xPDUBranchBreakerRating

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.15.4.2.3.1.2

Object

column mandatory r/w Integer32
Indicates current rating of this breaker.
0=Breaker is not present.
1=Earth leakage connection.
2=Neutral connection.
A value greater than 2 indicates breaker current rating in Amps.
A value above 60 Amp will signify a remote feed.
The xPDUBranchBreakerRDPFeed OID will indicate which breakers are
configured as a remote drop.
Note: When setting branch circuit thresholds/ratings for an entry,
all positions tied (see the xPDUBranchBreakerTieIndicator OID)
to this entry will inherit the new threshold/rating.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.2
Type
column
Access
readwrite
Status
mandatory
Parent
xPDUBranchBreakerEntry
Table
xPDUBranchBreakerTable
Siblings
10

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects

Sibling Objects