airFMModBlwr1ElOvTimeConst
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.18
Object
column
mandatory
Integer32
The delay between the current exceeding the overload threshold and the activation of the electronic overload relay. Measured in tenths of minutes. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.18- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- airFMModBlwr1Entry
- Table
- airFMModBlwr1Table
- Siblings
- 24
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| airFMModBlwr1ModuleIndex mandatory The index of the module. | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.1 |
| airFMModBlwr1Vlt mandatory The voltage supplied to the blower motor. Measured
in tenths of volts RMS.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration. | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.10 |
| airFMModBlwr1DCLinkVlt mandatory The voltage of the blower controller's DC bus.
Measured in volts DC.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration. | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.11 |
| airFMModBlwr1AccTime mandatory The time to accelerate the blower to the specified
frequency. Measured in tenths of seconds.
A value of -2147483648 indicates that this OID does
not apply to this device due to i… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.12 |
| airFMModBlwr1DecTime mandatory The time to decelerate the blower frequency to zero.
Measured in tenths of seconds.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configu… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.13 |
| airFMModBlwr1CapLife mandatory The remaining life of the main circuit capacitor.
Measured in tenths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configurat… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.14 |
| airFMModBlwr1CtrlCoolFanLife mandatory The total operation time of the blower controller
cooling fan. Measured in hours.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configur… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.15 |
| airFMModBlwr1ElOvMode mandatory Enables or disables the electronic overload relay.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration. | column | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.16 |
| airFMModBlwr1ElOvSetting mandatory The electronic overload relay is activated when the
current exceeds this threshold. Measured in
hundredths of amps.
A value of -2147483648 indicates that this OID does
not apply … | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.17 |
| airFMModBlwr1FanPower mandatory The actual power of the blower motor. Measured in
tenths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration. | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.19 |
| airFMModBlwr1CtrlType mandatory The type of blower controller.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration. | column | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.2 |
| airFMModBlwr1HeatsinkTempC mandatory The temperature of the heatsink on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its con… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.20 |
| airFMModBlwr1HeatsinkTempF mandatory The temperature of the heatsink on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its … | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.21 |
| airFMModBlwr1ChokeTempC mandatory The temperature of the choke on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its config… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.22 |
| airFMModBlwr1ChokeTempF mandatory The temperature of the choke on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its con… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.23 |
| airFMModBlwr1InverterTempC mandatory The temperature of the inverter on the blower
controller. Measured in degrees Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its con… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.24 |
| airFMModBlwr1InverterTempF mandatory The temperature of the inverter on the blower
controller. Measured in degrees Fahrenheit.
A value of -2147483648 indicates that this OID does
not apply to this device due to its … | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.25 |
| airFMModBlwr1CmdFreq mandatory The requested operating frequency for the blower.
Measured in tenths of hertz.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuratio… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.3 |
| airFMModBlwr1ActFreq mandatory The frequency at which the blower controller is
operating. Measured in tenths of hertz.
A value of -2147483648 indicates that this OID does
not apply to this device due to its co… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.4 |
| airFMModBlwr1Poles mandatory The number of poles of the blower motor that the
blower controller is controlling.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configur… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.5 |
| airFMModBlwr1RatedHorsePower mandatory The power rating of the blower motor. Measured in
hundredths of horsepower.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration. | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.6 |
| airFMModBlwr1RatedCurrent mandatory The current rating of the blower motor. Measured in
hundredths of amps.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration. | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.7 |
| airFMModBlwr1ActTorq mandatory The actual torque of the blower motor. Measured in
hundredths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration. | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.8 |
| airFMModBlwr1Current mandatory The percent of rated current drawn by the blower
motor. Measured in hundredths of percent.
A value of -2147483648 indicates that this OID does
not apply to this device due to its… | column | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.9 |