upsBatteryCabStringEntry
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.2.6.1
Object
row
optional
An entry containing information applicable to a particular battery string in the battery cabinet.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.2.6.1- Type
- row
- Status
- optional
- Parent
- upsBatteryCabStringTable
- Table
- upsBatteryCabStringTable
- Children
- 9
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBatteryCabStringIndex optional The battery cabinet string identifier. Battery cabinet string or halfstring
table index. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.1 |
| upsBatteryCabStringCabReference optional Reference to the global battery cabinet index where the battery string is placed. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.2 |
| upsBatteryCabStringLocalIndex optional Local battery string identification index in the actual battery cabinet (e.g. String 2 in cabinet) | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.3 |
| upsBatteryCabStringCurrent optional The current in a battery string or battery halfstring, in tenths of Amps. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.4 |
| upsBatteryCabStringAverageTemperature optional Temperature of the battery string or the average of the aggregated temperature of each
battery block/module (in tenths of degrees Celcius).
If not available, this variable is set … | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.5 |
| upsBatteryCabStringMaxTemperature optional The actual highest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius). | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.6 |
| upsBatteryCabStringMinTemperature optional The actual lowest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius). | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.7 |
| upsBatteryCabStringFuseStatus optional If the battery string has a common fuse, the status is given by this value.
1 = Fuse open
2 = Fuse OK
3 = Not present | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.2.6.1.8 |
| upsBatteryCabStringNumberOfBlocks optional The number of battery blocks/modules in a battery string.
Can be 0, if no data is available in the table of individual battery blocks/cartridges | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBatteryCabStringIndex optional The battery cabinet string identifier. Battery cabinet string or halfstring
table index. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.6.1.1 |