PDU2-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
87
Rows
87
Columns
799
trapInformationTable
table.1.3.6.1.4.1.13742.6.0.0.1
·
1 row entry
·
7 columns
A group of objects used exclusively in traps. This is a table for historic reasons; it can't be queried from the SNMP agent.
An entry containing objects used in traps.
Indexes
pduId
| Column | Syntax | OID |
|---|---|---|
|
userName
The user currently logged in.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.0.0.1.1.2 |
|
targetUser
The user added, deleted, or modified.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.0.0.1.1.3 |
|
imageVersion
The version of the upgrade image.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.0.0.1.1.5 |
|
roleName
The role added, deleted, or modified.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.0.0.1.1.6 |
|
smtpMessageRecipients
Comma separated list of SMTP message recipients
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.0.0.1.1.7 |
|
smtpServer
The IP address/host name of the SMTP server
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.0.0.1.1.8 |
|
newTargetUser
The new name of a renamed user.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.0.0.1.1.9 |
nameplateTable
table.1.3.6.1.4.1.13742.6.3.2.1
·
1 row entry
·
9 columns
A list of PDU nameplate entries. The number of entries is given by the value of pduCount.
An entry providing PDU nameplate information.
Indexes
pduId
| Column | Syntax | OID |
|---|---|---|
|
pduId
A unique value for each PDU or power meter.
For BCM2 and PMC, pduId can be: - 0 for the main controller - The meter ID (rotary switch) for power meter For all other products, pduId is the PDU's li… |
Integer32 Constraints: range: 0-256 |
.1.3.6.1.4.1.13742.6.3.2.1.1.1 |
|
pduManufacturer
The PDU manufacturer.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.1.1.2 |
|
pduModel
The PDU model name.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.1.1.3 |
|
pduSerialNumber
The PDU serial number.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.1.1.4 |
|
pduRatedVoltage
The PDU voltage rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.1.1.5 |
|
pduRatedCurrent
The PDU current rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.1.1.6 |
|
pduRatedFrequency
The PDU frequency rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.1.1.7 |
|
pduRatedVA
The PDU VA (VoltAmps) rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.1.1.8 |
|
pduImage
The URL of the wiring diagram for this PDU.
|
URL Textual Convention: URL OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.1.1.9 |
unitConfigurationTable
table.1.3.6.1.4.1.13742.6.3.2.2
·
1 row entry
·
58 columns
A list of PDU configuration entries. The number of entries is given by the value of pduCount.
An entry containing configuration objects for a particular PDU.
Indexes
pduId
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inletCount
The number of inlets.
|
Integer32 Constraints: range: 0-256 |
.1.3.6.1.4.1.13742.6.3.2.2.1.2 |
||||||||||||||
|
overCurrentProtectorCount
The number of overcurrent protectors.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.3 |
||||||||||||||
|
outletCount
The number of outlets.
|
Integer32 Constraints: range: 0-256 |
.1.3.6.1.4.1.13742.6.3.2.2.1.4 |
||||||||||||||
|
inletControllerCount
The number of inlet controllers.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.5 |
||||||||||||||
|
outletControllerCount
The number of outlet controllers.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.6 |
||||||||||||||
|
externalSensorCount
The maximum supported number of external sensors. This value is
fixed and does not reflect how many sensors are actually connected. |
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.7 |
||||||||||||||
|
pxIPAddress
deprecated
The current IP address. A value of 0.0.0.0 indicates an error
or an unset option. |
SNMPv2-SMIIpAddress Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.13742.6.3.2.2.1.8 |
||||||||||||||
|
netmask
deprecated
The current netmask. A value of 0.0.0.0 indicates an error
or an unset option. |
SNMPv2-SMIIpAddress Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.13742.6.3.2.2.1.9 |
||||||||||||||
|
gateway
deprecated
The current gateway. A value of 0.0.0.0 indicates an error
or an unset option. |
SNMPv2-SMIIpAddress Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.13742.6.3.2.2.1.10 |
||||||||||||||
|
pxMACAddress
deprecated
The current MAC address.
If bridge interface is enabled, then equal to the MAC address of Ethernet 1 else if Ethernet 1 is enabled, then equal to the MAC address of Ethernet 1 else if Ethernet 2 is enabled, then equal t… |
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.13742.6.3.2.2.1.11 |
||||||||||||||
|
utcOffset
The current UTC offset.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.12 |
||||||||||||||
|
pduName
The user-defined name for the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.13 |
||||||||||||||
|
networkInterfaceType
deprecated
The network interface type: wired or wireless.
If only the Wireless interface is enabled, then equal to wireless else equal to wired |
NetworkInterfaceTypeEnumeration Textual Convention: NetworkInterfaceTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.14 |
||||||||||||||
|
externalSensorsZCoordinateUnits
External sensor Z coordinate units: freeform text or rack units (U)
Default is U. |
ExternalSensorsZCoordinateUnitsEnumerationr/w Textual Convention: ExternalSensorsZCoordinateUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.34 |
||||||||||||||
|
unitDeviceCapabilities
A bit string indicating which unit sensors are available.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.35 |
||||||||||||||
|
outletSequencingDelay
deprecated
This OID is deprecated, it is an alias for inrushGuardDelay
|
Unsigned32r/w Constraints: range: 100-10000 |
.1.3.6.1.4.1.13742.6.3.2.2.1.36 |
||||||||||||||
|
globalOutletPowerCyclingPowerOffPeriod
The power-off period when an outlet is cycled;
applies to all outlets unless overridden at the outlet level; specified in seconds; 1 <= value <= 3600 seconds. |
Unsigned32r/w Constraints: range: 1-3600 |
.1.3.6.1.4.1.13742.6.3.2.2.1.37 |
||||||||||||||
|
globalOutletStateOnStartup
The outlet state used when powering the respective inlet;
applies to all outlets unless overridden at the outlet level. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching. |
GlobalOutletStateOnStartupEnumerationr/w Textual Convention: GlobalOutletStateOnStartupEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.38 |
||||||||||||||
|
outletPowerupSequence
The sequence in which will the outlets will be switched on under the following conditions.
