iemConfigProbeMinTempEnable
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.17
Object
column
mandatory
r/w
Enumeration
The low temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.10.2.2.2.1.17- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- iemConfigProbesEntry
- Table
- iemConfigProbesTable
- Siblings
- 21
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | disabled |
2 | enabled |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| iemConfigProbeNumber mandatory The index to a Environmental Monitor probe entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.1 |
| iemConfigProbeHighHumidEnable mandatory The high humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.10 |
| iemConfigProbeLowHumidEnable mandatory The low humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled(2)… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.11 |
| iemConfigProbeMaxTempThreshold mandatory The maximun temperature alarm threshold for the probe.
Units are displayed in the scale selected in the
'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.12 |
| iemConfigProbeMinTempThreshold mandatory The minimun temperature alarm threshold for the probe.
Units are displayed in the scale selected in the
'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.13 |
| iemConfigProbeMaxHumidThreshold mandatory The maximum humidity alarm threshold for the probe in
percent relative humidity. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.14 |
| iemConfigProbeMinHumidThreshold mandatory The minimum humidity alarm threshold for the probe in
percent relative humidity. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.15 |
| iemConfigProbeMaxTempEnable mandatory The maximum temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to ena… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.16 |
| iemConfigProbeMaxHumidEnable mandatory The maximum humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enable… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.18 |
| iemConfigProbeMinHumidEnable mandatory The minimum humidity alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enable… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.19 |
| iemConfigProbeName mandatory A descriptive name for the probe set by the user,
possibly denoting its location or purpose. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.2 |
| iemConfigProbeTempHysteresis mandatory The number of degrees beyond the temperature thresholds
at which an active temperature alarm will be cleared.
This configuration setting applies to all temperature
thresholds.
Uni… | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.20 |
| iemConfigProbeHumidHysteresis mandatory The number of percent RH points beyond the humidity
thresholds at which an active humidity alarm will be
cleared. This configuration setting applies to all
humidity thresholds.
Un… | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.21 |
| iemConfigProbeLocation mandatory A string describing the location of the probe. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.22 |
| iemConfigProbeHighTempThreshold mandatory The high temperature alarm threshold for the probe.
Units are displayed in the scale selected in the
'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.3 |
| iemConfigProbeLowTempThreshold mandatory The low temperature alarm threshold for the probe.
Units are displayed in the scale selected in the
'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.4 |
| iemConfigProbeTempUnits mandatory The temperature scale used to display the temperature
thresholds of the probe, Celsius(1) or Fahrenheit(2).
This setting is based on the system preferences
configuration in the ag… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.5 |
| iemConfigProbeHighHumidThreshold mandatory The high humidity alarm threshold for the probe in
percent relative humidity. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.6 |
| iemConfigProbeLowHumidThreshold mandatory The low humidity alarm threshold for the probe in
percent relative humidity. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.7 |
| iemConfigProbeHighTempEnable mandatory The high temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enable… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.8 |
| iemConfigProbeLowTempEnable mandatory The low temperature alarm enable/disable for the
probe. No alarm will be generated if this value
is set to disabled(1). The alarm will be
generated if this value is set to enabled… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.9 |