switchgearBreakerType
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.4
Object
column
mandatory
Enumeration
Indicates the switchgear breaker types available in the UPS system. If the UPS is unable to find any attached breakers, this variable is set to unknown(1). If the system has multiple breakers of the same type (e.g. multiple battery breakers) the status shown in OID switchgearBreakerStatus will be the aggregated status.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.4- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsDiagSwitchGearBreakerEntry
- Table
- upsDiagSwitchGearBreakerTable
- Siblings
- 4
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | unknown |
2 | unitInputBreaker |
3 | staticSwitchInputBreaker |
4 | maintenanceBypassBreaker |
5 | unitOutputBreaker |
6 | systemIsolationBreaker |
7 | batteryBreaker |
8 | bypassBackFeedBreaker |
9 | internalMaintenanceBypassBreaker |
10 | redundantInternalMaintenanceBypassBreaker |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| switchgearBreakerIndex mandatory The index of the switchgear breaker. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.1 |
| switchgearBreakerPresent mandatory Indicates if the switchgear breaker is present.
notPresent(1) indicates that the breaker is not present.
present(2) indicates that the breaker is present. | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.2 |
| switchgearBreakerName mandatory The name of the switchgear breaker. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.3 |
| switchgearBreakerStatus mandatory The status of switchgear breaker.
unknown(1) indicates the breaker status is unknown.
opened (2) indicates the breaker is opened.
closed (3) indicates the breaker is closed.
NOTE:… | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.5 |