1) Switch all outlets on operation is executed 2) Power to the PDU is cycled String must consist of a comma separated sequence o… |
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.39 |
||||||||||||||
|
pduPowerCyclingPowerOffPeriod
When power to the PX is cycled (either manually or because of a
temporary power loss), this number determines how many seconds the PX will wait before it provides power to the outlets. specified in seconds: 1 <= value … |
Unsigned32r/w Constraints: range: 1-3600 |
.1.3.6.1.4.1.13742.6.3.2.2.1.40 |
||||||||||||||
|
pduDaisychainMemberType
The role of the unit in a port forwarding USB or Ethernet cascade
|
DaisychainMemberTypeEnumeration Textual Convention: DaisychainMemberTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.41 |
||||||||||||||
|
managedExternalSensorCount
The number of managed external sensors
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.42 |
||||||||||||||
|
pxInetAddressType
deprecated
The type of address format
This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). |
INET-ADDRESS-MIBInetAddressType Textual Convention: INET-ADDRESS-MIBInetAddressType EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.50 |
||||||||||||||
|
pxInetIPAddress
deprecated
The current IP address. A value of 0.0.0.0 indicates an error
or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0 |
INET-ADDRESS-MIBInetAddress Textual Convention: INET-ADDRESS-MIBInetAddress OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.51 |
||||||||||||||
|
pxInetNetmask
deprecated
The current netmask. A value of 0.0.0.0 indicates an error
or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0 |
INET-ADDRESS-MIBInetAddress Textual Convention: INET-ADDRESS-MIBInetAddress OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.52 |
||||||||||||||
|
pxInetGateway
deprecated
The current gateway. A value of 0.0.0.0 indicates an error
or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0 |
INET-ADDRESS-MIBInetAddress Textual Convention: INET-ADDRESS-MIBInetAddress OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.53 |
||||||||||||||
|
loadShedding
Enter/Exit Load Shedding Mode
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.55 |
||||||||||||||
|
serverCount
The number of servers monitored with the server reachability feature
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.56 |
||||||||||||||
|
inrushGuardDelay
The time interval between switching on two outlets;
specified in milliseconds; 100 <= value <= 10000 milliseconds. |
Unsigned32r/w Constraints: range: 100-10000 |
.1.3.6.1.4.1.13742.6.3.2.2.1.57 |
||||||||||||||
|
cascadedDeviceConnected
Indicates whether another PX2 is connected using an USB cable to
the USB-A port of this PX2 in a cascaded configuration. |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.58 |
||||||||||||||
|
synchronizeWithNTPServer
Indicates whether time is synchronized with an NTP server.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.59 |
||||||||||||||
|
useDHCPProvidedNTPServer
obsolete
**NOTE: This object is obsolete. Its functionality has been replaced
by the following: - If at least one of firstNTPServerAddress and secondNTPServerAddress has been configured then use the static NTP servers - else u… |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.60 |
||||||||||||||
|
firstNTPServerAddressType
Represents the type of the corresponding instance
of firstNTPServerAddress object. When setting this value, be sure that firstNTPServerAddress is of this address type, e.g. by setting both of them. |
INET-ADDRESS-MIBInetAddressTyper/w Textual Convention: INET-ADDRESS-MIBInetAddressType EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.61 |
||||||||||||||
|
firstNTPServerAddress
The address of the primary NTP server.
When setting this value, be sure that it is of the type specified in firstNTPServerAddressType, e.g. by setting both of them. |
INET-ADDRESS-MIBInetAddressr/w Textual Convention: INET-ADDRESS-MIBInetAddress OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.62 |
||||||||||||||
|
secondNTPServerAddressType
Represents the type of the corresponding instance
of secondNTPServerAddress object. When setting this value, be sure that secondNTPServerAddress is of this address type, e.g. by setting both of them. Default is ipv4 |
INET-ADDRESS-MIBInetAddressTyper/w Textual Convention: INET-ADDRESS-MIBInetAddressType EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.63 |
||||||||||||||
|
secondNTPServerAddress
The address of the second NTP server.
When setting this value, be sure that it is of the type specified in secondNTPServerAddressType, e.g. by setting both of them. |
INET-ADDRESS-MIBInetAddressr/w Textual Convention: INET-ADDRESS-MIBInetAddress OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.64 |
||||||||||||||
|
wireCount
obsolete
The number of wire objects in the PDU topology. This feature is no
longer used, the returned value is always 0. |
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.65 |
||||||||||||||
|
transferSwitchCount
The number of transfer switches.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.66 |
||||||||||||||
|
productType
The product type (PDU, BCM, transfer switch or power meter).
|
ProductTypeEnumeration Textual Convention: ProductTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.67 |
||||||||||||||
|
meteringControllerCount
The number of metering controllers.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.6.3.2.2.1.68 |
||||||||||||||
|
relayBehaviorOnPowerLoss
The relay behavior on power loss (latching or non-latching).
|
RelayPowerLossBehaviorEnumerationr/w Textual Convention: RelayPowerLossBehaviorEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.69 |
||||||||||||||
|
deviceCascadeType
The type of network cascade this device is part of (none, bridging
or port forwarding). |
DeviceCascadeTypeEnumeration Textual Convention: DeviceCascadeTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.70 |
||||||||||||||
|
deviceCascadePosition
The position of the device in the cascade chain. Only supported in
port forwarding mode, 0 otherwise. |
Integer32 Constraints: range: 0-99 |
.1.3.6.1.4.1.13742.6.3.2.2.1.71 |
||||||||||||||
|
peripheralDevicesAutoManagement
Defines whether newly-connected peripheral devices are automatically
assigned to an unused slot. |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.72 |
||||||||||||||
|
frontPanelOutletSwitching
Enables/disables switching of outlets using the PDU front panel.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.73 |
||||||||||||||
|
frontPanelRCMSelfTest
Enables/disables front panel RCM self-test.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.74 |
||||||||||||||
|
frontPanelActuatorControl
Enables/disables front panel peripheral actuator control.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.75 |
||||||||||||||
|
circuitCount
The number of branch circuits in a panel.
|
Integer32 Constraints: range: 0-96 |
.1.3.6.1.4.1.13742.6.3.2.2.1.76 |
||||||||||||||
|
activeDNSServerCount
The number of active DNS servers
|
Integer32 Constraints: range: 0-16 |
.1.3.6.1.4.1.13742.6.3.2.2.1.77 |
||||||||||||||
|
activeNTPServerCount
The number of active NTP servers
|
Integer32 Constraints: range: 0-16 |
.1.3.6.1.4.1.13742.6.3.2.2.1.78 |
||||||||||||||
|
peripheralDevicePackageCount
The number of peripheral device packages.
|
Integer32 Constraints: range: 0-256 |
.1.3.6.1.4.1.13742.6.3.2.2.1.79 |
||||||||||||||
|
outletGroupCount
The number of configured outlet groups
|
Integer32 Constraints: range: 0-128 |
.1.3.6.1.4.1.13742.6.3.2.2.1.80 |
||||||||||||||
|
demandUpdateInterval
The update interval (in seconds) for demand sensors (BCM2 only).
