rPDUStatusOutletState
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.12.5.6.1.3
Object
column
mandatory
Enumeration
Getting this OID will return the Outlet load state.
outletLoadNormal(1) indicates that the Outlet is
operating properly within the rPDUOutletConfigMonitoredLowLoadThreshold
and rPDUOutletConfigMonitoredNearOverloadThreshold OID values.
outletLoadLow(2) indicates that the Outlet load has
dropped below the rPDUOutletConfigMonitoredLowLoadThreshold OID value.
An SNMP trap will occur when this state is entered or cleared.
outletLoadNearOverload(3) indicates that the Outlet load
is greater than or equal to the
rPDUOutletConfigMonitoredNearOverloadThreshold OID value.
An SNMP trap will occur when this state is entered or cleared.
outletLoadOverload(4) indicates that the Outlet load is
greater than or equal to the rPDUOutletConfigMonitoredOverloadThreshold
OID value.
An SNMP trap will occur when this state is entered or cleared.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.12.5.6.1.3- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDUStatusOutletEntry
- Table
- rPDUStatusOutletTable
- Siblings
- 2
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | outletLoadNormal |
2 | outletLoadLow |
3 | outletLoadNearOverload |
4 | outletLoadOverload |