subfeedBreakerStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.6
Object
column
mandatory
Enumeration
The status of the Circuit Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed(4) indicates the circuit breaker is closed.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.6- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsDiagSubFeedBreakerEntry
- Table
- upsDiagSubFeedBreakerTable
- Siblings
- 7
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | unknown |
2 | notInstalled |
3 | opened |
4 | closed |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| subfeedBreakerIndex mandatory The index of the subfeed breakers. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.1 |
| subfeedBreakerPresent mandatory Indicates if the subfeed breaker is present.
notPresent (1) indicates that the breaker is not present.
present (2) indicates that the breaker is present. | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.2 |
| subfeedBreakerRating mandatory The current rating of the installed subfeed breaker. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.3 |
| subfeedBreakerUpperAcceptPowerWarning mandatory The maximum acceptable load before warning is issued.
Expressed as percent of the subfeed breaker rating. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.4 |
| subfeedBreakerUpperAcceptPowerCritical mandatory The maximum load before a critical alarm occurs.
Expressed as percent of the subfeed breaker rating. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.5 |
| subfeedBreakerName mandatory The name of the subfeed breaker. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.7 |
| subfeedBreakerCurrent mandatory The subfeed current in tenths of Amps. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.8 |