Demand sensors report the average active power within the averaging period. The sensor reading is updated every 'demandUpdateInterval' seco… |
Unsigned32r/w Constraints: range: 15-300 |
.1.3.6.1.4.1.13742.6.3.2.2.1.81 |
||||||||||||||
|
demandAveragingIntervals
The number of intervals for demand sensor averaging (BCM2 only).
Demand sensors report the average active power within the averaging period. The sensor reading is updated every 'demandUpdateInterval' seco… |
Unsigned32r/w Constraints: range: 1-60 |
.1.3.6.1.4.1.13742.6.3.2.2.1.82 |
||||||||||||||
|
hasDCInlets
True if the PDU has at least one DC inlet
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.83 |
||||||||||||||
|
pduOrientation
The detected PDU orientation at startup (none if orientation is not
supported). |
PduOrientationEnumeration Textual Convention: PduOrientationEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.84 |
||||||||||||||
|
pduUptime
The number of seconds elapsed since the PDU booted. Link units
are not supported and return 0. |
Unsigned32 Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.13742.6.3.2.2.1.85 |
||||||||||||||
|
tripCauseOutletHandling
How to handle outlets that are suspected to have caused an OCP trip event.
|
TripCauseOutletHandlingEnumerationr/w Textual Convention: TripCauseOutletHandlingEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.2.1.86 |
.1.3.6.1.4.1.13742.6.3.2.3
·
1 row entry
·
5 columns
A list of entries for the boards in a PDU. The number of entries is one more than the sum of inletControllerCount, outletControllerCount and meterControllerCount.
An entry containing objects for a controller.
Indexes
pduId boardType boardIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
boardType
The type of board.
|
BoardTypeEnumeration Textual Convention: BoardTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.3.1.1 |
||||||||
|
boardIndex
A unique value for each controller.
|
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.2.3.1.2 |
||||||||
|
boardVersion
The board hardware version.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.3.1.4 |
||||||||
|
boardFirmwareVersion
The firmware version.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.3.1.6 |
||||||||
|
boardFirmwareTimeStamp
The time when the board firmware was updated as UNIX timestamp.
It is measured in seconds since January 1, 1970 (midnight UTC/GMT) |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.3.1.8 |
logConfigurationTable
table.1.3.6.1.4.1.13742.6.3.2.4
·
1 row entry
·
5 columns
A table of parameters for the data logging feature. The number of entries is given by the value of pduCount.
An entry containing data logging parameters for a particular PDU.
Indexes
pduId
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
dataLogging
Defines whether sensor data logging is enabled.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.4.1.1 |
||||
|
measurementPeriod
Data collection periodicity. This is the periodicity of the data
collected by the PDU. This value is fixed at 1 second. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.2.4.1.2 |
||||
|
measurementsPerLogEntry
The number of measurements aggregated into a data log entry.
|
Integer32r/w Constraints: range: 1-600 |
.1.3.6.1.4.1.13742.6.3.2.4.1.3 |
||||
|
logSize
The capacity (number of entries) of the data log.
Note: The value may be reduced due to memory limitations depending on the number of sensors with data logging enabled. |
Integer32r/w Constraints: range: 60-20000 |
.1.3.6.1.4.1.13742.6.3.2.4.1.4 |
||||
|
dataLoggingEnableForAllSensors
Operation to control data logging for all sensors:
- when set to true, all *SensorLogAvailable OIDs are set to true - when set to false, all *SensorLogAvailable OIDs are set to false This OID is supposed to be written o… |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.4.1.5 |
.1.3.6.1.4.1.13742.6.3.2.5
·
1 row entry
·
22 columns
A list of unit sensor configuration entries.
An entry containing unit sensor configuration objects.
Indexes
pduId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
sensorType
The type of sensor.
|
SensorTypeEnumeration Textual Convention: SensorTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.5.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.5.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.5.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorAccuracy
deprecated
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.2.5.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorTolerance
deprecated
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (unitSensorDecimalDigits + 1). For example, if the value is 50 and unitSensorDecimalDigi… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then a… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.2.5.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01.… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01.… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.2.5.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.2.5.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. T… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.2.5.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.2.5.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. T… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.2.5.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. Th… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.2.5.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. T… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.2.5.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
unitSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. Th… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.2.5.1.31 |
activeDNSServerTable
table.1.3.6.1.4.1.13742.6.3.2.6
·
1 row entry
·
4 columns
A list of active DNS server entries. The number of rows in the table is given by the value of activeDNSServerCount in unitConfigurationTable.
An entry containing an active DNS server for a particular PDU.
Indexes
pduId activeDNSServerIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
activeDNSServerIndex
A unique value for a DNS server. Its value ranges between 1 and activeDNSServerCount.
|
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.13742.6.3.2.6.1.2 |
||||||||||||||
|
activeDNSServerAddressType
Represents the type of the corresponding instance
of activeDNSServerAddress object. |
INET-ADDRESS-MIBInetAddressType Textual Convention: INET-ADDRESS-MIBInetAddressType EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.6.1.3 |
||||||||||||||
|
activeDNSServerAddress
The address of the DNS server.
|
INET-ADDRESS-MIBInetAddress Textual Convention: INET-ADDRESS-MIBInetAddress OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.6.1.4 |
||||||||||||||
|
activeDNSServerAddressSource
deprecated
How was the address obtained: static, DHCP, DHCPv6?
No longer used, always set to static. |
AddressSourceEnumeration Textual Convention: AddressSourceEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.6.1.5 |
activeNTPServerTable
table.1.3.6.1.4.1.13742.6.3.2.7
·
1 row entry
·
4 columns
A list of active NTP server entries. The number of rows in the table is given by the value of activeNTPServerCount in unitConfigurationTable.
An entry containing an active NTP server for a particular PDU.
Indexes
pduId activeNTPServerIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
activeNTPServerIndex
A unique value for an NTP server. Its value ranges between 1 and activeNTPServerCount.
|
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.13742.6.3.2.7.1.2 |
||||||||||||||
|
activeNTPServerAddressType
Represents the type of the corresponding instance
of activeNTPServerAddress object, e.g. IPv4, IPv6, DNS Name |
INET-ADDRESS-MIBInetAddressType Textual Convention: INET-ADDRESS-MIBInetAddressType EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.7.1.3 |
||||||||||||||
|
activeNTPServerAddress
The address of the NTP server.
|
INET-ADDRESS-MIBInetAddress Textual Convention: INET-ADDRESS-MIBInetAddress OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.2.7.1.4 |
||||||||||||||
|
activeNTPServerAddressSource
deprecated
How was the address obtained: static, DHCP, DHCPv6?
