sPDUOutletConfigVMRebootDuration
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.5.6.1.1.7
Object
column
mandatory
r/w
Integer32
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence, before turning power back on, at the
end of the reboot sequence.
Allowed values are:
5 wait 5 seconds between off/on.
10 wait 10 seconds between off/on.
15 wait 15 seconds between off/on.
20 wait 20 seconds between off/on.
30 wait 30 seconds between off/on.
45 wait 45 seconds between off/on.
60 wait 60 seconds (1 minute) between off/on.
If a value other than a supported value is provided in a
set request, the MasterSwitch VM interprets it as the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.5.6.1.1.7- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- sPDUOutletConfigVMEntry
- Table
- sPDUOutletConfigVMTable
- Siblings
- 6
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| sPDUOutletConfigVMIndex mandatory The index to the MasterSwitch VM. | column | Integer32 | .1.3.6.1.4.1.318.1.1.5.6.1.1.1 |
| sPDUOutletConfigVMName mandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.6.1.1.2 |
| sPDUOutletConfigVMOutletIndex mandatory The index to the outlet entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.5.6.1.1.3 |
| sPDUOutletConfigVMOutletName mandatory The name of the outlet. Maximum size is 23 characters. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.6.1.1.4 |
| sPDUOutletConfigVMPowerOnTime mandatory The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.
Allowed values are:
… | column | Integer32 | .1.3.6.1.4.1.318.1.1.5.6.1.1.5 |
| sPDUOutletConfigVMPowerOffTime mandatory The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.
Allowed values are:
… | column | Integer32 | .1.3.6.1.4.1.318.1.1.5.6.1.1.6 |