upsDCOutputStatusAbnormalConditions
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.17.1.2.1.6
Object
An ASCII string containing flags representing active
output faults. If the Network Card is unable to determine
the state of the faults, this variable is set to 'UNKNOWN'.
The flags are numbered 1 onward, read from left to
right. The flags are defined as follows starting from 1:
Flag 1: Output Overload
Flag 2: Output Short Circuit
Flag 3: Output Over Voltage
Flag 4: <Not Used>
Flag 5: Overtemperature
Flag 6: Backfeed Relay Fault
Flag 7: <Not Used>
Flag 8: PFC Input Relay Fault
Flag 9: <Not Used>
Flag 10: Bypass Relay Fault
Flag 11: <Not Used>
Flag 12: <Not Used>
Flag 13: <Not Used>
Flag 14: <Not Used>
Flag 15: <Not Used>
Flag 16: <Not Used>
Flag 17: <Not Used>
Flag 18: <Not Used>
Flag 19: Output Fault (over or undervoltage)
Flag 20: Bus Converter Fault
Flag 21: Sensor Fault
Flag 21: <Not Used>
Flag 22: <Not Used>
Flag 23: <Not Used>
Flag 24: <Not Used>
Flag 25: <Not Used>
Flag 26: <Not Used>
Flag 27: <Not Used>
Flag 28: <Not Used>
Flag 29: <Not Used>
Flag 30: <Not Used>
Flag 31: <Not Used>
Flag 32: <Not Used>
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.17.1.2.1.6- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsDCOutputStatusEntry
- Table
- upsDCOutputStatusTable
- Siblings
- 5
Syntax
RFC1213-MIBDisplayString
- Source
- RFC1213-MIBDisplayString
- Base type
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsDCOutputStatusTableIndex mandatory The index to the DC output status entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.1 |
| upsDCOutputStatusVoltageNominal mandatory The desired voltage for this output in tenths of VDC.
When the output is on and there are no fault conditions,
the actual voltage should be near the nominal.
If not supported, ret… | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.2 |
| upsDCOutputStatusCurrentRating mandatory The amount of current this output is able to supply in
tenths of amperes.
If not supported, return -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.3 |
| upsDCOutputStatusVoltage mandatory The voltage measured on this output in tenths of VDC.
If not supported, return -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.4 |
| upsDCOutputStatusCurrent mandatory The current drawn by the load measured on this output
in tenths of amperes.
If not supported, return -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.5 |