sPDUOutletPowerOnTime

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.4.5.2.1.2

Object

column mandatory r/w Integer32
The amount of time (in seconds) the outlet will delay
powering on when the MasterSwitch is powered on.
              
Allowed values are:
              
-1 never power on automatically.
0  power on with the Master Switch.
15 power on 15 seconds after the MasterSwitch has power applied.
30 power on 30 seconds after the MasterSwitch has power applied.
45 power on 45 seconds after the MasterSwitch has power applied.
60 power on 60 seconds (1 minute) after the MasterSwitch has power applied.
120 power on 120 seconds (2 minutes) after the MasterSwitch has power applied.
300 power on 300 seconds (5 minutes) after the MasterSwitch has power applied.
              
If a value other than a supported value is provided in a
set request, the PDU interprets it as the next lower
acceptable value.  If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.