sPDUOutletConfigMSPgsLowBattWarning

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.6.6.2.1.1.7

Object

column mandatory r/w Integer32
The amount of delay, in 6 second intervals, between
when the UPS goes on battery and the power down sequence for
the outlet is initiated.
              
Allowed values are:
              
-2 - Never initiate the power down sequence on low battery warning.
-1 - Initiate power down sequence based on remaining runtime.
1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs).
0 indicates to immediately initiate power down sequence on low
 battery warning.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.7
Type
column
Access
readwrite
Status
mandatory
Parent
sPDUOutletConfigMSPgsEntry
Table
sPDUOutletConfigMSPgsTable
Siblings
12

Syntax

Integer32

Values & Constraints

Object Constraints
range: -2-9999

Related Objects

Sibling Objects