeutral(2) indicat…
Rpdu2OutletPhaseLayoutType
Textual Convention: Rpdu2OutletPhaseLayoutType Enumeration
Type Values:
1seqPhase1ToNeutral
2seqPhase2ToNeutral
3seqPhase3ToNeutral
4seqPhase1ToPhase2
5seqPhase2ToPhase3
6seqPhase3ToPhase1
.1.3.6.1.4.1.318.1.1.26.9.2.2.1.5
rPDU2OutletSwitchedPropertiesBank mandatory
The numeric bank ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.2.1.6
.1.3.6.1.4.1.318.1.1.26.9.2.3 · 1 row entry · 7 columns
A table of Rack PDU switched outlet status
information
rPDU2OutletSwitchedStatusEntry entry .1.3.6.1.4.1.318.1.1.26.9.2.3.1
Status information for currently queried
Rack PDU switched outlet
Indexes
rPDU2OutletSwitchedStatusIndex
Column Syntax OID
rPDU2OutletSwitchedStatusIndex mandatory
The index to the Rack PDU switched outlet
status information table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.3.1.1
rPDU2OutletSwitchedStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.3.1.2
rPDU2OutletSwitchedStatusName mandatory
The user-defined switched outlet ID string
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.2.3.1.3
rPDU2OutletSwitchedStatusNumber mandatory
The numeric switched outlet ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.3.1.4
rPDU2OutletSwitchedStatusState mandatory
Indicates the present switch state of the Rack
PDU switched outlet being queried
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.318.1.1.26.9.2.3.1.5
rPDU2OutletSwitchedStatusCommandPending mandatory
Indicates whether or not the device is
processing a command for this outlet.

If the commandPendingUnknown (3) value is
returned, all devices powered by the Rack PDU
should be shut down. The Rack PDU's po…
Enumeration
Enumerated Values:
1commandPending
2noCommandPending
3commandPendingUnknown
.1.3.6.1.4.1.318.1.1.26.9.2.3.1.6
rPDU2OutletSwitchedStatusExternalLink mandatory
Each RPDU outlet can have its own external web URL link.
This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID.
When this link is clicked in the web interface, the linked URL will
open in the web b…
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.2.3.1.7
.1.3.6.1.4.1.318.1.1.26.9.2.4 · 1 row entry · 5 columns
A table of Rack PDU switched outlet control
data
rPDU2OutletSwitchedControlEntry entry .1.3.6.1.4.1.318.1.1.26.9.2.4.1
Control data for currently queried Rack
PDU switched outlet
Indexes
rPDU2OutletSwitchedControlIndex
Column Syntax OID
rPDU2OutletSwitchedControlIndex mandatory
The index to the Rack PDU switched outlet
control data table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.4.1.1
rPDU2OutletSwitchedControlModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.4.1.2
rPDU2OutletSwitchedControlName mandatory
The user-defined switched outlet ID string
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.2.4.1.3
rPDU2OutletSwitchedControlNumber mandatory
The numeric switched outlet ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.2.4.1.4
rPDU2OutletSwitchedControlCommand mandatory
Getting this variable will return the outlet state. If
the outlet is on, the immediateOn (1) value will be returned.
If the outlet is off, the immediateOff (2) value will be
returned. If the state of the outlet cannot b…
Enumerationr/w
Enumerated Values:
1immediateOn
2immediateOff
3immediateReboot
4outletUnknown
5delayedOn
6delayedOff
7delayedReboot
8cancelPendingCommand
.1.3.6.1.4.1.318.1.1.26.9.2.4.1.5
.1.3.6.1.4.1.318.1.1.26.9.4.1 · 1 row entry · 8 columns
A table of Rack PDU metered outlet configuration data
rPDU2OutletMeteredConfigEntry entry .1.3.6.1.4.1.318.1.1.26.9.4.1.1
Configuration data from currently queried
Rack PDU metered outlet
Indexes
rPDU2OutletMeteredConfigIndex
Column Syntax OID
rPDU2OutletMeteredConfigIndex mandatory
The index to the Rack PDU metered outlet
configuration table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.1.1.1
rPDU2OutletMeteredConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.1.1.2
rPDU2OutletMeteredConfigName mandatory
The user-defined metered outlet ID string
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.4.1.1.3
rPDU2OutletMeteredConfigNumber mandatory
The numeric switched outlet ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.1.1.4
rPDU2OutletMeteredConfigLowLoadCurrentThreshold mandatory
User-defined low load outlet current threshold in Watts
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.1.1.5
rPDU2OutletMeteredConfigNearOverloadCurrentThreshold mandatory
User-defined near outlet overload warning threshold
in Watts
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.1.1.6
rPDU2OutletMeteredConfigOverloadCurrentThreshold mandatory
User-defined outlet overload current threshold in Watts
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.1.1.7
rPDU2OutletMeteredConfigExternalLink mandatory
User-defined external device web link.
Possible use cases could be the IP address of the external device
plugged into the outlet or its manufacturer web page for convenient
support such as user manuals, specifications…
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.4.1.1.8
.1.3.6.1.4.1.318.1.1.26.9.4.2 · 1 row entry · 7 columns
A table of Rack PDU metered outlet properties
rPDU2OutletMeteredPropertiesEntry entry .1.3.6.1.4.1.318.1.1.26.9.4.2.1
Properties of currently queried Rack PDU
metered outlet
Indexes
rPDU2OutletMeteredPropertiesIndex
Column Syntax OID
rPDU2OutletMeteredPropertiesIndex mandatory
The index to the Rack PDU metered properties table
entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.2.1.1
rPDU2OutletMeteredPropertiesModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.2.1.2
rPDU2OutletMeteredPropertiesName mandatory
The user-defined metered outlet ID string
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.4.2.1.3
rPDU2OutletMeteredPropertiesNumber mandatory
The numeric metered outlet ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.2.1.4
rPDU2OutletMeteredPropertiesLayout mandatory
This OID describes the phase connections of
the referenced outlet as follows:

seqPhase1ToNeutral(1) indicates that the outlet is
wired from Phase 1 to Neutral.

seqPhase2ToNeutral(2) indicat…
Rpdu2OutletPhaseLayoutType
Textual Convention: Rpdu2OutletPhaseLayoutType Enumeration
Type Values:
1seqPhase1ToNeutral
2seqPhase2ToNeutral
3seqPhase3ToNeutral
4seqPhase1ToPhase2
5seqPhase2ToPhase3
6seqPhase3ToPhase1
.1.3.6.1.4.1.318.1.1.26.9.4.2.1.5
rPDU2OutletMeteredPropertiesPowerRating mandatory
Maximum power rating of Rack PDU metered outlet
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.2.1.6
rPDU2OutletMeteredPropertiesBank mandatory
This outlet's numeric bank ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.2.1.7
.1.3.6.1.4.1.318.1.1.26.9.4.3 · 1 row entry · 13 columns
A table of Rack PDU metered outlet status data
rPDU2OutletMeteredStatusEntry entry .1.3.6.1.4.1.318.1.1.26.9.4.3.1
Status data from currently queried Rack PDU
metered outlet
Indexes
rPDU2OutletMeteredStatusIndex
Column Syntax OID
rPDU2OutletMeteredStatusIndex mandatory
The index to the Rack PDU metered status table
entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.1
rPDU2OutletMeteredStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.2
rPDU2OutletMeteredStatusName mandatory
The user-defined metered outlet ID string
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.3
rPDU2OutletMeteredStatusNumber mandatory
The numeric metered outlet ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.4
rPDU2OutletMeteredStatusState mandatory
Indicates the present load status of the Rack
PDU metered outlet being queried
Enumeration
Enumerated Values:
1lowLoad
2normal
3nearOverload
4overload
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.5
rPDU2OutletMeteredStatusCurrent mandatory
Indicates the current draw, in tenths
of Amps, of the load on the Rack PDU
outlet being queried
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.6
rPDU2OutletMeteredStatusPower mandatory
Indicates the power draw of the load
on the Rack PDU outlet being queried
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.7
rPDU2OutletMeteredStatusPeakPower mandatory
Indicates the peak power load draw
on the Rack PDU outlet being queried
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.8
rPDU2OutletMeteredStatusPeakPowerTimestamp mandatory
Indicates the date and time that this metered
outlet's peak power consumption occurred
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.9
rPDU2OutletMeteredStatusPeakPowerStartTime mandatory
Indicates the start date and time that this metered
outlet began recording peak power observations
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.10
rPDU2OutletMeteredStatusEnergy mandatory
A user resettable energy meter measuring Rack PDU load
energy consumption in tenths of kilowatt-hours
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.11
rPDU2OutletMeteredStatusReceptacleType mandatory
Indicates receptacle type for the outlet.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.12
rPDU2OutletMeteredStatusExternalLink mandatory
Each RPDU outlet can have its own external web URL link.
This can be configured in the rPDU2OutletMeteredConfigExternalLink OID.
When this link is clicked in the web interface, the linked URL will
open in the web br…
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.9.4.3.1.13
.1.3.6.1.4.1.318.1.1.26.10.2.1 · 1 row entry · 16 columns
A table of temperature-humidity sensor
configuration data
rPDU2SensorTempHumidityConfigEntry entry .1.3.6.1.4.1.318.1.1.26.10.2.1.1
Configuration data from temperature-humidity sensor
being queried
Indexes
rPDU2SensorTempHumidityConfigIndex
Column Syntax OID
rPDU2SensorTempHumidityConfigIndex mandatory
The index to the temperature-humidity sensor
configuration data table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.1
rPDU2SensorTempHumidityConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.2
rPDU2SensorTempHumidityConfigName mandatory
The user-defined temperature-humidity
sensor ID string
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.3
rPDU2SensorTempHumidityConfigNumber mandatory
The temperature-humidity sensor numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.4
rPDU2SensorTempHumidityConfigTemperatureAlarmEnable mandatory
Setting this OID enables or disables generation
of sensor temperature alarm.

Getting this OID returns the current value of
the temperature alarm enable.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.5
rPDU2SensorTempHumidityConfigHumidityAlarmEnable mandatory
Setting this OID enables or disables generation
of sensor humidity alarm.

Getting this OID returns the current value of
the humidity alarm enable.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.6
rPDU2SensorTempHumidityConfigTempMaxThreshF mandatory
Sensor maximum temperature alarm threshold in
Fahrenheit. Attempting to set this OID to a
value less than or equal to that of
rPDU2SensorTempHumidityConfigTempHighThreshF
will result in an error.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.7
rPDU2SensorTempHumidityConfigTempHighThreshF mandatory
Sensor high temperature warning alarm threshold
in Fahrenheit. Attempting to set this OID to a
value greater than or equal to that of
rPDU2SensorTempHumidityConfigTempMaxThreshF
will result in an error.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.8
rPDU2SensorTempHumidityConfigTempHysteresisF mandatory
Sensor temperature hysteresis setting in Fahrenheit
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.9
rPDU2SensorTempHumidityConfigTempMaxThreshC mandatory
Sensor maximum temperature alarm threshold
in Celsius. Attempting to set this OID to a
value less than or equal to that of
rPDU2SensorTempHumidityConfigTempHighThreshC
will result in an error.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.10
rPDU2SensorTempHumidityConfigTempHighThreshC mandatory
Sensor high temperature warning alarm threshold
in Celsius. Attempting to set this OID to a
value greater than or equal to that of
rPDU2SensorTempHumidityConfigTempMaxThreshC
will result in an error.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.11
rPDU2SensorTempHumidityConfigTempHysteresisC mandatory
Sensor temperature hysteresis setting in Celsius
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.12
rPDU2SensorTempHumidityConfigHumidityLowThresh mandatory
Sensor low humidity warning alarm threshold in
percent relative humidity.
May be 10% to 90%, but must be greater than
rPDU2SensorTempHumidityConfigHumidityMinThresh.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.13
rPDU2SensorTempHumidityConfigHumidityMinThresh mandatory
Sensor minimum humidity alarm threshold in
percent relative humidity.
May be 10% to 90%, but must be less than
rPDU2SensorTempHumidityConfigHumidityLowThresh.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.14
rPDU2SensorTempHumidityConfigHumidityHysteresis mandatory
Sensor humidity hysteresis setting in percent relative
humidity
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.15
rPDU2SensorTempHumidityConfigTempPeakReset mandatory
Setting this OID to reset (2) will cause the existing peak temperature
to be replaced by the present temperature reading.

