rARUConfigAruRemoteSetpoint

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.14.2.1.1.3

Object

column mandatory r/w Enumeration
This OID defines the desired base airflow of the ARU, and sets the
speed of the ARU fans when the temperature override is inactive.
              
Values specified in cfm (cubic feet per minute) can be converted
to metric values using the conversion factor:
              
   1 cfm = 1.70 m^3/hr (cubic meters per hour).
              
Values (1) through (9) are for support of legacy (1st generation) ARUs.
Writing these values to a 2nd generation ARU will result in the following:
A value greater than (9) will be ignored by a 1st generation ARU.
              
   aruOff      (1) - Ignored
   aru85F-29C  (2) - 1200 cfm
   aru90F-32C  (3) - 800 cfm
   aru95F-35C  (4) - 500 cfm
   aru100F-38C (5) - 400 cfm
   aru7kW      (6) - 1200 cfm
   aru5kW      (7) - 800 cfm
   aru3kW      (8) - 500 cfm
   aru2kW      (9) - 400 cfm
              
NOTE: -1 will be returned if the ARU is not communicating.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.14.2.1.1.3
Type
column
Access
readwrite
Status
mandatory
Parent
rARUConfigEntry
Table
rARUConfigTable
Siblings
5

Syntax

Enumeration

Values & Constraints

Enumerated Values
1aruOff
2aru85F-29C
3aru90F-32C
4aru95F-35C
5aru100F-38C
6aru7kW-1200cfm
7aru5kW-800cfm
8aru3kW-500cfm
9aru2kW-300cfm
10aru400cfm
11aru600cfm
12aru700cfm
13aru900cfm
14aru1000cfm
15aru1400cfm
16aru1600cfm
17aru1800cfm
18aru2000cfm