pmmInputPhaseEntry
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.28.3.1.3.1
Object
row
mandatory
An entry containing information applicable to a particular input phase.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.28.3.1.3.1- Type
- row
- Status
- mandatory
- Parent
- pmmInputPhaseTable
- Table
- pmmInputPhaseTable
- Children
- 13
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pmmInputMeterNum mandatory The input meter identifier. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.1 |
| pmmInputPhaseAngle mandatory Current phase Angle. Measured in tenths of decimal
Returns -255 if unsupported | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.10 |
| pmmInputTHDLtoL mandatory Input harmonic distortions line to line for the present input voltage.
Measured in tenths. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.11 |
| pmmInputTHDLtoN mandatory Input harmonic distortions line to neutral for the present input voltage.
Measured in tenths. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.12 |
| pmmInputCurrentTHD mandatory Input harmonic distortions for each phase, for the present input current.
Returns -1 if unsupported or failed.
Specified in tenths. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.13 |
| pmmInputPhase mandatory Input phase index. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.2 |
| pmmInputVoltageLtoL mandatory Line-to-line input voltage available.
Measured in tenths of Volts. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.3 |
| pmmInputVoltageLtoN mandatory Line-to-neutral input voltage available.
Measured in tenths of Volts. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.4 |
| pmmInputPhaseCurrent mandatory Input current per phase. Measured in tenths of Amps. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.5 |
| pmmInputActivePower mandatory Input active power per phase. Measured in tenths of kW. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.6 |
| pmmInputApparentPower mandatory Input apparent power per phase. Measured in tenths of kVA. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.7 |
| pmmInputPowerFactor mandatory Indicates the power factor of the input per phase.
A value of 100 representing a unity power factor (1.00).
Specified in hundredths. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.8 |
| pmmInputMaxInstantaneousCurrent mandatory Input maximum phase instantaneous current. Measured in tenths of Amps. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| pmmInputMeterNum mandatory The input meter identifier. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.1 |
| pmmInputPhase mandatory Input phase index. | column | Integer32 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.2 |