ePDUSensorConfigModule
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.30.8.1.1.2
Object
column
mandatory
Integer32
The user-defined Easy PDU numeric ID
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.30.8.1.1.2- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- ePDUSensorConfigEntry
- Table
- ePDUSensorConfigTable
- Siblings
- 5
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| ePDUSensorConfigIndex mandatory The index to the temperature-humidity sensor configuration data table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.30.8.1.1.1 |
| ePDUSensorConfigTempMaxThreshold mandatory User-defined Max Temperature alarm threshold. Units: 0.1 degrees Celsius.
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.30.8.1.1.3 |
| ePDUSensorConfigTempMinThreshold mandatory User-defined Min Temperature alarm threshold. Units: 0.1 degrees Celsius.
Models that do not support this feature will
respond to this OID with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.30.8.1.1.4 |
| ePDUSensorConfigHumidityMaxThreshold mandatory User-defined Max Humidity alarm threshold. Units: 0.1% relative humidity.
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.30.8.1.1.5 |
| ePDUSensorConfigHumidityMinThreshold mandatory User-defined Min Humidity alarm threshold. Units: 0.1% relative humidity.
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.30.8.1.1.6 |