wirelessSensorStatusAlarmStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.23
Object
column
mandatory
Integer32
The alarm status of the wireless sensor. This integer should be interpreted
as a bit map, with each bit representing the presence or absence of
the specific alarm conditions listed below. The bit will be '1' if
the condition is present, and '0' if the condition is not present.
Bit Hex. Value Description
1 0x0001 Maximum temperature exceeded.
2 0x0002 High temperature exceeded.
3 0x0004 Low temperature exceeded.
4 0x0008 Minimum temperature exceeded.
5 0x0010 Maximum humidity exceeded.
6 0x0020 High humidity exceeded.
7 0x0040 Low humidity exceeded.
8 0x0080 Minimum humidity exceeded.
9 0x0100 Low battery exceeded.
10 0x0200 Minimum battery exceeded.
11 0x0400 Low signal strength exceeded.
12 0x0800 Minimum signal strength exceeded.
13 0x1000 Sensor inactive.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.10.5.1.1.1.23- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- wirelessSensorStatusEntry
- Table
- wirelessSensorStatusTable
- Siblings
- 22
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| wirelessSensorStatusIndex mandatory The index to the sensor entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.1 |
| wirelessSensorStatusLowHumidityThresh mandatory Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.10 |
| wirelessSensorStatusCommStatus mandatory The communication status of the wireless sensor.
inactive(0) indicates sensor is in the wireless network but not sending information.
active(1) indicates wireless sensor is live a… | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.11 |
| wirelessSensorStatusMaxTempThresh mandatory Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.12 |
| wirelessSensorStatusMinTempThresh mandatory Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.13 |
| wirelessSensorStatusMaxHumidityThresh mandatory Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.14 |
| wirelessSensorStatusMinHumidityThresh mandatory Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.15 |
| wirelessSensorStatusBattery mandatory Values are displayed in tenths of Volts DC. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.16 |
| wirelessSensorStatusLowBatteryThresh mandatory Values are displayed in tenths of Volts DC. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.17 |
| wirelessSensorStatusMinBatteryThresh mandatory Values are displayed in tenths of Volts DC. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.18 |
| wirelessSensorStatusRssi mandatory Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.19 |
| wirelessSensorStatusExtAddr mandatory The extended address is the combination of the unique 10 byte
MAC address of the sensor concatenated with its short address. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.2 |
| wirelessSensorStatusLowRssiThresh mandatory Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.20 |
| wirelessSensorStatusMinRssiThresh mandatory Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.21 |
| wirelessSensorStatusLocation mandatory A user-defined string identifying the location
of the wireless sensor. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.22 |
| wirelessSensorStatusName mandatory The name of the wireless sensor. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.3 |
| wirelessSensorStatusAlarmGeneration mandatory Indicates whether alarm generation is enabled or disabled for the sensor. | column | Enumeration | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.4 |
| wirelessSensorStatusTemperature mandatory The current temperature are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.5 |
| wirelessSensorStatusHighTempThresh mandatory Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.6 |
| wirelessSensorStatusLowTempThresh mandatory Values are displayed in tenths of degrees in the scale
shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.7 |
| wirelessSensorStatusHumidity mandatory Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.8 |
| wirelessSensorStatusHighHumidityThresh mandatory Values are represented in whole number percentage. | column | Integer32 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.9 |