Getting this OID will do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.318.1.1.26.10.2.1.1.16
.1.3.6.1.4.1.318.1.1.26.10.2.2 · 1 row entry · 15 columns
A table of temperature-humidity sensor status data
rPDU2SensorTempHumidityStatusEntry entry .1.3.6.1.4.1.318.1.1.26.10.2.2.1
Status information from temperature-humidity sensor
being queried
Indexes
rPDU2SensorTempHumidityStatusIndex
Column Syntax OID
rPDU2SensorTempHumidityStatusIndex mandatory
The index to the temperature-humidity
status data table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.1
rPDU2SensorTempHumidityStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.2
rPDU2SensorTempHumidityStatusName mandatory
The user-defined temperature-humidity
sensor ID string
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.3
rPDU2SensorTempHumidityStatusNumber mandatory
The temperature-humidity sensor numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.4
rPDU2SensorTempHumidityStatusType mandatory
The type of the sensor
Enumeration
Enumerated Values:
1temperatureOnly
2temperatureHumidity
3commsLost
4notInstalled
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.5
rPDU2SensorTempHumidityStatusCommStatus mandatory
The communications status of the sensor
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.6
rPDU2SensorTempHumidityStatusTempF mandatory
Sensor temperature reading in tenths of degrees Fahrenheit
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.7
rPDU2SensorTempHumidityStatusTempC mandatory
Sensor temperature reading in tenths of degrees Celsius
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.8
rPDU2SensorTempHumidityStatusTempStatus mandatory
This OID reports the current state of the temperature probe.

A notPresent (1) response indicates that no probe is attached.
A belowMin (2) response indicates that the probe is present and
its measured tem…
Enumeration
Enumerated Values:
1notPresent
2belowMin
3belowLow
4normal
5aboveHigh
6aboveMax
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.9
rPDU2SensorTempHumidityStatusRelativeHumidity mandatory
Sensor humidity reading in percent relative humidity
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.10
rPDU2SensorTempHumidityStatusHumidityStatus mandatory
This OID reports the current state of the humidity probe.

A notPresent (1) response indicates that no probe is attached.
A belowMin (2) response indicates that the probe is present and
its measured humidi…
Enumeration
Enumerated Values:
1notPresent
2belowMin
3belowLow
4normal
5aboveHigh
6aboveMax
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.11
rPDU2SensorTempHumidityStatusTempPeakF mandatory
Sensor peak temperature in tenths of degrees Fahrenheit
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.12
rPDU2SensorTempHumidityStatusTempPeakC mandatory
Sensor peak temperature in tenths of degrees Celsius
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.13
rPDU2SensorTempHumidityStatusTempPeakTimestamp mandatory
Indicates the date and time that the peak temperature occurred
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.14
rPDU2SensorTempHumidityStatusTempPeakStartTime mandatory
Indicates the date and time of the last temperature peak reset
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.10.2.2.1.15
.1.3.6.1.4.1.318.1.1.26.10.4.1 · 1 row entry · 6 columns
A table of discrete sensor configuration
data
rPDU2SensorDiscreteConfigEntry entry .1.3.6.1.4.1.318.1.1.26.10.4.1.1
Configuration data from discreste sensor
being queried
Indexes
rPDU2SensorDiscreteConfigIndex
Column Syntax OID
rPDU2SensorDiscreteConfigIndex mandatory
The index to the discrete sensor configuration
data table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.4.1.1.1
rPDU2SensorDiscreteConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.4.1.1.2
rPDU2SensorDiscreteConfigName mandatory
The user-defined discrete sensor ID string
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.10.4.1.1.3
rPDU2SensorDiscreteConfigNumber mandatory
The discrete sensor numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.4.1.1.4
rPDU2SensorDiscreteConfigNormalState mandatory
Indicates the normal state of the discrete input
contact
Enumerationr/w
Enumerated Values:
1normallyOpen
2normallyClosed
.1.3.6.1.4.1.318.1.1.26.10.4.1.1.5
rPDU2SensorDiscreteConfigAbnormalSeverity mandatory
Indicates the severity of alarm triggered by
abnormal discrete input contact state
Enumerationr/w
Enumerated Values:
1informational
2warning
3critical
.1.3.6.1.4.1.318.1.1.26.10.4.1.1.6
.1.3.6.1.4.1.318.1.1.26.10.4.2 · 1 row entry · 8 columns
A table of discrete sensor status data
rPDU2SensorDiscreteStatusEntry entry .1.3.6.1.4.1.318.1.1.26.10.4.2.1
Status information from discrete sensor
being queried
Indexes
rPDU2SensorDiscreteStatusIndex
Column Syntax OID
rPDU2SensorDiscreteStatusIndex mandatory
The index to the discrete sensor status data
table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.4.2.1.1
rPDU2SensorDiscreteStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.4.2.1.2
rPDU2SensorDiscreteStatusName mandatory
The user-defined discrete sensor ID string
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.10.4.2.1.3
rPDU2SensorDiscreteStatusNumber mandatory
The discrete sensor numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.4.2.1.4
rPDU2SensorDiscreteStatusType mandatory
The type of discrete sensor currently being queried
Enumeration
Enumerated Values:
1notConnected
2doorContactSensor
3smokeSensor
4motionDetector
5vibrationSensor
6dryContactSensor
7spotLeakSensor
.1.3.6.1.4.1.318.1.1.26.10.4.2.1.5
rPDU2SensorDiscreteStatusCommStatus mandatory
The communications status of the sensor
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.26.10.4.2.1.6
rPDU2SensorDiscreteStatusCurrentState mandatory
The current open/close state of the discrete
sensor
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.26.10.4.2.1.7
rPDU2SensorDiscreteStatusAlarmState mandatory
Indicates alarm status of discrete sensor input
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.318.1.1.26.10.4.2.1.8
.1.3.6.1.4.1.318.1.1.26.10.6.1 · 1 row entry · 7 columns
A table of voltage sensor status data. Not supported
by rPDU series 9000 or older.
rPDU2SensorAnalogVoltageStatusEntry entry .1.3.6.1.4.1.318.1.1.26.10.6.1.1
Status information from voltage sensor
being queried
Indexes
rPDU2SensorAnalogVoltageStatusIndex
Column Syntax OID
rPDU2SensorAnalogVoltageStatusIndex mandatory
The index to the voltage sensor status data
table entry
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.1
rPDU2SensorAnalogVoltageStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.2
rPDU2SensorAnalogVoltageStatusNumber mandatory
The voltage sensor numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.3
rPDU2SensorAnalogVoltageStatusName mandatory
The user-defined voltage sensor ID string
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.4
rPDU2SensorAnalogVoltageStatusCommStatus mandatory
The communications status of the sensor
Enumeration
Enumerated Values:
1notInstalled
2commsOK
3commsLost
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.5
rPDU2SensorAnalogVoltageStatusHundredthVolts mandatory
Sensor voltage reading in hundredths of volts.
Returns -1 for indices without voltage probes.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.6
rPDU2SensorAnalogVoltageStatusThreshStatus mandatory
This OID reports the current state of the voltage probe:

A notPresent (1) response indicates that no probe is attached,
or that the attached probe isn't a voltage probe.
A belowMin (2) response indicates …
Enumeration
Enumerated Values:
1notPresent
2belowMin
3belowLow
4normal
5aboveHigh
6aboveMax
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.7
.1.3.6.1.4.1.318.1.1.26.10.6.2 · 1 row entry · 8 columns
A table of analog voltage sensor configuration data.
Not supported by rPDU series 9000 or older.
rPDU2SensorAnalogVoltageConfigEntry entry .1.3.6.1.4.1.318.1.1.26.10.6.2.1
Configuration data from analog voltage sensor
being queried
Indexes
rPDU2SensorAnalogVoltageConfigIndex
Column Syntax OID
rPDU2SensorAnalogVoltageConfigIndex mandatory
The index to the voltage sensor configuration
data table entry
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.26.10.6.2.1.1
rPDU2SensorAnalogVoltageConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.6.2.1.2
rPDU2SensorAnalogVoltageConfigNumber mandatory
The voltage sensor numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.6.2.1.3
rPDU2SensorAnalogVoltageConfigName mandatory
The user-defined voltage sensor ID string.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.26.10.6.2.1.4
rPDU2SensorAnalogVoltageConfigThreshMin mandatory
Sensor minimum voltage alarm threshold in hundredths of volts.
This value may be as low as zero and must be less than
rPDU2SensorAnalogVoltageConfigThreshMax. Returns -1 for indices
without voltage probes.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.6.2.1.5
rPDU2SensorAnalogVoltageConfigThreshMax mandatory
Sensor minimum voltage alarm threshold in hundredths of volts.
This value must be greater than rPDU2SensorAnalogVoltageConfigThreshMin
and may be as high as 50. Returns -1 for indices without voltage probes.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.6.2.1.6
rPDU2SensorAnalogVoltageConfigHysteresis mandatory
Sensor voltage hysteresis in hundredths of volts. This value may be
0 to 20. If either of the alarm thresholds are crossed, the measured
voltage must recover by this amount before the alarm will be cleared.
Returns -1 f…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.10.6.2.1.7
rPDU2SensorAnalogVoltageConfigAlarmEnable mandatory
This OID may be used to enable or disable voltage alarm generation.
Disabling alarm generation while alarms are active clears the
active alarms. Returns -1 for indices without voltage probes.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.26.10.6.2.1.8
.1.3.6.1.4.1.318.1.1.26.13.1 · 1 row entry · 5 columns
A table of Rack PDU phase to phase status data.
This table is only applicable to SKUs that have
phase to phase outputs.
rPDU2PhaseToPhaseStatusEntry entry .1.3.6.1.4.1.318.1.1.26.13.1.1
Status data from currently queried Rack PDU
phase to phase outputs
Indexes
rPDU2PhaseToPhaseStatusIndex
Column Syntax OID
rPDU2PhaseToPhaseStatusIndex mandatory
The index to the Rack PDU phase to phase status table
entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.13.1.1.1
rPDU2PhaseToPhaseStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.13.1.1.2
rPDU2PhaseToPhaseStatusVoltage1to2 mandatory
Indicates the Voltage, in Volts, of the Rack
PDU phase 1 to phase 2 output being queried
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.13.1.1.3
rPDU2PhaseToPhaseStatusVoltage2to3 mandatory
Indicates the Voltage, in Volts, of the Rack
PDU phase 2 to phase 3 output being queried
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.13.1.1.4
rPDU2PhaseToPhaseStatusVoltage3to1 mandatory
Indicates the Voltage, in Volts, of the Rack
PDU phase 3 to phase 2 output being queried
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.13.1.1.5
.1.3.6.1.4.1.318.1.1.26.14.1 · 1 row entry · 8 columns
A table of Rack PDU bank configuration data
rPDU2AdvBankConfigEntry entry .1.3.6.1.4.1.318.1.1.26.14.1.1
Configuration data from currently queried
Rack PDU bank
Indexes
rPDU2AdvBankConfigIndex
Column Syntax OID
rPDU2AdvBankConfigIndex mandatory
The index to the Rack PDU bank configuration
table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.14.1.1.1
rPDU2AdvBankConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.14.1.1.2
rPDU2AdvBankConfigNumber mandatory
The numeric bank ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.14.1.1.3
rPDU2AdvBankConfigOverloadRestriction mandatory
This OID controls the behavior of a Switched Rack PDU
bank when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will alway…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
4notSupported
.1.3.6.1.4.1.318.1.1.26.14.1.1.4
rPDU2AdvBankConfigLowLoadCurrentThreshold mandatory
User-defined low load bank current
threshold in tenths of Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.14.1.1.5
rPDU2AdvBankConfigNearOverloadCurrentThreshold mandatory
User-defined near bank overload current warning
threshold in tenths of Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.14.1.1.6
rPDU2AdvBankConfigOverloadCurrentThreshold mandatory
User-defined bank overload current threshold
in tenths of Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.14.1.1.7
rPDU2AdvBankConfigBankPeakCurrentReset mandatory
Setting this OID to reset (2) will cause the existing peak current value
to be replaced by the present load current value.

Getting this OID will do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.318.1.1.26.14.1.1.8
.1.3.6.1.4.1.318.1.1.26.15.1 · 1 row entry · 8 columns
A table of Rack PDU phase configuration data
rPDU2AdvPhaseConfigEntry entry .1.3.6.1.4.1.318.1.1.26.15.1.1
Configuration data from currently queried Rack
PDU phase
Indexes
rPDU2AdvPhaseConfigIndex
Column Syntax OID
rPDU2AdvPhaseConfigIndex mandatory
The index to the Rack PDU phase configuration
table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.15.1.1.1
rPDU2AdvPhaseConfigModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.15.1.1.2
rPDU2AdvPhaseConfigNumber mandatory
The numeric phase ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.15.1.1.3
rPDU2AdvPhaseConfigOverloadRestriction mandatory
This OID controls the behavior of a Switched Rack PDU
phase when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will alwa…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
4notSupported
.1.3.6.1.4.1.318.1.1.26.15.1.1.4
rPDU2AdvPhaseConfigLowLoadCurrentThreshold mandatory
User-defined low load phase current
threshold measured in tenths of Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.15.1.1.5
rPDU2AdvPhaseConfigNearOverloadCurrentThreshold mandatory
User-defined near phase overload warning
threshold measured in tenths of Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.15.1.1.6
rPDU2AdvPhaseConfigOverloadCurrentThreshold mandatory
User-defined phase overload current
threshold measured in tenths of Amps
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.26.15.1.1.7
rPDU2AdvPhaseConfigPhasePeakCurrentReset mandatory
Setting this OID to reset (2) will cause the existing peak current value
to be replaced by the present load current value.

