atsConfigPhaseNearOverLoadThreshold
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.8.4.16.1.4
Object
column
mandatory
r/w
Integer32
A threshold that indicates the current drawn is nearing
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than
or equal to the threshold value.
Minimum value must be greater than the value returned by
the atsConfigPhaseLowLoadThreshold OID.
Maximum value must be less than or equal to the value
returned by the atsConfigPhaseOverLoadThreshold OID.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.8.4.16.1.4- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- atsConfigPhaseEntry
- Table
- atsConfigPhaseTable
- Siblings
- 4
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| atsConfigPhaseTableIndex mandatory The index to the phase table entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.8.4.16.1.1 |
| atsConfigPhase mandatory The phase number of an ATS | column | Enumeration | .1.3.6.1.4.1.318.1.1.8.4.16.1.2 |
| atsConfigPhaseLowLoadThreshold mandatory A threshold that indicates the current drawn is nearing
a low consumption condition. It is represented in Amps.
A warning will be issued when the load is less than the
threshold v… | column | Integer32 | .1.3.6.1.4.1.318.1.1.8.4.16.1.3 |
| atsConfigPhaseOverLoadThreshold mandatory A threshold that indicates the current drawn has entered
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than or