No longer used, always set to static. |
AddressSourceEnumeration Textual Convention: AddressSourceEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.2.7.1.5 |
inletConfigurationTable
table.1.3.6.1.4.1.13742.6.3.3.3
·
1 row entry
·
17 columns
A list of inlet configuration entries. The number of entries is given by the value of inletCount for the PDU.
An entry containing parametersfor a particular inlet.
Indexes
pduId inletId
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inletId
A unique value for each inlet. Its value ranges between 1 and the
value of inletCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.3.3.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLabel
The label on the PDU identifying the inlet.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.3.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletName
The user-defined name.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.3.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPlug
deprecated
The type of plug/receptacle wired to the inlet.
Note: PlugTypeEnumeration is no longer updated, unlisted plugs will be reported as plugOTHER. Use inletPlugDescriptor to reliably determine the plug type. |
PlugTypeEnumeration Textual Convention: PlugTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleCount
The number of poles.
PDU: 2 for 1-phase circuits 3 for 3-phase delta-wired models 4 for 3-phase wye-wired models, pole 4 is neutral Power Meter: 2 to 5 depending on the power meter type: Pole 1 is Phase A … |
Integer32 Constraints: range: 2-5 |
.1.3.6.1.4.1.13742.6.3.3.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletRatedVoltage
The inlet voltage rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.3.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletRatedCurrent
The inlet current rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.3.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletRatedFrequency
deprecated
The inlet frequency rating.
Deprecated: use pduRatedFrequency for unit nameplate information. |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.3.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletRatedVA
deprecated
The inlet VA (VoltAmps) rating.
Deprecated: use pduRatedVA for unit nameplate information. |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.3.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletDeviceCapabilities
A bit string indicating which inlet sensors are available.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.3.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleCapabilities
A bit string indicating which inlet pole sensors are available.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.3.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPlugDescriptor
The inlet plug type as a string.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.3.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletEnableState
Enable/disable PDU operation for this inlet.
When PDU operation is disabled the sensors for this inlet and all children will no longer be updated, and outlet switching is no longer allowed. This is only meaningful for m… |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletRCMResidualOperatingCurrent
obsolete
**NOTE:This object is obsolete.
Its functionality was implemented by existing RCM sensor thresholds. The Residual Operating Current (Threshold) for the RCM State sensor. For inlets without an RCM, any attempt to access … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.3.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletIsDC
Inlet current type: true for DC, false for AC
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.3.1.15 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairCount
The number of inlet line pairs.
|
Integer32 Constraints: range: 0-3 |
.1.3.6.1.4.1.13742.6.3.3.3.1.16 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairCapabilities
A bit string indicating which inlet line pair sensors are available.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.3.3.1.17 |
.1.3.6.1.4.1.13742.6.3.3.4
·
1 row entry
·
21 columns
A list of inlet sensor configuration entries.
An entry containing inlet sensor configuration objects.
Indexes
pduId inletId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inletSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorAccuracy
deprecated
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.3.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorTolerance
deprecated
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (inletSensorDecimalDigits + 1). For example, if the value is 50 and inletSensorDecimalDi… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.3.4.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.4.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.3.4.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01.… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.4.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.4.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01.… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.4.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. … |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.4.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01.… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.4.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. … |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.4.1.31 |
.1.3.6.1.4.1.13742.6.3.3.5
·
1 row entry
·
2 columns
A list of inlet pole configuration entries. The number of entries is given by the value of inletPoleCount for the inlet.
An entry containing parameters for a particular inlet pole.
Indexes
pduId inletId inletPoleIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inletPoleLine
The phase for this inlet pole.
|
LineEnumeration Textual Convention: LineEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.5.1.1 |
||||||||||||
|
inletPoleNode
The node to which this inlet pole is connected
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.5.1.2 |
.1.3.6.1.4.1.13742.6.3.3.6
·
1 row entry
·
22 columns
A list of inlet pole sensor configuration entries.
An entry containing inlet pole sensor configuration objects.
Indexes
pduId inletId inletPoleIndex sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inletPoleIndex
A unique value for each inlet pole. Its value
ranges between 1 and the value of inletPoleCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.3.6.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.6.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.6.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorAccuracy
deprecated
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.3.6.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorTolerance
deprecated
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (inletPoleSensorDecimalDigits + 1). For example, if the value is 50 and inletPoleSensorD… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.3.6.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual valu… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual valu… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.6.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.3.6.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.6.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.6.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value … |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.6.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value i… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.6.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value … |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.6.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletPoleSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value i… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.6.1.31 |
.1.3.6.1.4.1.13742.6.3.3.7
·
1 row entry
·
5 columns
A list of inlet line pair configuration entries. The number of entries is given by the value of inletLinePairCount for the inlet.
An entry containing parameters for a particular inlet line pair.
Indexes
pduId inletId inletLinePairIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inletLinePairIndex
A unique value for each inlet line pair. Its value
ranges between 1 and the value of inletLinePairCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.3.7.1.1 |
||||||||||||
|
inletLinePairLeftLine
The phase for the line pair's left power line.
|
LineEnumeration Textual Convention: LineEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.7.1.2 |
||||||||||||
|
inletLinePairRightLine
The phase for the line pair's right power line.
|
LineEnumeration Textual Convention: LineEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.7.1.3 |
||||||||||||
|
inletLinePairLeftNode
The node number of the line pair's left power line
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.7.1.4 |
||||||||||||
|
inletLinePairRightNode
The node number of the line pair's right power line
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.7.1.5 |
.1.3.6.1.4.1.13742.6.3.3.8
·
1 row entry
·
19 columns
A list of inlet line pair sensor configuration entries.
An entry containing inlet line pair sensor configuration objects.
Indexes
pduId inletId inletLinePairIndex sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inletLinePairSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.8.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.3.8.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDi… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then a… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalD… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.3.8.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then act… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then act… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.3.8.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.3.8.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actua… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.8.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actu… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.8.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actua… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.8.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.8.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actua… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.8.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inletLinePairSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.3.8.1.31 |
.1.3.6.1.4.1.13742.6.3.4.3
·
1 row entry
·
8 columns
A list of overcurrent protector configuration entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
An entry containing objects for a particular overcurrent protector.
Indexes
pduId overCurrentProtectorIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
overCurrentProtectorIndex
A unique value for each overcurrent protector. Its value
ranges between 1 and the value of overCurrentProtectorCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.4.3.1.1 |
||||||||||||||||
|
overCurrentProtectorLabel
The label on the PDU identifying the overcurrent protector.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.4.3.1.2 |
||||||||||||||||
|
overCurrentProtectorName
The user-defined name.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.4.3.1.3 |
||||||||||||||||
|
overCurrentProtectorType
The type of overcurrent protector.
|
OverCurrentProtectorTypeEnumeration Textual Convention: OverCurrentProtectorTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.4.3.1.4 |
||||||||||||||||
|
overCurrentProtectorRatedCurrent
The current rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.4.3.1.5 |
||||||||||||||||
|
overCurrentProtectorPoleCount
The number of overcurrent protector poles.