Getting this OID will do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.318.1.1.26.15.1.1.8

coolingUnitTable

table mandatory
.1.3.6.1.4.1.318.1.1.27.1.2 · 1 row entry · 1 columns
A table of cooling unit level data.
coolingUnitEntry entry .1.3.6.1.4.1.318.1.1.27.1.2.1
An element of coolingUnitTable.
Indexes
coolingUnitTableIndex
Column Syntax OID
coolingUnitTableIndex mandatory
The unit reference identifier for this table and all other table entries subordinate to coolingUnits.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.2.1.1

coolingUnitAboutTable

table mandatory
.1.3.6.1.4.1.318.1.1.27.1.3.2 · 1 row entry · 3 columns
A table of unit reference information.
coolingUnitAboutEntry entry .1.3.6.1.4.1.318.1.1.27.1.3.2.1
An element of coolingUnitAboutTable.
Indexes
coolingUnitTableIndex coolingUnitAboutTableIndex
Column Syntax OID
coolingUnitAboutTableIndex mandatory
The static reference identifier for each table entry.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.3.2.1.1
coolingUnitAboutDescription mandatory
A text description of the information presented in coolingUnitAboutValue.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.3.2.1.2
coolingUnitAboutValue mandatory
The actual value of the current table entry.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.3.2.1.3
.1.3.6.1.4.1.318.1.1.27.1.4.1.2 · 1 row entry · 5 columns
A table of analog unit status data.
coolingUnitStatusAnalogEntry entry .1.3.6.1.4.1.318.1.1.27.1.4.1.2.1
An element of coolingUnitStatusAnalogTable.
Indexes
coolingUnitTableIndex coolingUnitStatusAnalogTableIndex
Column Syntax OID
coolingUnitStatusAnalogTableIndex mandatory
The static reference identifier for each table entry.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.1
coolingUnitStatusAnalogDescription mandatory
A text description of the information presented in coolingUnitStatusAnalogValue.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.2
coolingUnitStatusAnalogValue mandatory
The scaled value of the current table entry (multiplied by coolingUnitStatusAnalogScale for integer presentation).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3
coolingUnitStatusAnalogUnits mandatory
The unit of measure by which coolingUnitStatusAnalogValue is expressed.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.4
coolingUnitStatusAnalogScale mandatory
The factor by which coolingUnitStatusAnalogValue is expressed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.5
.1.3.6.1.4.1.318.1.1.27.1.4.2.2 · 1 row entry · 5 columns
A table of discrete unit status data.
coolingUnitStatusDiscreteEntry entry .1.3.6.1.4.1.318.1.1.27.1.4.2.2.1
An element of coolingUnitStatusDiscreteTable.
Indexes
coolingUnitTableIndex coolingUnitStatusDiscreteTableIndex
Column Syntax OID
coolingUnitStatusDiscreteTableIndex mandatory
The static reference identifier for each table entry.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.1
coolingUnitStatusDiscreteDescription mandatory
A text description of the information presented in this table's 'value' OIDs.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.2
coolingUnitStatusDiscreteValueAsString mandatory
The actual value of the current table entry expressed as a string.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.3
coolingUnitStatusDiscreteValueAsInteger mandatory
The actual value of the current table entry expressed as an integer value.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.4
coolingUnitStatusDiscreteIntegerReferenceKey mandatory
A complete listing of all possible coolingUnitStatusDiscreteValueAsInteger values paired with their identifying strings.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.5
.1.3.6.1.4.1.318.1.1.27.1.5.1.2 · 1 row entry · 8 columns
A table of analog unit configuration data.
coolingUnitConfigurationAnalogEntry entry .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1
An element of coolingUnitConfigurationAnalogTable.
Indexes
coolingUnitTableIndex coolingUnitConfigurationAnalogTableIndex
Column Syntax OID
coolingUnitConfigurationAnalogTableIndex mandatory
The static reference identifier for each table entry.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.1
coolingUnitConfigurationAnalogDescription mandatory
A text description of the information presented in coolingUnitConfigurationAnalogValue.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.2
coolingUnitConfigurationAnalogValue mandatory
The scaled value of the current table entry (multiplied by coolingUnitConfigurationAnalogScale for integer presentation).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3
coolingUnitConfigurationAnalogUnits mandatory
The unit of measure by which coolingUnitConfigurationAnalogValue is expressed.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.4
coolingUnitConfigurationAnalogScale mandatory
The factor by which coolingUnitConfigurationAnalogValue is expressed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.5
coolingUnitConfigurationAnalogAccess mandatory
A description of available access to coolingUnitConfigurationAnalogValue via SNMP client.
Enumeration
Enumerated Values:
1readOnly
2readWrite
.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.6
coolingUnitConfigurationAnalogMinimum mandatory
The minimum possible value of coolingUnitConfigurationAnalogValue.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.7
coolingUnitConfigurationAnalogMaximum mandatory
The maximum possible value of coolingUnitConfigurationAnalogValue.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.8
.1.3.6.1.4.1.318.1.1.27.1.5.2.2 · 1 row entry · 6 columns
A table of discrete unit configuration data.
coolingUnitConfigurationDiscreteEntry entry .1.3.6.1.4.1.318.1.1.27.1.5.2.2.1
An element of coolingUnitConfigurationDiscreteTable.
Indexes
coolingUnitTableIndex coolingUnitConfigurationDiscreteTableIndex
Column Syntax OID
coolingUnitConfigurationDiscreteTableIndex mandatory
The static reference identifier for each table entry.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.1
coolingUnitConfigurationDiscreteDescription mandatory
A text description of the information presented in this table's 'value' OIDs.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.2
coolingUnitConfigurationDiscreteValueAsString mandatory
The actual value of the current table entry expressed as a string.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.3
coolingUnitConfigurationDiscreteValueAsInteger mandatory
The actual value of the current table entry expressed as an integer value.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.4
coolingUnitConfigurationDiscreteIntegerReferenceKey mandatory
A complete listing of all possible coolingUnitConfigurationDiscreteValueAsInteger values paired with their identifying strings.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.5
coolingUnitConfigurationDiscreteAccess mandatory
A description of available access to coolingUnitConfigurationDiscreteValueAsInteger via SNMP client.
Enumeration
Enumerated Values:
1readOnly
2readWrite
.1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.6
.1.3.6.1.4.1.318.1.1.27.1.5.3.2 · 1 row entry · 5 columns
A table of unit configuration strings.
coolingUnitConfigurationStringEntry entry .1.3.6.1.4.1.318.1.1.27.1.5.3.2.1
An element of coolingUnitConfigurationStringTable.
Indexes
coolingUnitTableIndex coolingUnitConfigurationStringTableIndex
Column Syntax OID
coolingUnitConfigurationStringTableIndex mandatory
The static reference identifier for each table entry.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.1
coolingUnitConfigurationStringDescription mandatory
A text description of the information presented in coolingUnitConfigurationStringValue.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.2
coolingUnitConfigurationStringValue mandatory
The actual value of the current table entry.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.3
coolingUnitConfigurationStringMaxLength mandatory
The maximum string length supported by coolingUnitConfigurationStringValue.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.4
coolingUnitConfigurationStringAccess mandatory
A description of available access to coolingUnitConfigurationStringValue via SNMP client.
Enumeration
Enumerated Values:
1readOnly
2readWrite
.1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.5
.1.3.6.1.4.1.318.1.1.27.1.6.1.2 · 1 row entry · 5 columns
A table of secondary analog data for the cooling unit or one of its components.
coolingUnitExtendedAnalogEntry entry .1.3.6.1.4.1.318.1.1.27.1.6.1.2.1
An element of coolingUnitExtendedAnalogTable.
Indexes
coolingUnitTableIndex coolingUnitExtendedAnalogTableIndex
Column Syntax OID
coolingUnitExtendedAnalogTableIndex mandatory
The static reference identifier for each table entry. This identifier may reference different table entries in different unit models.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.1
coolingUnitExtendedAnalogDescription mandatory
A text description of the information presented in coolingUnitExtendedAnalogValue.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.2
coolingUnitExtendedAnalogValue mandatory
The scaled value of the current table entry (multiplied by coolingUnitExtendedAnalogScale for integer presentation).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.3
coolingUnitExtendedAnalogUnits mandatory
The unit of measure by which coolingUnitExtendedAnalogValue is expressed.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.4
coolingUnitExtendedAnalogScale mandatory
The factor by which coolingUnitExtendedAnalogValue is expressed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.5
.1.3.6.1.4.1.318.1.1.27.1.6.2.2 · 1 row entry · 5 columns
A table of secondary discrete cooling unit data.
coolingUnitExtendedDiscreteEntry entry .1.3.6.1.4.1.318.1.1.27.1.6.2.2.1
An element of coolingUnitExtendedDiscreteTable.
Indexes
coolingUnitTableIndex coolingUnitExtendedDiscreteTableIndex
Column Syntax OID
coolingUnitExtendedDiscreteTableIndex mandatory
The static reference identifier for each table entry. This identifier may reference different table entries in different unit models.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.1
coolingUnitExtendedDiscreteDescription mandatory
A text description of the information presented in this table's 'value' OIDs.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.2
coolingUnitExtendedDiscreteValueAsString mandatory
The actual value of the current table entry expressed as a string.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.3
coolingUnitExtendedDiscreteValueAsInteger mandatory
The actual value of the current table entry expressed as an integer value.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.4
coolingUnitExtendedDiscreteIntegerReferenceKey mandatory
A complete listing of all possible coolingUnitExtendedDiscreteValueAsInteger values paired with their identifying strings.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.5
.1.3.6.1.4.1.318.1.1.27.1.6.3.2 · 1 row entry · 3 columns
A table of secondary unit reference data.
coolingUnitExtendedStringEntry entry .1.3.6.1.4.1.318.1.1.27.1.6.3.2.1
An element of coolingUnitExtendedStringTable.
Indexes
coolingUnitTableIndex coolingUnitExtendedStringTableIndex
Column Syntax OID
coolingUnitExtendedStringTableIndex mandatory
The static reference identifier for each table entry. This identifier may reference different table entries in different unit models.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.1
coolingUnitExtendedStringDescription mandatory
A text description of the information presented in coolingUnitExtendedStringValue.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.2
coolingUnitExtendedStringValue mandatory
The actual value of the current table entry.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.3

