rPDU2SensorAnalogVoltageStatusThreshStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.7
Object
column
mandatory
Enumeration
This OID reports the current state of the voltage probe:
A notPresent (1) response indicates that no probe is attached,
or that the attached probe isn't a voltage probe.
A belowMin (2) response indicates that the probe is present and
its measured voltage lies below the minimum threshold.
A belowLow (3) response indicates that the probe is present and
its measured voltage lies below the low threshold.
A normal (4) response indicates that the probe is present
and its measured voltage lies within all voltage thresholds.
An aboveHigh (5) response indicates that the probe is present
and is measuring a voltage above the high threshold.
An aboveMax (6) response indicates that the probe is present
and is measuring a voltage above the maximum threshold.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.26.10.6.1.1.7- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDU2SensorAnalogVoltageStatusEntry
- Table
- rPDU2SensorAnalogVoltageStatusTable
- Siblings
- 6
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | notPresent |
2 | belowMin |
3 | belowLow |
4 | normal |
5 | aboveHigh |
6 | aboveMax |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2SensorAnalogVoltageStatusIndex mandatory The index to the voltage sensor status data
table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.1 |
| rPDU2SensorAnalogVoltageStatusModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.2 |
| rPDU2SensorAnalogVoltageStatusNumber mandatory The voltage sensor numeric ID | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.3 |
| rPDU2SensorAnalogVoltageStatusName mandatory The user-defined voltage sensor ID string | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.4 |
| rPDU2SensorAnalogVoltageStatusCommStatus mandatory The communications status of the sensor | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.5 |
| rPDU2SensorAnalogVoltageStatusHundredthVolts mandatory Sensor voltage reading in hundredths of volts.
Returns -1 for indices without voltage probes. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.6 |