rARUConfigAruRemoteSetpoint
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.14.2.1.1.3
Object
column
mandatory
r/w
Enumeration
This OID defines the desired base airflow of the ARU, and sets the
speed of the ARU fans when the temperature override is inactive.
Values specified in cfm (cubic feet per minute) can be converted
to metric values using the conversion factor:
1 cfm = 1.70 m^3/hr (cubic meters per hour).
Values (1) through (9) are for support of legacy (1st generation) ARUs.
Writing these values to a 2nd generation ARU will result in the following:
A value greater than (9) will be ignored by a 1st generation ARU.
aruOff (1) - Ignored
aru85F-29C (2) - 1200 cfm
aru90F-32C (3) - 800 cfm
aru95F-35C (4) - 500 cfm
aru100F-38C (5) - 400 cfm
aru7kW (6) - 1200 cfm
aru5kW (7) - 800 cfm
aru3kW (8) - 500 cfm
aru2kW (9) - 400 cfm
NOTE: -1 will be returned if the ARU is not communicating.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.14.2.1.1.3- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- rARUConfigEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | aruOff |
2 | aru85F-29C |
3 | aru90F-32C |
4 | aru95F-35C |
5 | aru100F-38C |
6 | aru7kW-1200cfm |
7 | aru5kW-800cfm |
8 | aru3kW-500cfm |
9 | aru2kW-300cfm |
10 | aru400cfm |
11 | aru600cfm |
12 | aru700cfm |
13 | aru900cfm |
14 | aru1000cfm |
15 | aru1400cfm |
16 | aru1600cfm |
17 | aru1800cfm |
18 | aru2000cfm |