airFMModStmElectHumMode
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.7
Object
column
mandatory
r/w
Enumeration
Set the humidifier function mode.
Off: Remove power from electrodes.
Auto: Humidifier controlled by Module controller.
Drain: Remove power from electrodes and drain the cylinder.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.7- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- airFMModHumEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | notApplicable |
2 | off |
3 | auto |
4 | drain |