atsConfigBankNearOverLoadThreshold
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.8.4.14.1.4
Object
column
mandatory
r/w
Integer32
A threshold that indicates the current drawn is nearing
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than
or equal to the threshold value.
Minimum value must be greater than the value returned by
the atsConfigBankLowLoadThreshold OID.
Maximum value must be less than or equal to the value
returned by the atsConfigBankOverLoadThreshold OID.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.8.4.14.1.4- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- atsConfigBankEntry
- Table
- atsConfigBankTable
- Siblings
- 4
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| atsConfigBankTableIndex mandatory An index to the bank table entry. | column | Integer32 | .1.3.6.1.4.1.318.1.1.8.4.14.1.1 |
| atsConfigBank mandatory The bank number of an ATS | column | Enumeration | .1.3.6.1.4.1.318.1.1.8.4.14.1.2 |
| atsConfigBankLowLoadThreshold mandatory A threshold that indicates the current drawn is nearing
a low consumption condition. It is represented in Amps.
A warning will be issued when the load is less than the
threshold v… | column | Integer32 | .1.3.6.1.4.1.318.1.1.8.4.14.1.3 |
| atsConfigBankOverLoadThreshold mandatory A threshold that indicates the current drawn has entered
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than or
equal to the t… | column | Integer32 | .1.3.6.1.4.1.318.1.1.8.4.14.1.5 |