xPDUBranchBreakerTieIndicator

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.15.4.2.3.1.4

Object

column mandatory r/w Enumeration
Indicates whether or not the breaker in this position
is logically associated with the breaker immediately below it.
This setting is used grouping the breakers feeding
a multi-pole branch circuit.
Note: When setting an entry's branch breaker tie indicator to breakerTied,
all the positions that are tied to this breaker will take on the rating
and thresholds for this entry of the table.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.15.4.2.3.1.4
Type
column
Access
readwrite
Status
mandatory
Parent
xPDUBranchBreakerEntry
Table
xPDUBranchBreakerTable
Siblings
10

Syntax

Enumeration

Values & Constraints

Enumerated Values
1breakerUnTied
2breakerTied

Related Objects

Sibling Objects