dm3ConfigOutRlyAlarm
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.4
Object
column
mandatory
r/w
Enumeration
Output Relay Alarm. This setting indicates what action to perform in the event of
an output relay alarm condition;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
alarm condition.
Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
alarm condition.
Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
alarm condition.
Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
alarm condition.
Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
alarm condition.
Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
alarm condition.
Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
alarm condition.
Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
alarm condition.
Relay Alarm for Major and Minor alarms is not configurable and is always set to
alarmMajor and alarmMinor respectively.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.4- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- dm3ConfigOutRlyEntry
- Table
- dm3ConfigOutRlyTable
- Siblings
- 3
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alarmIgnore |
2 | alarmRelay1 |
3 | alarmRelay2 |
4 | alarmRelay3 |
5 | alarmRelay4 |
6 | alarmRelay5 |
7 | alarmRelay6 |
8 | alarmMinor |
9 | alarmMajor |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dm3ConfigOutRlyIndex mandatory The index to the DC powerplant output relay. | column | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.1 |
| dm3ConfigOutRlyName mandatory The name of the output relay. The maximum value is 16 characters. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.2 |
| dm3ConfigOutRlyDelay mandatory Output Relay Delay. This OID represents the time delay from the initiation of an
output relay action to when the output relay action does occur. If the alarm condition
disappear… | column | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.3 |