rARUStatusAruAlarmState

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.14.3.3.1.10

Object

column mandatory RFC1213-MIBDisplayString
An ASCII string containing the 8 flags representing
the current alarm state of the ARU. If the state of
the ARU is unknown, this variable is set to 'UNKNOWN'.
              
The flags are numbered 1 to 8, read from left to
right. The flags are defined as follows:
              
Flag  1: Fan Fail 1
Flag  2: Fan Fail 2
Flag  3: Fan Fail 3
Flag  4: Smoke (if ARU is equipped with smoke detector)
              
Flag  5: High Temp (Out of Thermal Control)
Flag  6: Over Temp (Exhaust Temp. Exceeds Override Setpoint)
Flag  7: Fan Fail 4 (Gen 2 ARU only)
Flag  8: Reserved

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.14.3.3.1.10
Type
column
Access
readonly
Status
mandatory
Parent
rARUStatusEntry
Table
rARUStatusTable
Siblings
13

Syntax

RFC1213-MIBDisplayString
Source
RFC1213-MIBDisplayString
Base type
OctetString

Values & Constraints

No enumerated values or constraints recorded.