iemStatusProbeMaxHumidViolation

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.10.2.3.2.1.13

Object

column mandatory Enumeration
The maximum humidity violation status of the probe humidity
reading. This OID will show a maxTempViolation(2)
if the current humidity reading shown in the
'iemStatusProbeCurrentHumid' OID is greater than or equal to
the maximum humidity threshold value, the
'iemConfigProbeMaxHumidThreshold' OID, and the value of the
'iemConfigProbeMaxHumidEnable' OID is enabled. Otherwise it will
show noViolation(1).  If the 'iemConfigProbeMaxHumidEnable' OID is
disabled, this OID will show disabled(3)

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.10.2.3.2.1.13
Type
column
Access
readonly
Status
mandatory
Parent
iemStatusProbesEntry
Table
iemStatusProbesTable
Siblings
14

Syntax

Enumeration

Values & Constraints

Enumerated Values
1noViolation
2maxHumidViolation
3disabled

Related Objects

Sibling Objects