sPDUOutletConfigMSPgsLowBattMult

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.6.6.2.1.1.8

Object

column mandatory r/w Integer32
Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID is
set to -1 (On Runtime Remaining).
              
Allows you to set the value to stagger the shutdown sequence of the outlets.
1 provides the longest delay (the outlet to shutoff first), and 7 would
provide the shortest delay (the outlet to shut off last).
              
Allowed values are:
1 - 7.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.8
Type
column
Access
readwrite
Status
mandatory
Parent
sPDUOutletConfigMSPgsEntry
Table
sPDUOutletConfigMSPgsTable
Siblings
12

Syntax

Integer32

Values & Constraints

Object Constraints
range: 1-7

Related Objects

Sibling Objects