rPDULoadPhaseConfigOverloadThreshold
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.12.2.2.1.1.4
Object
column
mandatory
r/w
Integer32
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Minimum value must be greater than or equal to the value
returned by the rPDULoadPhaseConfigNearOverloadThreshold OID.
Maximum value must be less than or equal to the value
returned by the rPDULoadDevMaxPhaseLoad OID.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.12.2.2.1.1.4- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- rPDULoadPhaseConfigEntry
- Table
- rPDULoadPhaseConfigTable
- Siblings
- 4
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDULoadPhaseConfigIndex mandatory The index to the Rack PDU phase entry. | column | Enumeration | .1.3.6.1.4.1.318.1.1.12.2.2.1.1.1 |
| rPDULoadPhaseConfigLowLoadThreshold mandatory A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less tha… | column | Integer32 | .1.3.6.1.4.1.318.1.1.12.2.2.1.1.2 |
| rPDULoadPhaseConfigNearOverloadThreshold mandatory A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than o… | column | Integer32 | .1.3.6.1.4.1.318.1.1.12.2.2.1.1.3 |
| rPDULoadPhaseConfigAlarm mandatory Getting this OID will return the current Phase Alarm. | column | Enumeration | .1.3.6.1.4.1.318.1.1.12.2.2.1.1.5 |