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.13742.6.3.4.3.1.6 |
||||||||||||||||
|
overCurrentProtectorCapabilities
A bit string indicating which overcurrent protector sensors are available.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.4.3.1.9 |
||||||||||||||||
|
overCurrentProtectorPowerSource
This object allows discovery of how the PDU is wired. It indicates the
overcurrent protector's power source which can be one of the following: - an inlet - another overcurrent protector - a transfer switch … |
SNMPv2-TCRowPointer Textual Convention: SNMPv2-TCRowPointer ObjectIdentifier |
.1.3.6.1.4.1.13742.6.3.4.3.1.10 |
.1.3.6.1.4.1.13742.6.3.4.4
·
1 row entry
·
21 columns
A list of over current protector sensor configuration entries.
An entry containing over current protector sensor configuration objects.
Indexes
pduId overCurrentProtectorIndex sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
overCurrentProtectorSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.4.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.4.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorAccuracy
deprecated
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.4.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorS… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorTolerance
deprecated
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (overCurrentProtectorSensorDecimalDigits + 1). For example, if the value is 50 and overC… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigit… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtector… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.4.4.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.4.4.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.4.4.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.4.4.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits i… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.4.4.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.4.4.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is … |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.4.4.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.4.4.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
overCurrentProtectorSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is … |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.4.4.1.31 |
.1.3.6.1.4.1.13742.6.3.4.5
·
1 row entry
·
4 columns
A list of overcurrent protector pole configuration entries. The number of entries is given by the value of overCurrentProtectorPoleCount.
An entry containing parameters for a particular overcurrent protector pole.
Indexes
pduId overCurrentProtectorIndex overCurrentProtectorPoleIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
overCurrentProtectorPoleIndex
A unique value for each overcurrent protector pole. Its value
ranges between 1 and the value of overCurrentProtectorPoleCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.4.5.1.1 |
||||||||||||
|
overCurrentProtectorPoleLine
The phase for this overcurrent protector pole.
|
LineEnumeration Textual Convention: LineEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.4.5.1.2 |
||||||||||||
|
overCurrentProtectorPoleInNode
The node to which this overcurrent protector pole input is connected
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.4.5.1.3 |
||||||||||||
|
overCurrentProtectorPoleOutNode
The node to which this overcurrent protector pole output is connected
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.4.5.1.4 |
outletConfigurationTable
table.1.3.6.1.4.1.13742.6.3.5.3
·
1 row entry
·
18 columns
A list of outlet configuration entries. The number of entries is given by the value of outletCount for the PDU.
An outlet entry containing parameters for a particular outlet.
Indexes
pduId outletId
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outletId
A unique value for each outlet. Its value
ranges between 1 and the value of outletCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.5.3.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletLabel
The label on the PDU identifying the outlet.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.5.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletName
The user-defined name.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.5.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletReceptacle
deprecated
The receptacle type.
Note: ReceptacleTypeEnumeration is no longer updated, unlisted receptacles will be listed as receptacleOTHER. Use outletReceptacleDescriptor to reliably determine the receptacle type. |
ReceptacleTypeEnumeration Textual Convention: ReceptacleTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleCount
The number of poles.
|
Integer32 Constraints: range: 2-4 |
.1.3.6.1.4.1.13742.6.3.5.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletRatedVoltage
The outlet voltage rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.5.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletRatedCurrent
The outlet current rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.5.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletRatedVA
The outlet VA (VoltAmps) rating.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.5.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletDeviceCapabilities
A bit string indicating which outlet sensors are available.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.5.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleCapabilities
A bit string indicating which outlet pole sensors are available.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.5.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPowerCyclingPowerOffPeriod
The power-off period when an outlet is cycled.
Overrides the global value if outletUseGlobalPowerCyclingPowerOffPeriod is false. Specified in seconds, 1 <= value <= 3600. |
Unsigned32r/w Constraints: range: 1-3600 |
.1.3.6.1.4.1.13742.6.3.5.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletStateOnStartup
The outlet state when powering the respective inlet.
This value is ignored if relayBehaviorOnPowerLoss is set to latching. |
OutletStateOnStartupEnumerationr/w Textual Convention: OutletStateOnStartupEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletUseGlobalPowerCyclingPowerOffPeriod
Indicates which power-off period to use when the outlet is cycled:
- true: use globalOutletPowerCyclingPowerOffPeriod - false: use outletPowerCyclingPowerOffPeriod |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.3.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSwitchable
Is this outlet switchable?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.3.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletReceptacleDescriptor
The outlet receptacle type as a string.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.5.3.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletNonCritical
Is this outlet non-critical? Non-critical outlets will be switched
off when load shedding is enabled. |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.3.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSequenceDelay
The time interval between switching on this outlet and the next outlet in the
outlet sequence. This applies to the following operations. 1) Switch all outlets on operation is executed 2) Power to the PDU is cycled I… |
Unsigned32r/w Constraints: range: 0-3600 |
.1.3.6.1.4.1.13742.6.3.5.3.1.32 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPowerSource
This object allows discovery of how the PDU is wired. It indicates the
outlet's power source which can one of the following: - an inlet - an overcurrent protector - a transfer switch If the power sourc… |
SNMPv2-TCRowPointer Textual Convention: SNMPv2-TCRowPointer ObjectIdentifier |
.1.3.6.1.4.1.13742.6.3.5.3.1.33 |
.1.3.6.1.4.1.13742.6.3.5.4
·
1 row entry
·
21 columns
A list of outlet sensor configuration entries.
An entry containing outlet sensor configuration objects.
Indexes
pduId outletId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outletSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorAccuracy
deprecated
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.5.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, the… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorTolerance
deprecated
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (outletSensorDecimalDigits + 1). For example, if the value is 50 and outletSensorDecimal… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, th… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.5.4.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.4.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.5.4.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.4.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.4.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.4.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.4.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.4.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.4.1.31 |
.1.3.6.1.4.1.13742.6.3.5.5
·
1 row entry
·
2 columns
A list of outlet pole configuration entries. The number of entries is given by the value of outletPoleCount for the PDU.
An entry containing parameters for a particular outlet pole.