pmmInputTable

table mandatory
.1.3.6.1.4.1.318.1.1.28.3.1.2 · 1 row entry · 56 columns
A list of input meter entries.
pmmInputEntry entry .1.3.6.1.4.1.318.1.1.28.3.1.2.1
An entry containing information applicable to a
particular input meter.
Indexes
pmmInputMeterIndex
Column Syntax OID
pmmInputMeterIndex mandatory
The input meter identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.1
pmmInputFrequency mandatory
The input frequency in tenths of Hertz.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.2
pmmInputTotalActivePower mandatory
Shows the total input active power in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.3
pmmInputTotalApparentPower mandatory
Shows the total input apparent power in tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.4
pmmInputTotalPowerFactor mandatory
Indicates the total power factor. A value of 100 representing
a unity power factor (1.00). Specified in hundredths.
Returns -255 if unsupported
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.5
pmmInputActiveEnergyDelivered mandatory
Shows the input active energy delivered in tenths of kWh.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.6
pmmInputActiveEnergyReceived mandatory
Shows the input active energy received in tenths of kWh.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.7
pmmInputApparentEnergyDelivered mandatory
Shows the input apparent energy delivered in tenths of kVAh.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.8
pmmInputApparentEnergyReceived mandatory
Shows the input apparent energy received in tenths of kVAh.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.9
pmmInputFrequencyDeviation mandatory
Displays the input frequency deviation in Hertz.
Threshold write returns as unsuccessful if one of the breaker threshold
groups does not meet conditions. In this case, read the thresholds
to know which threshold group…
Enumerationr/w
Enumerated Values:
1freqDeviationOff
2freqDeviationPointTwo
3freqDeviationPointFive
4freqDeviationOne
5freqDeviationOnePointFive
6freqDeviationTwo
7freqDeviationThree
8freqDeviationFour
9freqDeviationFive
10freqDeviationNine
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.10
pmmInputPowerFactorDeviation mandatory
Displays the input power factor deviation. Specified in tenths.
A value of zero indicates that the threshold is disabled.
Returns -1 if unsupported.
Threshold write returns as unsuccessful if one of the breaker threshol…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.11
pmmInputMinVoltThreshold mandatory
Threshold below which an input minimum voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalInputVoltage.
A value of zero indicates that the thr…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.12
pmmInputLowVoltThreshold mandatory
Threshold below which an input low voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalInputVoltage.
A value of zero indicates that the thresho…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.13
pmmInputHighVoltThreshold mandatory
Threshold above which an input high voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalInputVoltage.
A value of zero indicates that the thresh…
Integer32r/w
Constraints:
range: 0-120
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.14
pmmInputMaxVoltThreshold mandatory
Threshold above which an input maximum voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalInputVoltage.
A value of zero indicates that the thr…
Integer32r/w
Constraints:
range: 0-120
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.15
pmmInputMinCurrentThreshold mandatory
Threshold below which an input minimum current condition will be generated.
Specified as a percent of the panel breaker rating.
A value of zero indicates that the threshold is disabled.
Threshold write returns as unsucc…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.16
pmmInputLowCurrentThreshold mandatory
Threshold below which an input low current condition will be generated.
Specified as a percent of the panel breaker rating.
A value of zero indicates that the threshold is disabled.
Threshold write returns as unsuccessf…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.17
pmmInputHighCurrentThreshold mandatory
Threshold above which an input high current condition will be generated.
Specified as a percent of the panel breaker rating.
A value of zero indicates that the threshold is disabled.
Threshold write returns as unsuccess…
Integer32r/w
Constraints:
range: 0-110
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.18
pmmInputMaxCurrentThreshold mandatory
Threshold above which an input maximum current condition will be generated.
Specified as a percent of the panel breaker rating.
A value of zero indicates that the threshold is disabled.
Threshold write returns as unsucc…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.19
pmmInputMinApparentPowerThreshold mandatory
Threshold below which an input minimum apparent power condition will be generated.
Specified as a percent deviation from nominal power rating.
A value of zero indicates that the threshold is disabled.
Threshold write re…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.20
pmmInputMaxApparentPowerThreshold mandatory
Threshold above which an input maximum apparent power condition will be generated.
Specified as a percent deviation from nominal power rating.
A value of zero indicates that the threshold is disabled.
Threshold write re…
Integer32r/w
Constraints:
range: 0-110
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.21
pmmInputOverActivePowerThreshold mandatory
Threshold above which an input over active power condition will be generated.
Specified as a percent deviation from nominal power rating.
A value of zero indicates that the threshold is disabled.
Threshold write returns…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.22
pmmInputBreakerState mandatory
This value indicates the current state of input breaker.
1 will indicate open,
2 will indicate closed,
3 will indicate unknown.
Returns -1 if unsupported or failed.
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.23
pmmInputBreakerOpenAlarm mandatory
Breaker open alarm status.
1 will indicate enabled,
2 will indicate disabled,
3 will indicate unknown.
Enumerationr/w
Enumerated Values:
1enabled
2disabled
3unknown
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.24
pmmInputAverageCurrent mandatory
Input Average current. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.25
pmmInputNeturalCurrent mandatory
Input Neutral current. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.26
pmmInputMaxInstantaneousNeutralCurrent mandatory
Input maximum instantaneous neutral current. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.27
pmmInputAverageCurrentTHD mandatory
Input average harmonic distortions.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.28
pmmInputAverageVoltageLtoL mandatory
Input Average Line to Line voltage. Measured in tenths of Volts.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.29
pmmInputAverageVoltageLtoN mandatory
Input Average Line to Neutral voltage. Measured in tenths of Volts.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.30
pmmInputLoad mandatory
Total load of input breaker in percentage. Measured in tenths of percent.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.31
pmmInputMeterFirmwareVersion mandatory
Shows the input meter firmware version.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.32
pmmInputMeterSerialNumber mandatory
Shows the input meter serial number.
Returns -1 if unsupported or failed.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.33
pmmInputEnergyUsageAccumulatedTotal mandatory
Shows the total accumulated input energy usage in kWh.
Measured in tenths of kWh.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.34
pmmInputPhaseLoss mandatory
Threshold below which an input phase loss condition will be generated.
Specified as a percent deviation from phase to neutral nominal voltage.
A value of zero indicates that the threshold is disabled.
Returns -1 if unsu…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.35
pmmInputBreakerCTSize mandatory
Shows the input breaker CT size.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.36
pmmInputBreakerRating mandatory
Shows the input breaker rating in Amps(A).
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.37
pmmInputKWHResetDate mandatory
The date that the kWh usage was reset, in the format mm/dd/yyyy.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.38
pmmInputAlarmGeneration mandatory
Alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.39
pmmInputVoltageMaximumAlarm mandatory
Voltage maximum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.40
pmmInputVoltageHighAlarm mandatory
Voltage high alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.41
pmmInputVoltageLowAlarm mandatory
Voltage low alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.42
pmmInputVoltageMinimumAlarm mandatory
Voltage minimum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.43
pmmInputCurrentMaximumAlarm mandatory
Current maximum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.44
pmmInputCurrentHighAlarm mandatory
Current high alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.45
pmmInputCurrentLowAlarm mandatory
Current low alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.46
pmmInputCurrentMinimumAlarm mandatory
Current minimum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.47
pmmInputApparentPowerMaximumAlarm mandatory
Apparent Power maximum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.48
pmmInputApparentPowerMinimumAlarm mandatory
Apparent Power minimum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.49
pmmInputKWOverAlarm mandatory
Over active power alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.50
pmmInputPhaseLossAlarm mandatory
Phase loss alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.51
pmmInputPowerFactorTotalAlarm mandatory
Total power factor alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.52
pmmInputFrequencyDeviationAlarm mandatory
Frequency deviation alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.53
pmmInputNeutralOverCurrentAlarm mandatory
Neutral Overcurrent alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.54
pmmInputNeutralOverCurrentThreshold mandatory
Threshold above which an input neutral overcurrent condition will be generated.
Specified as a percent deviation from nominal current.
A value of zero indicates that the threshold is disabled.
Returns -1 if unsupported …
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.55
pmmInputAveragePowerFactor mandatory
Indicates the average power factor. A value of 100 representing
a unity power factor (1.00). Specified in hundredths.
Returns -255 if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.2.1.56

pmmInputPhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.28.3.1.3 · 1 row entry · 13 columns
A list of input table entries.
The number of entries is given by the value of
pmmInputMeterTableSize OID.
pmmInputPhaseEntry entry .1.3.6.1.4.1.318.1.1.28.3.1.3.1
An entry containing information applicable to a
particular input phase.
Indexes
pmmInputMeterNum pmmInputPhase
Column Syntax OID
pmmInputMeterNum mandatory
The input meter identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.1
pmmInputPhase mandatory
Input phase index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.2
pmmInputVoltageLtoL mandatory
Line-to-line input voltage available.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.3
pmmInputVoltageLtoN mandatory
Line-to-neutral input voltage available.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.4
pmmInputPhaseCurrent mandatory
Input current per phase. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.5
pmmInputActivePower mandatory
Input active power per phase. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.6
pmmInputApparentPower mandatory
Input apparent power per phase. Measured in tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.7
pmmInputPowerFactor mandatory
Indicates the power factor of the input per phase.
A value of 100 representing a unity power factor (1.00).
Specified in hundredths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.8
pmmInputMaxInstantaneousCurrent mandatory
Input maximum phase instantaneous current. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.9
pmmInputPhaseAngle mandatory
Current phase Angle. Measured in tenths of decimal
Returns -255 if unsupported
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.10
pmmInputTHDLtoL mandatory
Input harmonic distortions line to line for the present input voltage.
Measured in tenths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.11
pmmInputTHDLtoN mandatory
Input harmonic distortions line to neutral for the present input voltage.
Measured in tenths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.12
pmmInputCurrentTHD mandatory
Input harmonic distortions for each phase, for the present input current.
Returns -1 if unsupported or failed.
Specified in tenths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.1.3.1.13

pmmOutputTable

table mandatory
.1.3.6.1.4.1.318.1.1.28.3.2.2 · 1 row entry · 25 columns
A list of output meter entries.
pmmOutputEntry entry .1.3.6.1.4.1.318.1.1.28.3.2.2.1
An entry containing information applicable to a
particular output meter.
Indexes
pmmOutputMeterIndex
Column Syntax OID
pmmOutputMeterIndex mandatory
The output meter identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.1
pmmOutputFrequency mandatory
The output frequency in tenths of Hertz.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.2
pmmOutputTotalActivePower mandatory
Shows the total output active power in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.3
pmmOutputTotalApparentPower mandatory
Shows the total output apparent power in tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.4
pmmOutputTotalPowerFactor mandatory
Indicates the total power factor. A value of 100 representing
a unity power factor (1.00). Specified in hundredths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.5
pmmOutputActiveEnergyDelivered mandatory
Shows the output active energy delivered in tenths of kWh.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.6
pmmOutputActiveEnergyReceived mandatory
Shows the output active energy received in tenths of kWh.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.7
pmmOutputApparentEnergyDelivered mandatory
Shows the output apparent energy delivered in tenths of kVAh.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.8
pmmOutputApparentEnergyReceived mandatory
Shows the output apparent energy received in tenths of kVAh.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.9
pmmOutputFrequencyDeviation mandatory
Shows the output frequency deviation in Hertz.
Enumerationr/w
Enumerated Values:
1freqDeviationOff
2freqDeviationPointTwo
3freqDeviationPointFive
4freqDeviationOne
5freqDeviationOnePointFive
6freqDeviationTwo
7freqDeviationThree
8freqDeviationFour
9freqDeviationFive
10freqDeviationNine
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.10
pmmOutputPowerFactorDeviation mandatory
Shows the output power factor deviation. Specified in tenths.
A value of zero indicates that the threshold is disabled.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.11
pmmOutputMinVoltThreshold mandatory
Threshold below which an output minimum voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
A value of zero indicates that the t…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.12
pmmOutputLowVoltThreshold mandatory
Threshold below which an output low voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
A value of zero indicates that the thres…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.13
pmmOutputHighVoltThreshold mandatory
Threshold above which an output high voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
A value of zero indicates that the thre…
Integer32r/w
Constraints:
range: 0-120
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.14
pmmOutputMaxVoltThreshold mandatory
Threshold above which an output maximum voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
A value of zero indicates that the t…
Integer32r/w
Constraints:
range: 0-120
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.15
pmmOutputMinCurrentThreshold mandatory
Threshold below which an output minimum current condition will be generated.
Specified as a percent of the panel breaker rating.
A value of zero indicates that the threshold is disabled.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.16
pmmOutputLowCurrentThreshold mandatory
Threshold below which an output low current condition will be generated.
Specified as a percent of the panel breaker rating.
A value of zero indicates that the threshold is disabled.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.17
pmmOutputHighCurrentThreshold mandatory
Threshold above which an output high current condition will be generated.
Specified as a percent of the panel breaker rating.
A value of zero indicates that the threshold is disabled.
Integer32r/w
Constraints:
range: 0-110
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.18
pmmOutputMaxCurrentThreshold mandatory
Threshold above which an output maximum current condition will be generated.
Specified as a percent of the panel breaker rating.
A value of zero indicates that the threshold is disabled.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.19
pmmOutputMinApparentPowerThreshold mandatory
Threshold below which an output minimum apparent power condition will be generated.
Specified as a percent deviation from nominal power rating.
A value of zero indicates that the threshold is disabled.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.20
pmmOutputMaxApparentPowerThreshold mandatory
Threshold above which an output maximum apparent power condition will be generated.
Specified as a percent deviation from nominal power rating.
A value of zero indicates that the threshold is disabled.
Integer32r/w
Constraints:
range: 0-110
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.21
pmmOutputOverActivePowerThreshold mandatory
Threshold above which an output over active power condition will be generated.
Specified as a percent deviation from nominal power rating.
A value of zero indicates that the threshold is disabled.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.22
pmmOutputPhaseLossThreshold mandatory
Threshold below which an output phase loss condition will be generated.
Specified as a percent deviation from nominal voltage represented
in the OID pmmDeviceNominalOutputVoltage.
A value of zero indicates that the thre…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.23
pmmOutputBreakerState mandatory
This value indicates the current state of output breaker.
1 will indicate open,
2 will indicate closed,
3 will indicate unknown.
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.24
pmmOutputBreakerOpenAlarm mandatory
Breaker open alarm status.
1 will indicate enabled,
2 will indicate disabled,
3 will indicate unknown.
Enumerationr/w
Enumerated Values:
1enabled
2disabled
3unknown
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.25

pmmOutputPhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.28.3.2.3 · 1 row entry · 8 columns
A list of output table entries.
The number of entries is given by the value of
pmmOutputMeterTableSize OID.
pmmOutputPhaseEntry entry .1.3.6.1.4.1.318.1.1.28.3.2.3.1
An entry containing information applicable to a
particular output phase.
Indexes
pmmOutputMeterNum pmmOutputPhase
Column Syntax OID
pmmOutputMeterNum mandatory
The output meter identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.3.1.1
pmmOutputPhase mandatory
Output phase index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.3.1.2
pmmOutputVoltageLtoL mandatory
Line-to-line output voltage available.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.3.1.3
pmmOutputVoltageLtoN mandatory
Line-to-neutral output voltage available.
Measured in tenths of Volts.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.3.1.4
pmmOutputPhaseCurrent mandatory
Load current per phase. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.3.1.5
pmmOutputActivePower mandatory
Output power per phase. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.3.1.6
pmmOutputApparentPower mandatory
Output power per phase. Measured in tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.3.1.7
pmmOutputPowerFactor mandatory
Indicates the power factor of the output per phase.
A value of 100 representing a unity power factor (1.00).
Specified in hundredths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.2.3.1.8

pmmBranchBreakerTable

table mandatory
.1.3.6.1.4.1.318.1.1.28.3.3.3 · 1 row entry · 41 columns
A list of branch breaker table entries.
The number of entries is contained in the pmmBranchBreakerTableSize OID.
pmmBranchBreakerEntry entry .1.3.6.1.4.1.318.1.1.28.3.3.3.1
An entry containing information applicable to a
particular branch breaker (panel/circuit position).
Indexes
pmmBranchCircuitMeterIndex pmmBranchCircuitIndex
Column Syntax OID
pmmBranchCircuitMeterIndex mandatory
Index of branch circuit meter in the table.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.1
pmmBranchCircuitIndex mandatory
The branch circuit index.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.2
pmmBranchCircuitNumberOfPoles mandatory
The number of poles.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.3
pmmBranchCircuitPhase mandatory
The phase associated with branch circuit.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.4
pmmBranchCircuitBreakerIdentifier mandatory
The branch circuit identifier.
Returns (-1) if not supported.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.5
pmmBranchCircuitLoadIdentifier mandatory
Identifies the name or location of the branch circuit load.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.6
pmmBranchCircuitCurrent mandatory
The branch circuit current Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.7
pmmBranchCircuitBreakerRating mandatory
The rating of the branch circuit breaker in Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.8
pmmBranchCircuitTotalActivePower mandatory
Branch circuit total active power. Measured in tenths
of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.9
pmmBranchCircuitTotalApparentPower mandatory
Branch circuit total apparent power. Measured in
tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.10
pmmBranchCircuitEnergyUsage mandatory
Indicates the accumulated energy usage per phase in tenths of kWh.
Displayed as 0 when not available or no energy used.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.11
pmmBranchCircuitEnergyUsageResetDate mandatory
The date that the kWh usage was reset, in the format mm/dd/yyyy.
The default energy usage reset date is Not Available.
Displayed as NA when breaker is not installed
or if not first pole of breaker.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.12
pmmBranchCircuitTotalPowerFactor mandatory
Indicates the total power factor of the branch circuit.
A value of 100 representing a unity power factor (1.00)
Specified in hundredths. Returns -1 if unsupported.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.13
pmmBranchCircuitBreakerState mandatory
This value indicates the current state of branch
circuit breaker.
1 will indicate open,
2 will indicate closed,
3 will indicate unknown.
Enumeration
Enumerated Values:
1open
2closed
3unknown
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.14
pmmBranchCircuitMinCurrentThreshold mandatory
Threshold below which a branch circuit minimum current
condition will be generated.
Specified as a percentage of the branch breaker rating
represented in the OID pmmBranchCircuitBreakerRating
A value of zero indicates t…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.15
pmmBranchCircuitLowCurrentThreshold mandatory
Threshold below which a branch circuit low current
condition will be generated.
Specified as a percentage of the branch breaker rating
represented in the OID pmmBranchCircuitBreakerRating
A value of zero indicates that …
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.16
pmmBranchCircuitHighCurrentThreshold mandatory
Threshold above which a branch circuit high current
condition will be generated.
Specified as a percentage of the branch breaker rating
represented in the OID pmmBranchCircuitBreakerRating
A value of zero indicates that…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.17
pmmBranchCircuitMaxCurrentThreshold mandatory
Threshold above which a branch circuit maximum current
condition will be generated.
Specified as a percentage of the branch breaker rating
represented in the OID pmmBranchCircuitBreakerRating
A value of zero indicates t…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.18
pmmBranchCircuitMinApparentPowerThreshold mandatory
Threshold below which a branch circuit minimum apparent
power condition will be generated.
Specified as a percent of the branch breaker apparent power rating.
A value of zero indicates that the threshold is disabled.
Th…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.19
pmmBranchCircuitMaxApparentPowerThreshold mandatory
Threshold above which a branch circuit maximum apparent
power condition will be generated.
Specified as a percent of the branch breaker apparent power rating.
A value of zero indicates that the threshold is disabled.
Th…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.20
pmmBranchCircuitAlaramGeneration mandatory
Alarm generation status.
1 will indicate enabled,
2 will indicate disabled,
3 will indicate unknown.
Enumerationr/w
Enumerated Values:
1enabled
2disabled
3unknown
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.21
pmmBranchCircuitBreakerOpenAlarm mandatory
Breaker open alarm status.
1 will indicate enabled,
2 will indicate disabled,
3 will indicate unknown.
Enumerationr/w
Enumerated Values:
1enabled
2disabled
3unknown
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.22
pmmBranchCircuitBreakerAverageCurrent mandatory
Average branch breaker current. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.23
pmmBranchCircuitMaxInstantaneousCurrentPhase mandatory
Branch circuit maximum instantaneous current. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.24
pmmBranchCircuitBreakerMaxInstantaneousAverageCurrent mandatory
Average branch breaker maximum instantaneous current. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.25
pmmBranchCircuitAngle mandatory
Branch circuit phase angle. Measured in tenths of Decimal.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.26
pmmBranchCircuitActivePower mandatory
Branch circuit Active power. Measured in tenths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.27
pmmBranchCircuitApparentPower mandatory
Branch circuit apparent power. Measured in tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.28
pmmBranchCircuitBreakerEnergyTotalUsage mandatory
Indicates the circuit Breaker total accumulated energy usage in tenths of kWh.
Displayed as 0 when not available or no energy used.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.29
pmmBranchCircuitPowerFactor mandatory
Indicates the power factor of the branch circuit.
A value of 100 representing a unity power factor (1.00)
Specified in hundredths.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.30
pmmBranchCircuitTHD mandatory
Branch circuit current harmonic distortion.
Specified in tenths of percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.31
pmmBranchCircuitBreakerTHD mandatory
Average branch breaker current harmonic distortion.
Specified in tenths of percent.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.32
pmmBranchCircuitBreakerLoad mandatory
Total load on the Breaker.
Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.33
pmmBranchCircuitBranchNumber mandatory
The branch number.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.34
pmmBranchCircuitChannelCTSize mandatory
The branch CT Size.
Returns -1 if unsupported or failed.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.35
pmmBranchCircuitCurrentMaxAlarm mandatory
Current maximum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.36
pmmBranchCircuitCurrentHighAlarm mandatory
Current high alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.37
pmmBranchCircuitCurrentLowAlarm mandatory
Current low alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.38
pmmBranchCircuitCurrentMinAlarm mandatory
Current minimum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.39
pmmBranchCircuitApparentPowerMaxAlarm mandatory
Apparent power maximum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.40
pmmBranchCircuitApparentPowerMinAlarm mandatory
Apparent power minimum alarm generation status.
1 - enabled
2 - disabled
3 - unknown
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.41

pmmSiteConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.28.3.4.2 · 1 row entry · 7 columns
A list of PMM site configurable entries.
pmmSiteConfigEntry entry .1.3.6.1.4.1.318.1.1.28.3.4.2.1
An entry containing information applicable to a
particular site configuration.
Indexes
pmmSiteConfigIndex
Column Syntax OID
pmmSiteConfigIndex mandatory
PMM site configuration identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.4.2.1.1
pmmSiteConfigNominalPtoPVoltage mandatory
The nominal input phase to phase voltage to the PMM. Measured in Volts,
line-to-line for a 3-wire (delta) service or line-to-neutral for a
4-wire (wye) service.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.4.2.1.2
pmmSiteConfigNominalPtoNVoltage mandatory
The nominal input phase to neutral voltage to the PMM. Measured in Volts,
line-to-line for a 3-wire (delta) service or line-to-neutral for a
4-wire (wye) service.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.4.2.1.3
pmmSiteConfigNominalCurrent mandatory
The nominal input current to the PMM. Measured in tenths of Amps.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.4.2.1.4
pmmSiteConfigNominalFrequency mandatory
The nominal input frequency to the PMM. Measured in tenths of Hertz.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.4.2.1.5
pmmSiteConfigNominalApparentPower mandatory
The nominal input apparent power to the PMM. Measured in tenths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.28.3.4.2.1.6
pmmSiteConfigServiceType mandatory
The type of utility input to the PMM. Either 3 wires (delta), or 4 wires (wye).
Enumeration
Enumerated Values:
1threeWire
2fourWire
.1.3.6.1.4.1.318.1.1.28.3.4.2.1.7

chargerInputPhaseTable

table mandatory
.1.3.6.1.4.1.318.1.1.29.2.1 · 1 row entry · 5 columns
A list of input table entries.  The number of entries
is given by the sum of the Charger input phases.
chargerInputPhaseEntry entry .1.3.6.1.4.1.318.1.1.29.2.1.1
An entry containing information applicable to a
particular input phase.
Indexes
chargerInputPhaseTableIndex
Column Syntax OID
chargerInputPhaseTableIndex mandatory
The input identifier.
If not supported, return 0.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.29.2.1.1.1
chargerInputPhaseVoltage mandatory
The input voltage in VAC, or -1 if it's unsupported
by this Charger.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.29.2.1.1.2
chargerInputPhaseMinVoltage mandatory
The lowest input voltage to the Charger during the previous minute of operation, or -1 if it's unsupported
by this Charger.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.29.2.1.1.3
chargerInputPhaseMaxVoltage mandatory
The highest input voltage to the Charger during the previous minute of operation, or -1 if it's unsupported
by this Charger.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.29.2.1.1.4
chargerInputPhaseCurrent mandatory
The input current in 0.1 amperes, or -1 if it's
unsupported by this Charger.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.29.2.1.1.5

ePDUDeviceStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.30.2.1 · 1 row entry · 12 columns
A table of Easy PDU status information
ePDUDeviceStatusEntry entry .1.3.6.1.4.1.318.1.1.30.2.1.1
Status information from the Easy PDU being queried
Indexes
ePDUDeviceStatusIndex
Column Syntax OID
ePDUDeviceStatusIndex mandatory
The index to the Easy PDU status table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.1
ePDUDeviceStatusModule mandatory
The user-defined Rack PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.2
ePDUDeviceStatusVersion mandatory
The Easy PDU firmware and hardware version
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.30.2.1.1.3
ePDUDeviceStatusModelNumber mandatory
The Easy PDU model number
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.30.2.1.1.4
ePDUDeviceStatusSerialNumber mandatory
The Easy PDU serial number
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.30.2.1.1.5
ePDUDeviceStatusNumPhases mandatory
The number of phases present in the Easy PDU
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.6
ePDUDeviceStatusActivePower mandatory
Indicates the PDU Active Power. Units:1 Watt.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.7
ePDUDeviceStatusReactivePower mandatory
Indicates the PDU Reactive Power. Units:1 Var.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.8
ePDUDeviceStatusApparentPower mandatory
Indicates the PDU Apparent Power. Units:1 VA.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.9
ePDUDeviceStatusPowerFactor mandatory
Indicates the PDU Power Factor. Units:0.1%.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.10
ePDUDeviceStatusEnergy mandatory
Indicates the PDU Energy. Units:1 Wh.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.11
ePDUDeviceStatusFrequency mandatory
Indicates the PDU Frequency. Units:0.001 Hz.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.1.1.12

ePDUDeviceControlTable

table mandatory
.1.3.6.1.4.1.318.1.1.30.2.2 · 1 row entry · 5 columns
A table of Easy PDU control data
ePDUDeviceControlEntry entry .1.3.6.1.4.1.318.1.1.30.2.2.1
Control data from Easy PDU being queried
Indexes
ePDUDeviceControlIndex
Column Syntax OID
ePDUDeviceControlIndex mandatory
The index to the Easy PDU control table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.2.1.1
ePDUDeviceControlModule mandatory
The user-defined Easy PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.2.2.1.2
ePDUDeviceControlReboot mandatory
Setting this OID to reboot (1) will cause the device reboot immediately.
Getting this OID in models that support this feature will do nothing and
return the noOperation(0) value.
Enumerationr/w
Enumerated Values:
0noOperation
1reboot
.1.3.6.1.4.1.318.1.1.30.2.2.1.3
ePDUDeviceControlEnergyReset mandatory
Setting this OID to reset (1) will cause the device energy meter value
to be reset to zero.

