rPDU2BankPropertiesPhaseLayout

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.26.8.2.1.4

Object

column mandatory Rpdu2OutletPhaseLayoutType
This OID describes the outlet phase connections on
the referenced bank as follows:
              
seqPhase1ToNeutral(1) indicates that bank outlets are
wired from Phase 1 to Neutral.
              
seqPhase2ToNeutral(2) indicates that bank outlets are
wired from Phase 2 to Neutral.
              
seqPhase3ToNeutral(3) indicates that bank outlets are
wired from Phase 3 to Neutral.
              
seqPhase1ToPhase2(4) indicates that bank outlets are
wired from Phase 1 to Phase 2.
              
seqPhase2ToPhase3(5) indicates that bank outlets are
wired from Phase 2 to Phase 3.
              
seqPhase3ToPhase1(6) indicates that bank outlets are
wired from Phase 3 to Phase 1.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.26.8.2.1.4
Type
column
Access
readonly
Status
mandatory
Parent
rPDU2BankPropertiesEntry
Table
rPDU2BankPropertiesTable
Siblings
4

Syntax

Rpdu2OutletPhaseLayoutType
Source
Rpdu2OutletPhaseLayoutType
Base type
Enumeration

Values & Constraints

Type Values
1seqPhase1ToNeutral
2seqPhase2ToNeutral
3seqPhase3ToNeutral
4seqPhase1ToPhase2
5seqPhase2ToPhase3
6seqPhase3ToPhase1

Related Objects

Sibling Objects