upsBatteryCabBlockEntry
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.2.7.1
Object
row
optional
An entry containing information applicable to a particular battery block in the battery cabinet.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.2.7.1- Type
- row
- Status
- optional
- Parent
- upsBatteryCabBlockTable
- Table
- upsBatteryCabBlockTable
- Children
- 11
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBatteryCabBlockIndex optional The battery cabinet block identifier. Global battery cabinet block
table index. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.1 |
| upsBatteryCabBlockVerticalPosition optional The vertical position of the battery block/module in the actual battery cabinet
(e.g. 4, if it is the 4th shelf counting from the bottom) | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.10 |
| upsBatteryCabBlockHorizontalPosition optional The horizontal position of the battery block/module in the actual battery cabinet
(e.g. 3, if it is the 3rd position counting from the left) | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.11 |
| upsBatteryCabBlockStringReference optional Reference to the specific global battery string index | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.2 |
| upsBatteryCabBlockLocalIndex optional Local battery block/module identification index in the actual battery string (e.g. Battery block 3 in the battery string) | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.3 |
| upsBatteryCabBlockPresent optional Value indicates if battery block/module is present in the system.
Typically battery modules are removable and battery blocks are static. Reports notAvailable(3) if data is not ava… | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.2.7.1.4 |
| upsBatteryCabBlockType optional Text string value, showing the vendor and model of the battery in the battery block/module | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.7.1.5 |
| upsBatteryCabBlockTemperature optional The temperature for the battery block/module in tenths of degrees Celcius.
If multiple sensors are available it is the highest temperature in the battery block/module | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.6 |
| upsBatteryCabBlockFuseStatus optional If the battery module has a fuse, the status is given by this value.
1 = Fuse open
2 = Fuse OK
3 = Not present | column | Enumeration | .1.3.6.1.4.1.318.1.1.1.2.7.1.7 |
| upsBatteryCabBlockVoltage optional The voltage of the battery block/module | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.8 |
| upsBatteryCabBlockNumberOfCells optional The number of cells in the battery block/module | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBatteryCabBlockIndex optional The battery cabinet block identifier. Global battery cabinet block
table index. | column | Integer32 | .1.3.6.1.4.1.318.1.1.1.2.7.1.1 |