upsHighPrecBatteryPackOnlyStatus

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5

Object

column mandatory OctetString
The battery status for the pack only.
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
bit 12 VoltageSenseError
bit 13 IncompatiblePack

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5
Type
column
Access
readonly
Status
mandatory
Parent
upsHighPrecBatteryPackOnlyEntry
Table
upsHighPrecBatteryPackOnlyTable
Siblings
9

Syntax

OctetString

Values & Constraints

No enumerated values or constraints recorded.

Related Objects