Indexes
pduId outletId outletPoleIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outletPoleLine
The phase for this outlet pole.
|
LineEnumeration Textual Convention: LineEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.5.1.1 |
||||||||||||
|
outletPoleNode
The node to which this outlet pole is connected
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.5.1.2 |
.1.3.6.1.4.1.13742.6.3.5.6
·
1 row entry
·
22 columns
A list of outlet pole sensor configuration entries.
An entry containing outlet pole sensor configuration objects.
Indexes
pduId outletId outletPoleIndex sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outletPoleIndex
A unique value for each outlet pole. Its value
ranges between 1 and the value of outletPoleCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.5.6.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.6.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.5.6.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorAccuracy
deprecated
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.5.6.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits i… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorTolerance
deprecated
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (outletPoleSensorDecimalDigits + 1). For example, if the value is 50 and outletPoleSenso… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual v… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.5.6.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual v… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual v… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.5.6.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.5.6.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual valu… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.6.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.6.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual valu… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.6.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.6.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual valu… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.6.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletPoleSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.5.6.1.31 |
.1.3.6.1.4.1.13742.6.3.6.3
·
1 row entry
·
29 columns
A list of external sensor configuration entries. The number of entries is given by the value of externalSensorCount for the PDU.
An entry containing parameters for an external sensor.
Indexes
pduId sensorID
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
sensorID
A unique value for each sensor. Its value
ranges between 1 and the value of externalSensorCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.6.3.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorType
The type of sensor.
|
SensorTypeEnumeration Textual Convention: SensorTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.6.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorSerialNumber
The sensor serial number.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorName
The user-defined name.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorDescription
The user-defined description.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorXCoordinate
The X coordinate.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorYCoordinate
The Y coordinate.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorZCoordinate
The Z coordinate. The value must be a number if
externalSensorsZCoordinateUnits is rackUnits. |
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorChannelNumber
The channel number.
This applies only to contact sensors, -1 for other sensors. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalOnOffSensorSubtype
The subtype of the binary sensor.
|
SensorTypeEnumerationr/w Textual Convention: SensorTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.6.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.6.3.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.6.3.1.16 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.6.3.1.17 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorAccuracy
deprecated
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.6.3.1.18 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.6.3.1.19 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTolerance
deprecated
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (externalSensorDecimalDigits + 1). For example, if the value is 50 and externalSensorDe… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.6.3.1.20 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorMaximum
The largest possible value
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.3.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorMinimum
The smallest possible value
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.3.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.6.3.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.6.3.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorLowerCriticalThreshold
The lower critical threshold
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This paramete… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.3.1.31 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorLowerWarningThreshold
The lower warning threshold
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.3.1.32 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorUpperCriticalThreshold
The upper critical threshold
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This paramete… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.3.1.33 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorUpperWarningThreshold
The upper warning threshold
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.3.1.34 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.6.3.1.35 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorIsActuator
Indicates whether the sensor is an actuator.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.6.3.1.36 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorPosition
The position of the sensor in the bus topology.
The format is a semicolon separated list of Keyword:value pairs. Keyword can be one of the following: ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION, REMOTE-HUB, … |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.3.1.37 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorUseDefaultThresholds
Use default thresholds for this sensor?
True: Use default thresholds from externalSensorTypeDefaultThresholdsTable False: Use sensor-specific thresholds from this table |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.6.3.1.38 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorAlarmedToNormalDelay
The delay (in seconds) before the sensor returns from alarmed to normal.
This is supported for motion detectors only. For all other sensors the value is 0 and cannot be set to any other value. |
Integer32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.6.3.1.39 |
.1.3.6.1.4.1.13742.6.3.6.4
·
1 row entry
·
11 columns
A table listing the default thresholds for each sensor type. The table contains a row for each supported type of external sensor with a numeric reading.
An entry containing default thresholds for a sensor type.
Indexes
pduId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
externalSensorTypeDefaultHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDe… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.6.4.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.6.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultLowerCriticalThreshold
The lower critical threshold
The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value … |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.4.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultLowerWarningThreshold
The lower warning threshold
The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value i… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultUpperCriticalThreshold
The upper critical threshold
The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value … |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultUpperWarningThreshold
The upper warning threshold
The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value i… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultEnabledThresholds
A bit string indicating which thresholds are enabled.
|
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.6.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultUnit
The unit in which the default threshold parameters are specified.
|
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.6.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultDecimalDigits
The number of digits displayed to the right of the decimal point.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.6.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultMaximum
The largest possible threshold value for this sensor type.
The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalD… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
externalSensorTypeDefaultMinimum
The smallest possible threshold value for this sensor type.
The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimal… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.6.4.1.13 |
.1.3.6.1.4.1.13742.6.3.6.5
·
1 row entry
·
8 columns
A list of entries for the peripheral device packages connected to a PDU. The number of entries is given by the value of peripheralDevicePackagesCount. A peripheral device package contains one or more sensors or actuators in a single enclosure.
An entry containing objects for a peripheral device package.
Indexes
pduId peripheralDevicePackageId
| Column | Syntax | OID |
|---|---|---|
|
peripheralDevicePackageId
A unique value for each peripheral device package.
|
Integer32 Constraints: range: 0-256 |
.1.3.6.1.4.1.13742.6.3.6.5.1.1 |
|
peripheralDevicePackageSerialNumber
The peripheral device package serial number.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.5.1.3 |
|
peripheralDevicePackageModel
The peripheral device package model.
Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1 |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.5.1.4 |
|
peripheralDevicePackageFirmwareVersion
The peripheral device package firmware version.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.5.1.5 |
|
peripheralDevicePackageMinFirmwareVersion
The peripheral device package minimum firmware version.
This field may be empty. If it is not empty, then it shall not be possible to downgrade the peripheral device firmware to an older version. |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.5.1.6 |
|
peripheralDevicePackageFirmwareTimeStamp
The time when the peripheral device package firmware was last updated.
It is measured in seconds since January 1, 1970 (midnight UTC/GMT). |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.6.5.1.7 |
|
peripheralDevicePackagePosition
The position of the package in the bus topology.
The format is a semicolon separated list of Keyword:value pairs. Keyword can be one of the following: ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION, REMOTE-HUB … |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.5.1.8 |
|
peripheralDevicePackageState
The state of the package.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.6.5.1.9 |
serverReachabilityTable
table.1.3.6.1.4.1.13742.6.3.7.3
·
1 row entry
·
3 columns
A list of server entries. The number of entries is given by the value of serverCount for the PDU.
An entry containing parameters for a server.
