xPDUBranchBreakerRating
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.2
Object
column
mandatory
r/w
Integer32
Indicates current rating of this breaker. 0=Breaker is not present. 1=Earth leakage connection. 2=Neutral connection. A value greater than 2 indicates breaker current rating in Amps. A value above 60 Amp will signify a remote feed. The xPDUBranchBreakerRDPFeed OID will indicate which breakers are configured as a remote drop. Note: When setting branch circuit thresholds/ratings for an entry, all positions tied (see the xPDUBranchBreakerTieIndicator OID) to this entry will inherit the new threshold/rating.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.2- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- xPDUBranchBreakerEntry
Syntax
Integer32
Values & Constraints
No enumerated values or constraints recorded.