wirelessSensorPodStatusAlarmStatus

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.10.5.2.1.1.26

Object

column mandatory Integer32
The alarm status of the wireless pod sensor.  This integer should be interpreted
as a bit map, with each bit representing the presence or absence of
the specific alarm conditions listed below.  The bit will be '1' if
the condition is present, and '0' if the condition is not present.
              
Bit  Hex. Value  Description
1    0x0001      Maximum temperature exceeded.
2    0x0002      High temperature exceeded.
3    0x0004      Low temperature exceeded.
4    0x0008      Minimum temperature exceeded.
5    0x0010      Maximum humidity exceeded.
6    0x0020      High humidity exceeded.
7    0x0040      Low humidity exceeded.
8    0x0080      Minimum humidity exceeded.
9    0x0100      Low battery exceeded.
10   0x0200      Minimum battery exceeded.
11   0x0400      Low signal strength exceeded.
12   0x0800      Minimum signal strength exceeded.
13   0x1000      Sensor inactive.
14   0x2000      Dry contact in Critical state.
15   0x4000      Dry contact in warning state.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.10.5.2.1.1.26
Type
column
Access
readonly
Status
mandatory
Parent
wirelessSensorPodStatusEntry
Table
wirelessSensorPodStatusTable
Siblings
25

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects