upsDiagPMLifetimeInfoEntry
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.13.2.3.1
Object
row
mandatory
The diagnostics of a Power Module lifetime information.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.13.2.3.1- Type
- row
- Status
- mandatory
- Parent
- upsDiagPMLifetimeInfoTable
- Table
- upsDiagPMLifetimeInfoTable
- Children
- 7
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsDiagPMLifetimeInfoIndex mandatory The index to the Power Module lifetime information entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.1 |
| upsDiagPMLifetimeStatus mandatory The status of the Power Module lifetime information.
ok(1) indicates the device lifetime status is OK.
nearEnd(2) indicates the device lifetime status is near end.
exceeded(3) ind… | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.2 |
| upsDiagPMEstmtdLifetimeRmng mandatory Displays the time remaining for the module before it should be replaced.
Measured in months. This value is set when you originally install the module. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.3 |
| upsDiagPMEstmtdLifetimeRmngPct mandatory Displays the percentage of the total lifetime remaining for the module
before it should be replaced. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.4 |
| upsDiagPMFanLifetimeStatus mandatory The status of the Power Module Fan lifetime information.
ok(1) indicates the device lifetime status is OK.
nearEnd(2) indicates the device lifetime status is near end.
exceeded(3)… | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.5 |
| upsDiagPMFanEstmtdLifetimeRmng mandatory Displays the time remaining, measured in months, before the module's
fan should be replaced. It is reset by the field service engineer when
a new fan is installed. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.6 |
| upsDiagPMFanEstmtdLifetimeRmngPct mandatory Displays the percentage of the total lifetime remaining
before the module's fan should be replaced. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.7 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsDiagPMLifetimeInfoIndex mandatory The index to the Power Module lifetime information entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.1 |