sPDUOutletConfigMSPgsLowBattWarning
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.7
Object
column
mandatory
r/w
Integer32
The amount of delay, in 6 second intervals, between
when the UPS goes on battery and the power down sequence for
the outlet is initiated.
Allowed values are:
-2 - Never initiate the power down sequence on low battery warning.
-1 - Initiate power down sequence based on remaining runtime.
1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs).
0 indicates to immediately initiate power down sequence on low
battery warning.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.7- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- sPDUOutletConfigMSPgsEntry
Syntax
Integer32
Values & Constraints
Object Constraints
range: -2-9999