dcmim2ConfigLVDTrip
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.9.3.3.2.1.2
Object
column
mandatory
r/w
Integer32
LVD Trip threshold. System bus voltage at which LVD will trip (open)
during a battery backup operation.
Values are represented in thousandths of Volts (mV).
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.9.3.3.2.1.2- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- dcmim2ConfigLVDEntry
- Table
- dcmim2ConfigLVDTable
- Siblings
- 3
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dcmim2ConfigLVDIndex mandatory The index to the DC powerplant LVD. | column | Integer32 | .1.3.6.1.4.1.318.1.1.9.3.3.2.1.1 |
| dcmim2ConfigLVDReset mandatory LVD Reset threshold. System bus voltage at which LVD will reset (close)
after AC power has been restored.
Values are represented in thousandths of Volts (mV). | column | Integer32 | .1.3.6.1.4.1.318.1.1.9.3.3.2.1.3 |
| dcmim2ConfigLVDState mandatory Getting this OID will return statusClosed (1) if the LVD is closed.
statusOpened (2) will be returned if the LVD is opened. | column | Enumeration | .1.3.6.1.4.1.318.1.1.9.3.3.2.1.4 |