rPDUOutletStatusIndex
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.1
Object
column
mandatory
Integer32
The index to the outlet entry.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.12.3.5.1.1.1- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDUOutletStatusEntry
- Table
- rPDUOutletStatusTable
- Siblings
- 6
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDUOutletStatusOutletName mandatory The name of the outlet. The maximum string size is device dependent.
This OID is provided for informational purposes only. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.2 |
| rPDUOutletStatusOutletPhase mandatory The phase/s associated with this outlet.
For single phase devices, this object will always
return phase1(1).
For 3-phase devices, this object will re… | column | Enumeration | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.3 |
| rPDUOutletStatusOutletState mandatory Getting this variable will return the outlet state. If
the outlet is on, the outletStatusOn (1) value will be returned.
If the outlet is off, the outletStatusOff (2) value will be… | column | Enumeration | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.4 |
| rPDUOutletStatusCommandPending mandatory Getting this variable will return the command pending
state of the outlet. If a command is pending on the
outlet, the outletStatusCommandPending (1) value
will be returned. If the… | column | Enumeration | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.5 |
| rPDUOutletStatusOutletBank mandatory The bank associated with this outlet. | column | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.6 |
| rPDUOutletStatusLoad mandatory Getting this OID will return the measured Outlet load for
an Outlet Monitored Rack PDU in tenths of Amps. For other
models this OID is not supported. | column | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.7 |