upsDiagBatteryHealth
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.11
Object
column
mandatory
OctetString
The battery health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement module bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement module bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement module bit 6 Battery measured lifetime near end acknowledged, order replacement module
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.11- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsDiagBatteryEntry
- Table
- upsDiagBatteryTable
- Siblings
- 10
Syntax
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsDiagBatteryFrameIndex mandatory The index to the battery frame entry.
Frame 0 indicates the Main frame. Extended Run (XR) frames
start from index 1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.1 |
| upsDiagBatterySKU mandatory The SKU of the battery. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.10 |
| upsDiagBatteryIndex mandatory The index to the battery entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.2 |
| upsDiagBatteryStatus mandatory The status of the battery.
unknown(1) indicates the device status is unknown.
notInstalled(2) indicates the device is not installed.
ok(3) indicates the battery status is OK.
fail… | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.3 |
| upsDiagBatterySerialNumber mandatory The serial number of the battery. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.4 |
| upsDiagBatteryFirmwareRev mandatory The firmware revision of the battery. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.5 |
| upsDiagBatteryManufactureDate mandatory The manufacture date of the battery. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.6 |
| upsDiagBatteryType mandatory The battery type or rating for the battery. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.7 |
| upsDiagBatteryFramePresent mandatory The battery frame/cabinet status.
0 indicates frame/cabinet is not present.
1 indicates frame/cabinet is present. | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.8 |
| upsDiagBatteryFrameTemperature mandatory The battery frame/cabinet temperature in tenths of degrees celsius.
If the frame/cabinet is not present, this variable is set to (-1). | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.9 |