uioSensorConfigMinHumidityThreshold
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.25.1.4.1.14
Object
column
mandatory
r/w
Integer32
The minimum (critical) humidity alarm threshold for the probe in percent relative humidity. Must be lower than the low threshold to ensure proper sensor alarm behavior. -1 if the sensor doesn't read humidity.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.25.1.4.1.14- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- uioSensorConfigEntry
- Table
- uioSensorConfigTable
- Siblings
- 21
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| uioSensorConfigPortID mandatory The ID of the port to which the sensor is attached. | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.1 |
| uioSensorConfigMinTemperatureEnable mandatory The minimum temperature alarm enable/disable for the sensor.
1 - disabled
2 - enabled | column | Enumeration | .1.3.6.1.4.1.318.1.1.25.1.4.1.10 |
| uioSensorConfigLowTemperatureEnable mandatory The low temperature alarm enable/disable for the sensor.
1 - disabled
2 - enabled | column | Enumeration | .1.3.6.1.4.1.318.1.1.25.1.4.1.11 |
| uioSensorConfigHighTemperatureEnable mandatory The high temperature alarm enable/disable for the sensor.
1 - disabled
2 - enabled | column | Enumeration | .1.3.6.1.4.1.318.1.1.25.1.4.1.12 |
| uioSensorConfigMaxTemperatureEnable mandatory The maximum temperature alarm enable/disable for the sensor.
1 - disabled
2 - enabled | column | Enumeration | .1.3.6.1.4.1.318.1.1.25.1.4.1.13 |
| uioSensorConfigLowHumidityThreshold mandatory The low (warning) humidity alarm threshold for the probe in
percent relative humidity. Must be higher than the minimum
threshold and lower than the high threshold to ensure proper… | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.15 |
| uioSensorConfigHighHumidityThreshold mandatory The high (warning) humidity alarm threshold for the probe in
percent relative humidity. Must be lower than the maximum
threshold and higher than the low threshold to ensure proper… | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.16 |
| uioSensorConfigMaxHumidityThreshold mandatory The maximum (critical) humidity alarm threshold for the
probe in percent relative humidity. Must be higher than the
high threshold to ensure proper sensor alarm behavior. -1 if
th… | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.17 |
| uioSensorConfigHumidityHysteresis mandatory The number of percent relative humidity beyond the humidity
thresholds at which an active humidity alarm will be cleared.
This value applies to all humidity thresholds. -1 if the
… | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.18 |
| uioSensorConfigMinHumidityEnable mandatory The minimum humidity alarm enable/disable for the sensor.
1 - disabled (always set if the sensor doesn't read humidity)
2 - enabled | column | Enumeration | .1.3.6.1.4.1.318.1.1.25.1.4.1.19 |
| uioSensorConfigSensorID mandatory The ID of the sensor. | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.2 |
| uioSensorConfigLowHumidityEnable mandatory The low humidity alarm enable/disable for the sensor.
1 - disabled (always set if the sensor doesn't read humidity)
2 - enabled | column | Enumeration | .1.3.6.1.4.1.318.1.1.25.1.4.1.20 |
| uioSensorConfigHighHumidityEnable mandatory The high humidity alarm enable/disable for the sensor.
1 - disabled (always set if the sensor doesn't read humidity)
2 - enabled | column | Enumeration | .1.3.6.1.4.1.318.1.1.25.1.4.1.21 |
| uioSensorConfigMaxHumidityEnable mandatory The maximum humidity alarm enable/disable for the sensor.
1 - disabled (always set if the sensor doesn't read humidity)
2 - enabled | column | Enumeration | .1.3.6.1.4.1.318.1.1.25.1.4.1.22 |
| uioSensorConfigSensorName mandatory The sensor name. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.1.4.1.3 |
| uioSensorConfigSensorLocation mandatory The location of the sensor. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.1.4.1.4 |
| uioSensorConfigMinTemperatureThreshold mandatory The minimum (critical) temperature alarm threshold for the
probe in degrees C. Must be lower than the low threshold to
ensure proper sensor alarm behavior. | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.5 |
| uioSensorConfigLowTemperatureThreshold mandatory The low (warning) temperature alarm threshold for the probe
in degrees C. Must be higher than the minimum threshold and
lower than the high threshold to ensure proper sensor alarm… | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.6 |
| uioSensorConfigHighTemperatureThreshold mandatory The high (warning) temperature alarm threshold for the probe
in degrees C. Must be lower than the maximum threshold and
higher than the low threshold to ensure proper sensor alarm… | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.7 |
| uioSensorConfigMaxTemperatureThreshold mandatory The maximum (critical) temperature alarm threshold for the
probe in degrees C. Must be higher than the high threshold
to ensure proper sensor alarm behavior. | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.8 |
| uioSensorConfigTemperatureHysteresis mandatory The number of degrees C beyond the temperature thresholds at
which an active temperature alarm will be cleared. This value
applies to all temperature thresholds. | column | Integer32 | .1.3.6.1.4.1.318.1.1.25.1.4.1.9 |