emsProbeStatusProbeCommStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.10
Object
column
mandatory
Enumeration
The state of communications to the probe. commNeverDiscovered(1) indicates there has never been communications with this device. commsEstablished(2) indicates communication is normal and active with this device. commsLost(3) indicates communication had been established, but is no longer.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.10.3.13.1.1.10- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- emsProbeStatusEntry
- Table
- emsProbeStatusTable
- Siblings
- 17
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | commsNeverDiscovered |
2 | commsEstablished |
3 | commsLost |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| emsProbeStatusProbeIndex mandatory The index to the probe entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.1 |
| emsProbeStatusProbeAlarmStatus mandatory The alarm status of the probe. This integer should be interpreted
as a bit map, with each bit representing the presence or absence of
the specific alarm conditions listed below. … | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.11 |
| emsProbeStatusProbeMaxTempThresh mandatory Probe maximum temperature threshold.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsiu… | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.12 |
| emsProbeStatusProbeMinTempThresh mandatory Probe minimum temperature threshold.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsiu… | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.13 |
| emsProbeStatusProbeMaxHumidityThresh mandatory Probe maximum humidity threshold.
Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.14 |
| emsProbeStatusProbeMinHumidityThresh mandatory Probe minimum humidity threshold.
Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.15 |
| emsProbeStatusProbeVoltage mandatory Probe voltage reading.
Values are displayed in tenths of Volts DC. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.16 |
| emsProbeStatusProbeMaxVoltThresh mandatory Probe maximum voltage threshold in Volts. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.17 |
| emsProbeStatusProbeMinVoltThresh mandatory Probe minimum voltage threshold in Volts. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.18 |
| emsProbeStatusProbeName mandatory The name of the probe. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.2 |
| emsProbeStatusProbeTemperature mandatory Probe temperature reading.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or Fahre… | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.3 |
| emsProbeStatusProbeHighTempThresh mandatory Probe high temperature threshold.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius o… | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.4 |
| emsProbeStatusProbeLowTempThresh mandatory Probe low temperature threshold.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the emsStatusSysTempUnits OID (Celsius or… | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.5 |
| emsProbeStatusProbeHumidity mandatory Probe humidity reading.
Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.6 |
| emsProbeStatusProbeHighHumidityThresh mandatory Probe high humidity threshold.
Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.7 |
| emsProbeStatusProbeLowHumidityThresh mandatory Probe low humidity threshold.
Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.8 |
| emsProbeStatusProbeSerialNumber mandatory A label indicating the type (Local[L] or Remote[R]) and Number
of the probe. For example, the first local probe would be L1 and
the third remote probe would be R3. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.9 |