battManStringEntry
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.16.9.2.1
Object
row
mandatory
The string to get data from.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.16.9.2.1- Type
- row
- Status
- mandatory
- Parent
- battManStringTable
- Table
- battManStringTable
- Children
- 13
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| battManStringIndex mandatory Index of string entries in the table. | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.1 |
| battManStringDischargeLess5Seconds mandatory The number of recorded discharges lasting less than
5 seconds. | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.10 |
| battManStringDischarge5to10Seconds mandatory The number of recorded discharges lasting between 5
and 10 seconds. | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.11 |
| battManStringDischarge10to60Seconds mandatory The number of recorded discharges lasting between 10
and 60 seconds. | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.12 |
| battManStringDischargeMore60Seconds mandatory The number of recorded discharges lasting more than
60 seconds (1 minute). | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.13 |
| battManStringCurrent mandatory The string current in tenths of amps. | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.2 |
| battManStringRippleCurrent mandatory The string ripple current in tenths of amps. | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.3 |
| battManStringChargerHighVoltageAlarm mandatory When set to alarm(2), indicates that the string charger has a high voltage alarm. | column | Enumeration | .1.3.6.1.4.1.318.1.1.16.9.2.1.4 |
| battManStringChargerLowVoltageAlarm mandatory When set to alarm(2), indicates that the string charger has a low voltage alarm. | column | Enumeration | .1.3.6.1.4.1.318.1.1.16.9.2.1.5 |
| battManStringCurrentProbeDisconnected mandatory When set to alarm(2), indicates that the string charger probe is disconnected. | column | Enumeration | .1.3.6.1.4.1.318.1.1.16.9.2.1.6 |
| battManStringOnBattery mandatory When set to alarm(2), indicates that the string is in the on-battery state. | column | Enumeration | .1.3.6.1.4.1.318.1.1.16.9.2.1.7 |
| battManStringHighRippleCurrent mandatory When set to alarm(2), indicates that the string has a high ripple current. | column | Enumeration | .1.3.6.1.4.1.318.1.1.16.9.2.1.8 |
| battManStringVoltage mandatory The sum of the voltages for all of the batteries on a
string in millivolts DC. | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| battManStringIndex mandatory Index of string entries in the table. | column | Integer32 | .1.3.6.1.4.1.318.1.1.16.9.2.1.1 |