rPDU2DeviceStatusCommandPending
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.26.4.3.1.11
Object
column
mandatory
Enumeration
Indicates whether or not the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.26.4.3.1.11- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDU2DeviceStatusEntry
- Table
- rPDU2DeviceStatusTable
- Siblings
- 17
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | commandPending |
2 | noCommandPending |
3 | commandPendingUnknown |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2DeviceStatusIndex mandatory The index to the Rack PDU status table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.1 |
| rPDU2DeviceStatusEnergyStartTime mandatory Indicates the date and time of the last device energy
meter reset. Models that do not support this feature will
respond to this OID with string 'notsupported'. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.10 |
| rPDU2DeviceStatusPowerSupplyAlarm mandatory Indicates a power supply alarm is active when value
equals alarm (2) | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.12 |
| rPDU2DeviceStatusPowerSupply1Status mandatory Indicates whether or not an alarm is active in Power
Supply 1 | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.13 |
| rPDU2DeviceStatusPowerSupply2Status mandatory Indicates whether or not an alarm is active in Power
Supply 2 | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.14 |
| rPDU2DeviceStatusOutletsEnergyStartTime mandatory Indicates the date and time of the last outlets energy
meter reset. Models that do not support this feature will
respond to this OID with string 'notsupported'. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.15 |
| rPDU2DeviceStatusApparentPower mandatory The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA).
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.16 |
| rPDU2DeviceStatusPowerFactor mandatory The power factor of the Rack PDU load in hundredths. Models that do not support this feature
will respond to this OID with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.17 |
| rPDU2DeviceStatusNPSType mandatory The device NPS status:
notNPS (1) indicates the Rack PDU is not in an NPS group.
host (2) indicates the Rack PDU has been designated as a host in an NPS group.
Only one Rack PDU… | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.18 |
| rPDU2DeviceStatusModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.2 |
| rPDU2DeviceStatusName mandatory A user-defined string identifying the Rack PDU | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.3 |
| rPDU2DeviceStatusLoadState mandatory Indicates the present load status of the Rack PDU.
Models that do not support this feature will respond to this OID
with a value of notsupported (5). | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.4 |
| rPDU2DeviceStatusPower mandatory The power consumption of the Rack PDU load in hundredths of kilowatts.
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.5 |
| rPDU2DeviceStatusPeakPower mandatory The peak power consumption of the Rack PDU load in hundredths of kilowatts.
Models that do not support this feature will respond to this OID with a value
of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.6 |
| rPDU2DeviceStatusPeakPowerTimestamp mandatory Indicates the date and time that peak power consumption occurred.
Models that do not support this feature will respond to this OID with string
'notsupported'. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.7 |
| rPDU2DeviceStatusPeakPowerStartTime mandatory Indicates the date and time of the last device peak power reset.
Models that do not support this feature will respond to this OID with string
'notsupported'. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.8 |
| rPDU2DeviceStatusEnergy mandatory A user resettable energy meter measuring Rack PDU load
energy consumption in tenths of kilowatt-hours. Models that do not
support this feature will respond to this OID
with a valu… | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.9 |