sPDUMasterControlMSPCommand
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.6.2.2.1.3
Object
column
mandatory
r/w
Enumeration
Setting this OID to immediateAllOnMSP (2) will turn all outlets
on immediately.
Setting this OID to sequencedAllOnMSP (3) will turn all outlets
on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value.
Setting this OID to immediateAllOffMSP (4) will turn all outlets
off immediately.
Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets
(after the device running PowerChute confirms shutdown) as defined
by each outlet's sPDUOutletConfigMSPRebootDuration OID time value.
Setting this OID to immediateAllRebootMSP (6) will reboot all outlets
immediately.
Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets
(after the device running PowerChute confirms shutdown) as defined
by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each
outlet will then turn on after the sum of its
sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID
values.
Setting this OID to overrideAllBatCapThreshMSP (8) will cause the
outlet to ignore the Battery Capacity Threshold and proceed turning on
the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay
OID value.
Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending
commands on the MasterSwitch plus to be canceled.
Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of
the MasterSwitch plus to be restored to the factory defaults.
Getting this OID will return the noCommandAllMSP (1) value.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.6.2.2.1.3- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- sPDUMasterControlMSPEntry
- Table
- sPDUMasterControlMSPTable
- Siblings
- 2
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noCommandAllMSP |
2 | immediateAllOnMSP |
3 | sequencedAllOnMSP |
4 | immediateAllOffMSP |
5 | gracefulAllRebootMSP |
6 | immediateAllRebootMSP |
7 | gracefulAllShutdownMSP |
8 | overrideAllBatCapThreshMSP |
9 | cancelAllPendingCommandsMSP |
10 | restoreFactoryDefaultsMSP |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| sPDUMasterControlMSPIndex mandatory The index to the MasterSwitch plus entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.6.2.2.1.1 |
| sPDUMasterControlMSPName mandatory The name of the MasterSwitch plus. The maximum
value is 23 characters. The name is set by
using the sPDUMasterConfigMSPName OID. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.2.2.1.2 |