Getting this OID in models that support this feature will do nothing
and return the noOperation(0) value.
Enumerationr/w
Enumerated Values:
0noOperation
1reset
.1.3.6.1.4.1.318.1.1.30.2.2.1.4
ePDUDeviceControlBeepAlarm mandatory
User-defined Beep alarm, 1 for turn off Beep, 2 for turn on Beep.
Models that do not support this feature will respond to this OID
with a value of -1.
Enumerationr/w
Enumerated Values:
1off
2on
.1.3.6.1.4.1.318.1.1.30.2.2.1.5

ePDUPhaseConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.30.4.1 · 1 row entry · 7 columns
A table of Easy PDU phase configuration data
ePDUPhaseConfigEntry entry .1.3.6.1.4.1.318.1.1.30.4.1.1
Configuration data from currently queried Easy PDU phase
Indexes
ePDUPhaseConfigIndex
Column Syntax OID
ePDUPhaseConfigIndex mandatory
The index to the Easy PDU phase configuration table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.1.1.1
ePDUPhaseConfigModule mandatory
The user-defined Easy PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.1.1.2
ePDUPhaseConfigNumber mandatory
The numeric phase ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.1.1.3
ePDUPhaseConfigOverVoltageThreshold mandatory
User-defined Phase Over Voltage alarm threshold. Units:0.1 V.
Models that do not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.1.1.4
ePDUPhaseConfigLowVoltageThreshold mandatory
User-defined Phase Low Voltage alarm threshold. Units:0.1 V.
Models that do not support this feature will
respond to this OID with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.1.1.5
ePDUPhaseConfigOverCurrentThreshold mandatory
User-defined Phase Over Current alarm threshold. Units:0.01 A.
Models that do not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.1.1.6
ePDUPhaseConfigLowCurrentThreshold mandatory
User-defined Phase Low Current alarm threshold. Units:0.01 A.
Models that do not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.1.1.7

ePDUPhaseStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.30.4.2 · 1 row entry · 10 columns
A table of Rack PDU phase status data
ePDUPhaseStatusEntry entry .1.3.6.1.4.1.318.1.1.30.4.2.1
Status data from currently queried Easy PDU phase
Indexes
ePDUPhaseStatusIndex
Column Syntax OID
ePDUPhaseStatusIndex mandatory
The index to the Easy PDU phase configuration table entry
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.318.1.1.30.4.2.1.1
ePDUPhaseStatusModule mandatory
The user-defined Easy PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.2
ePDUPhaseStatusNumber mandatory
The numeric phase ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.3
ePDUPhaseStatusVoltage mandatory
Indicates the Phase Voltage. Units:0.1 V
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.4
ePDUPhaseStatusCurrent mandatory
Indicates the Phase Current. Units:0.01 A
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.5
ePDUPhaseStatusActivePower mandatory
Indicates the Phase Active Power. Units:1 Watt
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.6
ePDUPhaseStatusReactivePower mandatory
Indicates the Phase Reactive Power. Units:1 Var.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.7
ePDUPhaseStatusApparentPower mandatory
Indicates the Phase Apparent Power. Units:1 VA.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.8
ePDUPhaseStatusPowerFactor mandatory
Indicates the Phase Power Factor. Units:0.1%
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.9
ePDUPhaseStatusEnergy mandatory
Indicates the Phase Energy. Units:1 Wh
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.4.2.1.10

ePDUOutletStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.30.6.1 · 1 row entry · 4 columns
The number of switched outlets on connected Rack PDUs
ePDUOutletStatusEntry entry .1.3.6.1.4.1.318.1.1.30.6.1.1
Switched Outlet status from currently queried
Easy PDU switched outlet
Indexes
ePDUOutletStatusIndex
Column Syntax OID
ePDUOutletStatusIndex mandatory
The index to the Easy PDU switched outlet status information table entry.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Constraints:
range: 1-128
.1.3.6.1.4.1.318.1.1.30.6.1.1.1
ePDUOutletStatusModule mandatory
The user-defined Easy PDU numeric ID.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.6.1.1.2
ePDUOutletStatusNumber mandatory
The numeric switched outlet ID.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.6.1.1.3
ePDUOutletStatusState mandatory
Indicates the present switch state of the Easy PDU switched outlet being queried.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.318.1.1.30.6.1.1.4

ePDUOutletControlTable

table mandatory
.1.3.6.1.4.1.318.1.1.30.6.2 · 1 row entry · 4 columns
A table of Easy PDU switched outlet control data
ePDUOutletControlEntry entry .1.3.6.1.4.1.318.1.1.30.6.2.1
Control data for currently queried Easy PDU switched outlet
Indexes
ePDUOutletControlIndex
Column Syntax OID
ePDUOutletControlIndex mandatory
The index to the Easy PDU switched outlet configuration table entry.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Constraints:
range: 1-128
.1.3.6.1.4.1.318.1.1.30.6.2.1.1
ePDUOutletControlModule mandatory
The user-defined Easy PDU numeric ID.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.6.2.1.2
ePDUOutletControlNumber mandatory
The numeric switched outlet ID.
Models that do not support this feature, will respond to this OID
with a value of notSupported (-1).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.6.2.1.3
ePDUOutletControlCommand mandatory
Getting this variable will return the outlet state. If
the outlet is on, the immediateOn (1) value will be returned.
If the outlet is off, the immediateOff (2) value will be
returned. If the state of the outlet cannot b…
Enumerationr/w
Enumerated Values:
1immediateOn
2immediateOff
3outletUnknown
.1.3.6.1.4.1.318.1.1.30.6.2.1.4

ePDUSensorConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.30.8.1 · 1 row entry · 6 columns
A table of temperature-humidity sensor configuration data
ePDUSensorConfigEntry entry .1.3.6.1.4.1.318.1.1.30.8.1.1
Configuration data from temperature-humidity sensor being queried
Indexes
ePDUSensorConfigIndex
Column Syntax OID
ePDUSensorConfigIndex mandatory
The index to the temperature-humidity sensor configuration data table entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.1.1.1
ePDUSensorConfigModule mandatory
The user-defined Easy PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.1.1.2
ePDUSensorConfigTempMaxThreshold mandatory
User-defined Max Temperature alarm threshold. Units: 0.1 degrees Celsius.
Models that do not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.1.1.3
ePDUSensorConfigTempMinThreshold mandatory
User-defined Min Temperature alarm threshold. Units: 0.1 degrees Celsius.
Models that do not support this feature will
respond to this OID with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.1.1.4
ePDUSensorConfigHumidityMaxThreshold mandatory
User-defined Max Humidity alarm threshold. Units: 0.1% relative humidity.
Models that do not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.1.1.5
ePDUSensorConfigHumidityMinThreshold mandatory
User-defined Min Humidity alarm threshold. Units: 0.1% relative humidity.
Models that do not support this feature will respond to this OID
with a value of -1.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.1.1.6

ePDUSensorStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.30.8.2 · 1 row entry · 4 columns
A table of temperature-humidity sensor status data
ePDUSensorStatusEntry entry .1.3.6.1.4.1.318.1.1.30.8.2.1
Status information from temperature-humidity sensor being queried
Indexes
ePDUSensorStatusIndex
Column Syntax OID
ePDUSensorStatusIndex mandatory
The index to the temperature-humidity status data table entry
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.318.1.1.30.8.2.1.1
ePDUSensorStatusModule mandatory
The user-defined Easy PDU numeric ID
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.2.1.2
ePDUSensorStatusTemperature mandatory
Sensor temperature reading in tenths of degrees Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.2.1.3
ePDUSensorStatusHumidity mandatory
Sensor humidity reading in 0.1 percent relative humidity.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.30.8.2.1.4

mdcUpsInputTable

table mandatory
.1.3.6.1.4.1.318.1.1.31.2.2.1 · 1 row entry · 2 columns
A list of UPS input table entries. The number of entries
is given by the value of mdcUpsNumUnits.
mdcUpsInputEntry entry .1.3.6.1.4.1.318.1.1.31.2.2.1.1
An entry containing information applicable to a
particular input of UPS.
Indexes
mdcUpsInputTableIndex
Column Syntax OID
mdcUpsInputTableIndex mandatory
The UPS identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.2.2.1.1.1
mdcUpsInputVoltage mandatory
The current utility line voltage in VAC.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.31.2.2.1.1.2

mdcUpsOutputTable

table mandatory
.1.3.6.1.4.1.318.1.1.31.2.3.1 · 1 row entry · 5 columns
A list of UPS output table entries. The number of entries
is given by the value of mdcUpsNumUnits.
mdcUpsOutputEntry entry .1.3.6.1.4.1.318.1.1.31.2.3.1.1
An entry containing information applicable to a
output of particular UPS.
Indexes
mdcUpsOutputTableIndex
Column Syntax OID
mdcUpsOutputTableIndex mandatory
The UPS identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.2.3.1.1.1
mdcUpsOutputVoltage mandatory
The output voltage of the UPS system in VAC.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.31.2.3.1.1.2
mdcUpsOutputCurrent mandatory
The current in amperes drawn by the load on the UPS.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.31.2.3.1.1.3
mdcUpsOutputActivePower mandatory
The total output active power of the UPS system in W.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.2.3.1.1.4
mdcUpsOutputFrequency mandatory
The current output frequency of the UPS system in Hz.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.31.2.3.1.1.5

mdcUpsBatteryTable

table mandatory
.1.3.6.1.4.1.318.1.1.31.2.4.1 · 1 row entry · 3 columns
Table of Battery details. The number of entries
is given by the value of mdcUpsNumUnits.
mdcUpsBatteryEntry entry .1.3.6.1.4.1.318.1.1.31.2.4.1.1
An entry containing information applicable to
battery of individual UPS.
Indexes
mdcUpsBatteryTableIndex
Column Syntax OID
mdcUpsBatteryTableIndex mandatory
The UPS identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.2.4.1.1.1
mdcUpsBatteryRunTimeRemaining mandatory
The UPS battery run time remaining before battery
exhaustion.
RFC1155-SMITimeTicks
Textual Convention: RFC1155-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.31.2.4.1.1.2
mdcUpsBatteryCapacity mandatory
The remaining battery capacity expressed in
percent of full capacity.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.31.2.4.1.1.3

mdcCoolingStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.31.3.2.1 · 1 row entry · 4 columns
A list of cooling status table entries. The number of entries
is given by the value of mdcCoolingNumUnits.
mdcCoolingStatusEntry entry .1.3.6.1.4.1.318.1.1.31.3.2.1.1
An entry containing information applicable to a
particular status of cooling unit.
Indexes
mdcCoolingStatusTableIndex
Column Syntax OID
mdcCoolingStatusTableIndex mandatory
The cooling unit identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.3.2.1.1.1
mdcCoolingStatusSupplyAirTemp mandatory
The unit supply air temperature in degree Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.3.2.1.1.2
mdcCoolingStatusReturnAirTemp mandatory
The unit return air temperature in degree Celsius.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.3.2.1.1.3
mdcCoolingStatusOperateMode mandatory
The cooling unit operating mode.
Enumeration
Enumerated Values:
1unknown
2cooling
3dehumidification
4bmsshutdown
5coolinghmishutdown
6faultshutdown
7remoteshutdown
8coolingorauxiliaryheating
.1.3.6.1.4.1.318.1.1.31.3.2.1.1.4

mdcCoolingConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.31.3.3.4 · 1 row entry · 4 columns
A list of cooling configuration table entries. The number of entries
is given by the value of mdcCoolingNumUnits.
mdcCoolingConfigEntry entry .1.3.6.1.4.1.318.1.1.31.3.3.4.1
An entry containing information applicable to
configuration of particular cooling unit.
Indexes
mdcCoolingConfigTableIndex
Column Syntax OID
mdcCoolingConfigTableIndex mandatory
The cooling unit identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.3.3.4.1.1
mdcCoolingConfigOutletAirTemp mandatory
Outlet air temperature set point. This OID represents the value sent to
the particular cooling unit in degree Celsius.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.3.3.4.1.2
mdcCoolingConfigPTCHeater mandatory
The status of PTC heater of particular cooling unit.
Enumeration
Enumerated Values:
1unknown
2active
3inactive
.1.3.6.1.4.1.318.1.1.31.3.3.4.1.3
mdcCoolingConfigCondensationpump mandatory
The status of condensation pump of particular cooling unit.
Enumeration
Enumerated Values:
1unknown
2active
3inactive
.1.3.6.1.4.1.318.1.1.31.3.3.4.1.4

mdcMeterStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.31.5.2.1 · 1 row entry · 6 columns
A list of meter status table entries. The number of entries
is given by the value of mdcMeterNumUnits.
mdcMeterStatusEntry entry .1.3.6.1.4.1.318.1.1.31.5.2.1.1
An entry containing information applicable to a
particular status of meter.
Indexes
mdcMeterStatusTableIndex
Column Syntax OID
mdcMeterStatusTableIndex mandatory
The meter identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.5.2.1.1.1
mdcMeterFrequency mandatory
The frequency in Hertz.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.5.2.1.1.2
mdcMeterVoltage mandatory
The voltage in Volts as measured by the meter.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.5.2.1.1.3
mdcMeterCurrent mandatory
The current in Amps as measured by the meter.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.5.2.1.1.4
mdcMeterActivePower mandatory
Shows the active power measured by the meter in hundreths of kW.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.5.2.1.1.5
mdcMeterApparentPower mandatory
Shows the apparent power measured by the meter in hundreths of kVA.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.5.2.1.1.6

mdcMeterConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.31.5.3.1 · 1 row entry · 9 columns
A list of meter configuration table entries. The number of entries
is given by the value of mdcMeterNumUnits.
mdcMeterConfigEntry entry .1.3.6.1.4.1.318.1.1.31.5.3.1.1
An entry containing information applicable to
configuration of particular meter.
Indexes
mdcMeterConfigTableIndex
Column Syntax OID
mdcMeterConfigTableIndex mandatory
The meter identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.1
mdcMeterMinVoltThreshold mandatory
Threshold below which an input minimum voltage condition
will be generated. Specified as percent deviation from
nominal voltage.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.2
mdcMeterLowVoltThreshold mandatory
Threshold below which an input low voltage condition
will be generated. Specified as percent deviation from
nominal voltage.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.3
mdcMeterHighVoltThreshold mandatory
Threshold above which an input high voltage condition
will be generated. Specified as percent deviation from
nominal voltage.
Integer32r/w
Constraints:
range: 0-120
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.4
mdcMeterMaxVoltThreshold mandatory
Threshold above which an input maximum voltage condition
will be generated. Specified as percent deviation from
nominal voltage.
Integer32r/w
Constraints:
range: 0-120
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.5
mdcMeterMinCurrentThreshold mandatory
Threshold below which an input minimum current condition will be generated.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.6
mdcMeterLowCurrentThreshold mandatory
Threshold below which an input low current condition will be generated.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.7
mdcMeterHighCurrentThreshold mandatory
Threshold above which an input high current condition will be generated.
Integer32r/w
Constraints:
range: 0-110
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.8
mdcMeterMaxCurrentThreshold mandatory
Threshold above which an input maximum current condition will be generated.
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.318.1.1.31.5.3.1.1.9

ats5gDeviceIdentTable

table mandatory
.1.3.6.1.4.1.318.1.1.33.2 · 1 row entry · 14 columns
This table organizes the identifying data of devices in the device group.
ats5gDeviceIdentEntry entry .1.3.6.1.4.1.318.1.1.33.2.1
This entry organizes the identity data of a single device.
Indexes
ats5gIdentDeviceIndex
Column Syntax OID
ats5gIdentDeviceIndex mandatory
This value is the data entry's index in the identity table.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.318.1.1.33.2.1.1
ats5gIdentConfigModuleID mandatory
This value is ID number that can be configured for each device. It cannot be
greater than the maximum number of devices in the network port sharing (NPS)
group (32).
Changing this value causes the device to reboot, whic…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.2.1.2
ats5gIdentModuleType mandatory
This value describes the role the specified device holds in the device group:
notNPS(1) specifies that the device is not in a group
host(2) specifies that a device will broadcast firmware updates to guests
guest(3) spec…
Enumeration
Enumerated Values:
1notNPS
2host
3guest
.1.3.6.1.4.1.318.1.1.33.2.1.3
ats5gIdentModuleStatus mandatory
This value tracks the communication status of a device within the group.
Enumeration
Enumerated Values:
1notPresent
2checkingComm
3lostComm
4firmwareUpdate
5firmwareVerify
6active
7firmwareAborted
8unknown
.1.3.6.1.4.1.318.1.1.33.2.1.4
ats5gIdentSerialNumber mandatory
This is the serial number of the automatic transfer switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.5
ats5gIdentModelNumber mandatory
This is the model number of the automatic transfer switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.6
ats5gIdentHardwareRev mandatory
This is the hardware revision of the automatic transfer switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.7
ats5gIdentManufactureDate mandatory
This is the manufacture date of the automatic transfer switch.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.8
ats5gIdentBootmonRev mandatory
This is the boot monitor firmware revision of the network management card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.9
ats5gIdentAOSRev mandatory
This is the operating system firmware revision of the network management card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.10
ats5gIdentAppRev mandatory
This is the application firmware revision of the network management card.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.11
ats5gIdentConfigName mandatory
This is the configurable name of the device. It may be up to 255 characters long.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.12
ats5gIdentConfigLocation mandatory
This is the configurable location of the device. It may be up to 255 characters long.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.13
ats5gIdentConfigContact mandatory
This is the configurable contact information of the device. It may be up to 255 characters long.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.2.1.14

ats5gDeviceSwitchTable

table mandatory
.1.3.6.1.4.1.318.1.1.33.3 · 1 row entry · 41 columns
This table organizes the data specific to the automatic transfer switch.
ats5gDeviceSwitchEntry entry .1.3.6.1.4.1.318.1.1.33.3.1
This entry organizes the switch data of a single device.
Indexes
ats5gSwitchDeviceIndex
Column Syntax OID
ats5gSwitchDeviceIndex mandatory
This value is the data entry's index in the switching table.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.318.1.1.33.3.1.1
ats5gSwitchModuleID mandatory
This value is the ats5gIdentConfigModuleID of the device being queried.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.2
ats5gSwitchOrientation mandatory
This value describes the voltage orientation of the ATS.
Enumeration
Enumerated Values:
1unknown
2singlePhase
3splitPhase
4threePhasePhaseToNeutral
5threePhasePhaseToPhase
.1.3.6.1.4.1.318.1.1.33.3.1.3
ats5gSwitchCumulativeAlarmStatus mandatory
This is the severity of the most severe alarm currently active.
Enumeration
Enumerated Values:
1normal
2informational
3warning
4critical
.1.3.6.1.4.1.318.1.1.33.3.1.4
ats5gSwitchCommunicationStatus mandatory
This is the communication status between the network management card
and the automatic transfer switch.
Enumeration
Enumerated Values:
1atsNeverDiscovered
2atsCommEstablished
3atsCommLost
.1.3.6.1.4.1.318.1.1.33.3.1.5
ats5gSwitchConfigFrontPanelLockout mandatory
This is the configurable lockout status of the source preference toggle button
on the front panel. The button does nothing while the front panel is locked.
Enumerationr/w
Enumerated Values:
1disableFrontPanel
2enableFrontPanel
.1.3.6.1.4.1.318.1.1.33.3.1.6
ats5gSwitchConfigPreferredSource mandatory
This is the configurable source preference. If the ATS is fully redundant the
preferred source will be the selected source. If the preferred source is none(3),
the ATS will switch sources only in response to measured ch…
Enumerationr/w
Enumerated Values:
1sourceA
2sourceB
3none
.1.3.6.1.4.1.318.1.1.33.3.1.7
ats5gSwitchSelectedSource mandatory
This is the selected source that will be used to power downstream devices.
Enumeration
Enumerated Values:
1sourceA
2sourceB
3none
.1.3.6.1.4.1.318.1.1.33.3.1.8
ats5gSwitchRedundancyState mandatory
This is the ATS redundancy status. While this value is atsFullyRedundant(2),
either input may be used to power downstream devices. While this value is
atsRedundancyLost(1), one input has failed validation and downstream…
Enumeration
Enumerated Values:
1atsRedundancyLost
2atsFullyRedundant
.1.3.6.1.4.1.318.1.1.33.3.1.9
ats5gSwitchSourceAStatus mandatory
This is the input status of source A. The ATS will use source B as the selected source
while this value is fail(1).
Enumeration
Enumerated Values:
1fail
2ok
.1.3.6.1.4.1.318.1.1.33.3.1.10
ats5gSwitchSourceBStatus mandatory
This is the input status of source B. The ATS will use source A as the selected source
while this value is fail(1).
Enumeration
Enumerated Values:
1fail
2ok
.1.3.6.1.4.1.318.1.1.33.3.1.11
ats5gSwitchRatedVoltage mandatory
This is the default nominal line VRMS in volts (V) for this unit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.12
ats5gSwitchConfigNominalVoltage mandatory
This is the configurable line VRMS in volts (V) that will be used to select sources.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.13
ats5gSwitchConfigTransferVoltageRange mandatory
This value specifies which voltage transfer range should be used to disqualify
sources and raise alarms. The narrow transfer voltage must be less than the medium
transfer voltage, which must be less than the wide transf…
Enumerationr/w
Enumerated Values:
1wide
2medium
3narrow
.1.3.6.1.4.1.318.1.1.33.3.1.14
ats5gSwitchConfigTransferVoltageWide mandatory
This is the configurable transfer range in volts (V) used to disqualify sources when
ats5gSwitchConfigTransferVoltageRange is wide(1).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.15
ats5gSwitchConfigTransferVoltageMedium mandatory
This is the configurable transfer range in volts (V) used to disqualify sources when
ats5gSwitchConfigTransferVoltageRange is medium(2).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.16
ats5gSwitchConfigTransferVoltageNarrow mandatory
This is the configurable transfer range in volts (V) used to disqualify sources when
ats5gSwitchConfigTransferVoltageRange is narrow(3).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.17
ats5gSwitchConfigVoltageSensitivity mandatory
This is the configured sensitivity threshold for rapid changes to input voltage.
It is recommended to use high(1) unless frequent small changes are expected.
Enumerationr/w
Enumerated Values:
1high
2low
.1.3.6.1.4.1.318.1.1.33.3.1.18
ats5gSwitchSourceAVoltage mandatory
This is the measured line VRMS of source A reported in volts (V).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.19
ats5gSwitchSourceBVoltage mandatory
This is the measured line VRMS of source B reported in volts (V).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.20
ats5gSwitchRatedFrequency mandatory
This is the default nominal line frequency for this unit reported in Hertz (Hz).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.21
ats5gSwitchConfigNominalFrequency mandatory
This is the configurable line frequency in Hertz (Hz) that will be used to select
sources. If the difference between ats5gSwitchConfigNominalFrequency and a source's
measured frequency is greater than ats5gSwitchConfigF…
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.22
ats5gSwitchConfigFrequencyDeviation mandatory
This is the configurable frequency deviation in Hertz (Hz) that will be used to select
sources.
Enumerationr/w
Enumerated Values:
1one
2two
3three
5five
10ten
.1.3.6.1.4.1.318.1.1.33.3.1.23
ats5gSwitchSourceAFrequency mandatory
This is the measured line frequency of source A reported in Hertz (Hz).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.24
ats5gSwitchSourceBFrequency mandatory
This is the measured line frequency of source B reported in Hertz (Hz).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.25
ats5gSwitchEventCountStartTime mandatory
This value is the time and date of the last event count reset action.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.3.1.26
ats5gSwitchEventCountRedundancyLoss mandatory
This value tracks the number of redundancy loss events. It increments each time
a source becomes invalid.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.27
ats5gSwitchEventCountSourceSwitch mandatory
This value tracks the number of source switch events. It increments each time the
selected source changes.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.28
ats5gSwitchEventCountSourcePrefChange mandatory
This value tracks the number of preferred source configuration change events.
It increments each time the user updates their source preference.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.29
ats5gSwitchEventCountSpikeOrDrop mandatory
This value tracks voltage spike and drop events. It increments each time a
source's measured instantaneous voltage increases or decreases rapidly.
This depends on configured voltage sensitivity.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.30
ats5gSwitchEventCountSurgeOrDroop mandatory
This value tracks voltage surge or droop events. It increments each time a
source's calculated VRMS increases or decreases rapidly.
This does not depend on any user configurations.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.31
ats5gSwitchEventCountFreqOutOfRange mandatory
This value tracks frequency threshold violations. It increments each time a source
is disqualified because the difference between its measured frequency and the
configured nominal frequency is greater than the configure…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.3.1.32
ats5gSwitchControlEventCountReset mandatory
This control resets the event counts when the value is set to reset(2).
Enumerationr/w
Enumerated Values:
1none
2reset
.1.3.6.1.4.1.318.1.1.33.3.1.33
ats5gSwitchVoltageOutStatus mandatory
This value is on(2) while the output outlets are powered.
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.318.1.1.33.3.1.34
ats5gSwitchOverCurrentState mandatory
This value is atsOverCurrent(1) when the ATS has exceeded the output
current threshold and will not allow a switch over to the alternate power
source if the current source fails.
Enumeration
Enumerated Values:
1atsOverCurrent
2atsCurrentOK
.1.3.6.1.4.1.318.1.1.33.3.1.35
ats5gSwitchPhaseSyncStatus mandatory
This value tracks the phase sync status.
Enumeration
Enumerated Values:
1inSync
2outOfSync
.1.3.6.1.4.1.318.1.1.33.3.1.36
ats5gSwitchSourceA24VSupplyStatus mandatory
This value tracks the internal source A 24VDC power supply status.
Enumeration
Enumerated Values:
1fail
2ok
.1.3.6.1.4.1.318.1.1.33.3.1.37
ats5gSwitchSourceB24VSupplyStatus mandatory
This value tracks the internal source B 24VDC power supply status.
Enumeration
Enumerated Values:
1fail
2ok
.1.3.6.1.4.1.318.1.1.33.3.1.38
ats5gSwitchSourceA48VSupplyStatus mandatory
This value tracks the internal source A 48VDC power supply status.
Enumeration
Enumerated Values:
1fail
2ok
.1.3.6.1.4.1.318.1.1.33.3.1.39
ats5gSwitchSourceB48VSupplyStatus mandatory
This value tracks the internal source B 48VDC power supply status.
Enumeration
Enumerated Values:
1fail
2ok
.1.3.6.1.4.1.318.1.1.33.3.1.40
ats5gSwitch3p3VSupplyStatus mandatory
This value tracks the internal 3.3VDC power supply status.
Enumeration
Enumerated Values:
1fail
2ok
.1.3.6.1.4.1.318.1.1.33.3.1.41
.1.3.6.1.4.1.318.1.1.33.4 · 1 row entry · 18 columns
This table organizes the data specific to the environment monitoring accessories.
ats5gDeviceEnvironmentEntry entry .1.3.6.1.4.1.318.1.1.33.4.1
This entry organizes the switch data of a single device.
Indexes
ats5gEnvDeviceIndex
Column Syntax OID
ats5gEnvDeviceIndex mandatory
This value is the data entry's index in the environment table.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.318.1.1.33.4.1.1
ats5gEnvModuleID mandatory
This value is the ats5gIdentConfigModuleID of the device being queried.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.2
ats5gEnvSensorType mandatory
This value is the type of the currently attached sensor accessory.
Enumeration
Enumerated Values:
1noSensor
2sensorUnrecognized
3sensorUnsupported
4temperatureOnly
5temperatureHumidity
.1.3.6.1.4.1.318.1.1.33.4.1.3
ats5gEnvAlarmStatus mandatory
This is the severity of the most severe environment-specific alarm currently active.
Enumeration
Enumerated Values:
1normal
2informational
3warning
4critical
.1.3.6.1.4.1.318.1.1.33.4.1.4
ats5gEnvTemperature mandatory
This is the measured temperature of the attached sensor reported in tenth-degrees
Fahrenheit. The value reports as -1 if the attached sensor does not support temperature
measurements.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.5
ats5gEnvConfigTempMaxThreshold mandatory
This is the configured maximum temperature threshold reported in degrees Fahrenheit.
The value reports as -1 if the attached sensor does not support temperature measurements.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.6
ats5gEnvConfigTempHighThreshold mandatory
This is the configured high temperature threshold reported in degrees Fahrenheit.
The value reports as -1 if the attached sensor does not support temperature measurements.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.7
ats5gEnvConfigTempHysteresis mandatory
This is the configured temperature threshold hysteresis reported in degrees Fahrenheit.
The value reports as -1 if the attached sensor does not support temperature measurements.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.8
ats5gEnvConfigTempAlarmsEnabled mandatory
This is the configured temperature monitoring status. While this value is disabled(1),
no temperature-related alarms will be active. The value reports as -1 if the attached
sensor does not support temperature measuremen…
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.33.4.1.9
ats5gEnvHumidity mandatory
This is the measured humidity around the attached sensor reported in percent relative
humidity. The value reports as -1 if the attached sensor does not support humidity
measurements.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.10
ats5gEnvConfigHumLowThreshold mandatory
This is the configured low humidity threshold reported in %RH. The value reports as -1
if the attached sensor does not support humidity measurements.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.11
ats5gEnvConfigHumMinThreshold mandatory
This is the configured minimum humidity threshold reported in %RH. The value reports
as -1 if the attached sensor does not support humidity measurements.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.12
ats5gEnvConfigHumHysteresis mandatory
This is the configured humidity threshold hysteresis reported in %RH. The value reports
as -1 if the attached sensor does not support humidity measurements.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.13
ats5gEnvConfigHumAlarmsEnabled mandatory
This is the configured humidity monitoring status. While this value is disabled(1),
no humidity-related alarms will be active. The value reports as -1 if the attached
sensor does not support humidity measurements.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.318.1.1.33.4.1.14
ats5gEnvPeakTemperature mandatory
This is the highest temperature recorded since the last peak temperature reset,
reported in degrees Fahrenheit.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.4.1.15
ats5gEnvPeakTempTime mandatory
This is the date and time that the peak temperature was recorded.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.4.1.16
ats5gEnvPeakTempResetTime mandatory
This is the date and time that the peak temperature was last reset.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.1.33.4.1.17
ats5gEnvControlPeakTempReset mandatory
This control resets the peak temperature when the value is set to reset(2).
Enumerationr/w
Enumerated Values:
1none
2reset
.1.3.6.1.4.1.318.1.1.33.4.1.18