Indexes
pduId serverID
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
serverID
A unique value for each server. Its value
ranges between 1 and the value of serverCount for that PDU |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.7.3.1.1 |
||||
|
serverIPAddress
The IP Address/host name of the server
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.7.3.1.3 |
||||
|
serverPingEnabled
Is ping enabled for this server?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.7.3.1.4 |
.1.3.6.1.4.1.13742.6.3.8.3
·
1 row entry
·
4 columns
A list of wire configuration entries. The number of entries is given by the value of wireCount for the PDU. Note: This feature is no longer used, the table is always empty.
An entry containing objects for a particular wire.
Indexes
pduId wireId
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
wireId
obsolete
A unique value for each wire. Its value
ranges between 1 and the value of wireCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.8.3.1.1 |
||||||||||||||||||
|
wireLabel
obsolete
The label on the PDU identifying the wire.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.8.3.1.2 |
||||||||||||||||||
|
wireCapabilities
obsolete
A bit string indicating which wire sensors are available.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.8.3.1.3 |
||||||||||||||||||
|
wirePowerSource
obsolete
This object allows discovery of how the PDU is wired. It indicates the
wire's power source which can one of the following: - an inlet - an overcurrent protector - a transfer switch If the power sour… |
SNMPv2-TCRowPointer Textual Convention: SNMPv2-TCRowPointer ObjectIdentifier |
.1.3.6.1.4.1.13742.6.3.8.3.1.4 |
.1.3.6.1.4.1.13742.6.3.8.4
·
1 row entry
·
15 columns
A list of wire sensor configuration entries. Note: This feature is no longer used, the table is always empty.
An entry containing wire sensor configuration objects.
Indexes
pduId wireId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
wireSensorLogAvailable
obsolete
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.8.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorUnits
obsolete
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.8.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorDecimalDigits
obsolete
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorAccuracy
obsolete
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.8.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorResolution
obsolete
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorTolerance
obsolete
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (wireSensorDecimalDigits + 1). For example, if the value is 50 and wireSensorDecimalDigi… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorMaximum
obsolete
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorMinimum
obsolete
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorHysteresis
obsolete
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then a… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorStateChangeDelay
obsolete
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.8.4.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorLowerCriticalThreshold
obsolete
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorLowerWarningThreshold
obsolete
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorUpperCriticalThreshold
obsolete
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorUpperWarningThreshold
obsolete
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01.… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.8.4.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
wireSensorEnabledThresholds
obsolete
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.8.4.1.25 |
.1.3.6.1.4.1.13742.6.3.9.3
·
1 row entry
·
12 columns
A list of transfer switch configuration entries. The number of entries is given by the value of transferSwitchCount.
An entry containing objects for a particular transfer switch.
Indexes
pduId transferSwitchId
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
transferSwitchId
A unique value for each transfer switch. Its value
ranges between 1 and the value of transferSwitchCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.9.3.1.1 |
||||||||||||
|
transferSwitchLabel
The label on the PDU identifying the transfer switch.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.9.3.1.2 |
||||||||||||
|
transferSwitchName
The user-defined name of the transfer switch.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.9.3.1.3 |
||||||||||||
|
transferSwitchPreferredInlet
The preferred inlet. This is the inlet to be selected in case both
inlets have acceptable power. |
Integer32 Constraints: range: 1-64 |
.1.3.6.1.4.1.13742.6.3.9.3.1.4 |
||||||||||||
|
transferSwitchPoleCount
The number of poles.
|
Integer32 Constraints: range: 2-4 |
.1.3.6.1.4.1.13742.6.3.9.3.1.5 |
||||||||||||
|
transferSwitchAutoReTransferEnabled
Enables or disables automatic retransfer from the standby inlet to
the preferred inlet after power has been restored. |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.9.3.1.20 |
||||||||||||
|
transferSwitchAutoReTransferWaitTime
The delay for automatic retransfers. Retransfer occurs this many
seconds after the condition causing the original transfer has been corrected. |
Unsigned32r/w Constraints: range: 1-180 |
.1.3.6.1.4.1.13742.6.3.9.3.1.21 |
||||||||||||
|
transferSwitchAutoReTransferRequiresPhaseSync
Enables or disables automatic retransfer in case the two inlets are
not synchronized. If set to True, automatic retransfer is inhibited while a phase sync alarm is present, i.e. the phase difference between the two inle… |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.9.3.1.22 |
||||||||||||
|
transferSwitchFrontPanelManualTransferButtonEnabled
Enables or disables the Manual Transfer button on the unit's front panel.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.9.3.1.23 |
||||||||||||
|
transferSwitchCapabilities
A bit string indicating which sensors are available for the transfer switch.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.9.3.1.24 |
||||||||||||
|
transferSwitchPowerSource1
This object allows discovery of how the PDU is wired. It indicates the
transfer switch's first power source, typically a fuse. It contains the OID of an overCurrentProtectorLabel in the overCurrentProtect… |
SNMPv2-TCRowPointer Textual Convention: SNMPv2-TCRowPointer ObjectIdentifier |
.1.3.6.1.4.1.13742.6.3.9.3.1.31 |
||||||||||||
|
transferSwitchPowerSource2
This object allows discovery of how the PDU is wired. It indicates the
transfer switch's second power source, typically a fuse. It contains the OID of an overCurrentProtectorLabel in the overCurrentProtec… |
SNMPv2-TCRowPointer Textual Convention: SNMPv2-TCRowPointer ObjectIdentifier |
.1.3.6.1.4.1.13742.6.3.9.3.1.32 |
.1.3.6.1.4.1.13742.6.3.9.4
·
1 row entry
·
21 columns
A list of transfer switch sensor configuration entries.
An entry containing transfer switch sensor configuration objects.
Indexes
pduId transferSwitchId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
transferSwitchSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.9.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.9.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorAccuracy
deprecated
The accuracy: the maximum relative difference (in percent) between
measurement and the actual value. This parameter does not apply to sensors without numerical reading. |
HundredthsOfAPercentage Textual Convention: HundredthsOfAPercentage Unsigned32Type Constraints: range: 0..10000 |
.1.3.6.1.4.1.13742.6.3.9.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimal… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorTolerance
deprecated
The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by (transferSwitchSensorDecimalDigits + 1). For example, if the value is 50 and transferSwi… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecima… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.9.4.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then a… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then a… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.9.4.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.9.4.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then act… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.4.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.4.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then act… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.4.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actu… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.4.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then act… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.4.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
transferSwitchSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actu… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.4.1.31 |
.1.3.6.1.4.1.13742.6.3.9.5
·
1 row entry
·
5 columns
A list of transfer switch pole configuration entries. The number of entries is given by the value of transferSwitchPoleCount.
An entry containing parameters for a particular transfer switch pole.
