ats5gSwitchConfigNominalFrequency

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.33.3.1.22

Object

column mandatory r/w Integer32
This is the configurable line frequency in Hertz (Hz) that will be used to select
sources. If the difference between ats5gSwitchConfigNominalFrequency and a source's
measured frequency is greater than ats5gSwitchConfigFrequencyDeviation, the ATS will
disqualify that source. The ATS will be in a 'lost redundancy' state until the source
recovers or the configuration is updated.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.33.3.1.22
Type
column
Access
readwrite
Status
mandatory
Parent
ats5gDeviceSwitchEntry

Syntax

Integer32

Values & Constraints

No enumerated values or constraints recorded.