ats5gBankTable

table mandatory
.1.3.6.1.4.1.318.1.1.33.6 · 1 row entry · 10 columns
This table organizes the bank data of devices in the device group.
ats5gBankEntry entry .1.3.6.1.4.1.318.1.1.33.6.1
This entry organizes the bank data of a single device.
Indexes
ats5gBankIndex
Column Syntax OID
ats5gBankIndex mandatory
This value is the data entry's index in the bank table.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.318.1.1.33.6.1.1
ats5gBankModuleID mandatory
This value is the ats5gIdentConfigModuleID of the device being queried.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.6.1.2
ats5gBankType mandatory
This value describes the type of bank associated with this bank index. If a device
has multiple banks, then its total(1) output will include the bank1(2) and bank2(3)
outputs.
Enumeration
Enumerated Values:
1total
2bank1
3bank2
.1.3.6.1.4.1.318.1.1.33.6.1.3
ats5gBankRatedAmps mandatory
This value is the rated output of the specified bank reported in amps (A).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.6.1.4
ats5gBankOutputTenthAmps mandatory
This value is the measured output of the specified bank reported in tenths of amps (A).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.6.1.5
ats5gBankConfigLowLoadThreshold mandatory
This value is the configured low load threshold of the specified bank reported
in amps (A).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.6.1.6
ats5gBankConfigNearOverLoadThreshold mandatory
This value is the configured near overload threshold of the specified bank reported
in amps (A).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.6.1.7
ats5gBankConfigOverloadThreshold mandatory
This value is the configured overload threshold of the specified bank reported
in amps (A).
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.6.1.8
ats5gBankApparentPower mandatory
This value is the calculated apparent power of the specified bank reported
in kilovolt-amps (kVA).
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.33.6.1.9
ats5gBankOutputCurrentStatus mandatory
This value tracks the load status of the specified bank.
Enumeration
Enumerated Values:
1lowLoad
2normal
3nearOverload
4overload
.1.3.6.1.4.1.318.1.1.33.6.1.10

powerNetSoftwareTable

table mandatory
.1.3.6.1.4.1.318.1.2.1.2.2 · 1 row entry · 4 columns
A list of the software monitoring the UPS.
powerNetSoftwareEntry entry .1.3.6.1.4.1.318.1.2.1.2.2.1
An entry containing information on a software module.
Indexes
moduleNumber
Column Syntax OID
moduleNumber mandatory
The index into the Software Entry Table
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.2.1.2.2.1.1
moduleName mandatory
The name of the software module.
OctetString
Constraints:
range: 0-79
.1.3.6.1.4.1.318.1.2.1.2.2.1.2
moduleVersion mandatory
The version of the software module.
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.318.1.2.1.2.2.1.3
moduleDate mandatory
The date of the software module represented as mm-dd-yy.
OctetString
Constraints:
range: 0-9
.1.3.6.1.4.1.318.1.2.1.2.2.1.4

pcnsNmcTable

table mandatory
.1.3.6.1.4.1.318.1.2.3.3.4 · 1 row entry · 3 columns
The Network Management Cards in the UPS devices, which PCNS is monitoring to provide safe shutdown.
pcnsNmcEntry entry .1.3.6.1.4.1.318.1.2.3.3.4.1
Details of the NMC.
Indexes
pcnsNmcIndex
Column Syntax OID
pcnsNmcIndex mandatory
Index of the NMC within PCNS setup.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.2.3.3.4.1.1
pcnsNmcAddr mandatory
The IP address of the NMC.
RFC1155-SMIIpAddress
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.1.2.3.3.4.1.2
pcnsNmcOutlet mandatory
The Outlet Group which PCNS is enrolled with on the NMC.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.2.3.3.4.1.3
.1.3.6.1.4.1.318.1.2.3.5.9 · 1 row entry · 11 columns
The Network Management Cards in the UPS devices, which PCNS is monitoring to provide safe shutdown.
pcnsAdvancedShutdownEntry entry .1.3.6.1.4.1.318.1.2.3.5.9.1
Details of the NMC.
Indexes
pcnsAdvancedGroupNo
Column Syntax OID
pcnsAdvancedGroupNo mandatory
Index of the Advanced Shutdown Group.
RFC1155-SMIGauge
Textual Convention: RFC1155-SMIGauge Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.2.3.5.9.1.1
pcnsAdvancedGroupName mandatory
Name of the Advanced Shutdown Group.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.318.1.2.3.5.9.1.2
pcnsAdvancedGroupNMC mandatory
List of NMCs in the Advanced Shutdown Group.
RFC1213-MIBDisplayString
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.2.3.5.9.1.3
pcnsAdvancedShutdownUPSRequiredForLoad mandatory
Number of UPS devices required to power load.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.2.3.5.9.1.4
pcnsAdvancedShutdownCommandFileEnabled mandatory
Run a shutdown command file before performing graceful shutdown.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.2.3.5.9.1.5
pcnsAdvancedShutdownCommandFile mandatory
Full name of the shutdown command file to run before graceful shutdown.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.1.2.3.5.9.1.6
pcnsAdvancedShutdownCommandFileDuration mandatory
How long in seconds shutdown command file takes to run.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.2.3.5.9.1.7
pcnsAdvancedShutdownPowerchuteServer mandatory
Shut down PowerChute Server.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.2.3.5.9.1.8
pcnsAdvancedShutdownOnLostRedundancy mandatory
Shut down if Redundancy lost.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.2.3.5.9.1.9
pcnsAdvancedTurnOffUps mandatory
Turn off the UPS when performing a graceful shutdown.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.2.3.5.9.1.10
pcnsAdvancedTurnOffSOG mandatory
Turn off the Outlet Group on the UPS when performing a graceful shutdown.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.1.2.3.5.9.1.11
.1.3.6.1.4.1.318.2.1.2 · 1 row entry · 6 columns
A list of managers to send traps to.  The number of
entries is given by the value of mconfigNumTrapReceivers.
mconfigTrapReceiverEntry entry .1.3.6.1.4.1.318.2.1.2.1
The managers to send traps to.
Indexes
trapIndex
Column Syntax OID
trapIndex mandatory
The index to a trap receiver entry.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.2.1.2.1.1
receiverAddr mandatory
The IP address of the manager to send a trap to.
RFC1155-SMIIpAddressr/w
Textual Convention: RFC1155-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.318.2.1.2.1.2
communityString mandatory
The community name to use in the trap when
sent to the manager.
RFC1213-MIBDisplayStringr/w
Textual Convention: RFC1213-MIBDisplayString OctetString
.1.3.6.1.4.1.318.2.1.2.1.3
severity obsolete
The severity threshold of traps to send to the manager.
traps are labeled in severity as informational(1), warning(2),
severe(3). Only traps of equal or greater severity than
this value are sent to the manager.
Enumeration
Enumerated Values:
1information
2warning
3severe
.1.3.6.1.4.1.318.2.1.2.1.4
acceptThisReceiver mandatory
The value of yes(1) indicates that trap generation for this manager is enabled.
The value of no(2) indicates that trap generation for this manager is disabled
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.318.2.1.2.1.5
receiveTrapType obsolete
Type of trap.
Enumeration
Enumerated Values:
1powernet
2ietf
3both
.1.3.6.1.4.1.318.2.1.2.1.6