rPDUOutletConfigPowerOffTime

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.12.3.4.1.1.5

Object

column mandatory r/w Integer32
The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.
              
Allowed values are:
              
-1        - never power off.
0         - power off immediately.
1 to 7200 - power off up to 7200 seconds after being
           commanded.

Context