rPDUOutletBankOverloadRestriction

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.12.3.6.1.1.2

Object

column mandatory r/w Enumeration
This OID controls the behavior of a Switched Rack PDU
bank when an overload condition is possible and
additional outlets are requested to be turned on.
              
Setting this OID to alwaysAllowTurnON (1) will always allow
the outlets on the corresponding bank to turn on.
              
Setting this OID to restrictOnNearOverload (2) will not allow
outlets on the corresponding bank to turn on if the
rPDULoadBankConfigNearOverloadThreshold OID is exceeded.
              
Setting this OID to restrictOnOverload (3) will not allow
outlets on the corresponding bank to turn on if the
rPDULoadBankConfigOverloadThreshold OID is exceeded.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.12.3.6.1.1.2
Type
column
Access
readwrite
Status
mandatory
Parent
rPDUOutletBankEntry
Table
rPDUOutletBankTable
Siblings
1

Syntax

Enumeration

Values & Constraints

Enumerated Values
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload

Related Objects

Sibling Objects