pmmBranchCircuitLowCurrentThreshold

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.28.3.3.3.1.16

Object

column mandatory r/w Integer32
Threshold below which a branch circuit low current
condition will be generated.
Specified as a percentage of the branch breaker rating
represented in the OID pmmBranchCircuitBreakerRating
A value of zero indicates that the threshold is disabled.
Threshold write returns as unsuccessful if one of the breaker threshold 
groups does not meet conditions. In this case, read the thresholds 
to know which threshold group's write condition is not met.
Threshold needs to be enabled to read value

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.28.3.3.3.1.16
Type
column
Access
readwrite
Status
mandatory
Parent
pmmBranchBreakerEntry
Table
pmmBranchBreakerTable
Siblings
40

Syntax

Integer32

Values & Constraints

Object Constraints
range: 0-100

Related Objects

Sibling Objects