upsIntegratedATSSourceStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.16.5.1.3
Object
column
mandatory
Enumeration
Getting this variable will return the input source status.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.16.5.1.3- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsIntegratedATSSourceEntry
- Table
- upsIntegratedATSSourceTable
- Siblings
- 4
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | upsIntegratedATSSourceGood |
2 | upsIntegratedATSSourceBad |
3 | upsIntegratedATSSourceUnknown |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsIntegratedATSSourceIndex mandatory The index to the input source entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.16.5.1.1 |
| upsIntegratedATSSourceName mandatory The name of the input source. This OID is provided
for informational purposes only. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.16.5.1.2 |
| upsIntegratedATSLineFailDelay mandatory The delay between a selected input source becoming bad, and the ATS switching away from that source.
This delay is used to make sure that the line has truly failed before the ATS … | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.16.5.1.4 |
| upsIntegratedATSLineStabilityDelay mandatory The delay between an unselected input source becoming good, and the ATS switching to that source.
This delay is used to make sure that the line has truly returned before the ATS w… | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.16.5.1.5 |