upsPhaseNumInputPhases
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.9.2.2.1.2
Object
column
mandatory
Integer32
The number of input phases utilized in this device. The sum of all the upsPhaseNumInputPhases variable indicates the number of rows in the input phase table.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.9.2.2.1.2- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsPhaseInputEntry
- Table
- upsPhaseInputTable
- Siblings
- 5
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsPhaseInputTableIndex mandatory The input identifier. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.1 |
| upsPhaseInputVoltageOrientation mandatory The input voltage orientation:
1: unknown for this UPS
2: singlePhase - phase 1 voltage is between Phase 1
and Neutral.
3: splitPhase - phase 1 voltage is between Phase 1 and
Neut… | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.3 |
| upsPhaseInputFrequency mandatory The input frequency in 0.1 Hertz, or -1 if it's unsupported
by this UPS. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.4 |
| upsPhaseInputType mandatory The input type. | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.5 |
| upsPhaseInputName mandatory A name given to a particular input. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.6 |