rPDUOutletConfigOutletName
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.2
Object
The name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.12.3.4.1.1.2- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- rPDUOutletConfigEntry
- Table
- rPDUOutletConfigTable
- Siblings
- 6
Syntax
RFC1213-MIBDisplayString
- Source
- RFC1213-MIBDisplayString
- Base type
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDUOutletConfigIndex mandatory The index to the outlet entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.1 |
| rPDUOutletConfigOutletPhase mandatory The phase/s associated with this outlet.
For single phase devices, this object will always
return phase1(1).
For 3-phase devices, this object will re… | column | Enumeration | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.3 |
| rPDUOutletConfigPowerOnTime mandatory The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.
Allowed values are:
… | column | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.4 |
| rPDUOutletConfigPowerOffTime mandatory The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.
Allowed values are:
-1 … | column | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.5 |
| rPDUOutletConfigRebootDuration mandatory During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence,… | column | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.6 |
| rPDUOutletConfigOutletBank mandatory The bank associated with this outlet. | column | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.7 |