Indexes
pduId transferSwitchId transferSwitchPoleIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
transferSwitchPoleIndex
A unique value for each transfer switch pole. Its value
ranges between 1 and the value of transferSwitchPoleCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.9.5.1.1 |
||||||||||||
|
transferSwitchPoleLine
The phase for this transfer switch pole.
|
LineEnumeration Textual Convention: LineEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.9.5.1.2 |
||||||||||||
|
transferSwitchPoleIn1Node
The node to which this transfer switch pole input 1 is connected
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.5.1.3 |
||||||||||||
|
transferSwitchPoleIn2Node
The node to which this transfer switch pole input 2 is connected
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.5.1.4 |
||||||||||||
|
transferSwitchPoleOutNode
The node to which this transfer switch pole output is connected
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.9.5.1.5 |
.1.3.6.1.4.1.13742.6.3.10.2
·
1 row entry
·
8 columns
A list of power meter and panel configuration entries. Note: Also see inlet tables for settings and sensor information.
An entry containing configuration objects for power meters and panels.
Indexes
pduId
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
powerMeterPhaseCTRating
The rating of the phase CT in Amps, or 0 if no CT is present.
At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.10.2.1.2 |
||||||
|
powerMeterNeutralCTRating
The rating of the neutral CT in Amps, or 0 if no CT is present.
At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.10.2.1.3 |
||||||
|
powerMeterEarthCTRating
The rating of the earth CT in Amps, or 0 if no CT is present.
At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.10.2.1.4 |
||||||
|
powerMeterBranchCount
The maximum number of circuits supported by the panel.
This can be used to distinguish between panels (>0) and power meters (0). See circuitCount for the number of currently defined circuits. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.10.2.1.5 |
||||||
|
powerMeterPanelPositions
The number of circuit positions in the panel, or 0 for power meters.
Its value is specified by the user when configuring a panel |
Integer32 Constraints: range: 0-256 |
.1.3.6.1.4.1.13742.6.3.10.2.1.6 |
||||||
|
powerMeterPanelLayout
The panel circuit position layout: one or two columns.
This is valid only for panels, the value is -1 for power meters. |
PanelLayoutEnumeration Textual Convention: PanelLayoutEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.10.2.1.7 |
||||||
|
powerMeterPanelNumbering
The panel circuit position numbering scheme: odd/even or sequential.
This is valid only for panels, the value is -1 for power meters. |
PanelNumberingEnumeration Textual Convention: PanelNumberingEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.10.2.1.8 |
||||||
|
powerMeterType
The power meter type: 3-phase, single-phase or split-phase.
|
PowerMeterTypeEnumeration Textual Convention: PowerMeterTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.10.2.1.9 |
.1.3.6.1.4.1.13742.6.3.11.2
·
1 row entry
·
9 columns
A list of circuit configuration entries. The number of entries is given by the value of panelCircuitPositionCount.
An entry containing configuration objects for the circuit.
Indexes
pduId circuitId
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
circuitId
A unique value for each circuit. Its value is the smallest panel
position occupied by the circuit. |
Integer32 Constraints: range: 1-1024 |
.1.3.6.1.4.1.13742.6.3.11.2.1.1 |
||||||||||||||||||||||||||||||||||||||
|
circuitPoleCount
The number of panel positions occupied by the circuit.
|
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.11.2.1.2 |
||||||||||||||||||||||||||||||||||||||
|
circuitName
The user-defined name for the circuit.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.11.2.1.3 |
||||||||||||||||||||||||||||||||||||||
|
circuitType
The circuit type: line-line, line-neutral, line-line-neutral or 3-phase
|
CircuitTypeEnumeration Textual Convention: CircuitTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.11.2.1.4 |
||||||||||||||||||||||||||||||||||||||
|
circuitRatedCurrent
The rating of the breaker for the circuit in Amps.
At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.2.1.5 |
||||||||||||||||||||||||||||||||||||||
|
circuitCTRating
The rating of the CTs metering this circuit in Amps.
At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.2.1.6 |
||||||||||||||||||||||||||||||||||||||
|
circuitCapabilities
A bit string indicating which sensors are available for the circuit.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.11.2.1.7 |
||||||||||||||||||||||||||||||||||||||
|
circuitPoleCapabilities
A bit string indicating which sensors are available for each circuit pole.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.11.2.1.8 |
||||||||||||||||||||||||||||||||||||||
|
circuitPowerSource
This object allows discovery of how the circuit is wired. It indicates the
circuit's power source, typically an inlet. It contains the OID of an inletLabel in the inletConfigurationTable. The indices of t… |
SNMPv2-TCRowPointer Textual Convention: SNMPv2-TCRowPointer ObjectIdentifier |
.1.3.6.1.4.1.13742.6.3.11.2.1.9 |
.1.3.6.1.4.1.13742.6.3.11.3
·
1 row entry
·
4 columns
A list of branch circuit pole configuration entries. The number of entries is given by the value of circuitPoleCount for the circuit.
An entry containing configuration objects for the circuit poles.
Indexes
pduId circuitId circuitPoleId
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
circuitPoleId
A unique value for each circuit pole. Its value
ranges between 1 and the value of circuitPoleCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.11.3.1.1 |
||||||||||
|
circuitPolePanelPosition
The panel position for this pole.
|
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.6.3.11.3.1.2 |
||||||||||
|
circuitPoleCTNumber
The CT number for this circuit pole, or 0 if no CT is present.
At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 |
Integer32r/w Constraints: range: 0-256 |
.1.3.6.1.4.1.13742.6.3.11.3.1.3 |
||||||||||
|
circuitPolePhase
The phase for this circuit pole.
At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 |
PhaseEnumerationr/w Textual Convention: PhaseEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.11.3.1.4 |
.1.3.6.1.4.1.13742.6.3.11.4
·
1 row entry
·
19 columns
A list of circuit sensor configuration entries.
An entry containing circuit sensor configuration objects.
Indexes
pduId circuitId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
circuitSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.11.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.11.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, t… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value i… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.11.4.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value i… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value i… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.4.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.11.4.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.4.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.4.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.4.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.4.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.4.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.4.1.31 |
.1.3.6.1.4.1.13742.6.3.11.6
·
1 row entry
·
19 columns
A list of circuit pole sensor configuration entries.
An entry containing circuit pole sensor configuration objects.
Indexes
pduId circuitId circuitPoleId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
circuitPoleSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.11.6.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.11.6.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actua… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigit… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.11.6.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.11.6.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.11.6.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.6.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual v… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.6.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.6.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.6.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.6.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
circuitPoleSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.11.6.1.31 |
.1.3.6.1.4.1.13742.6.3.12.2
·
1 row entry
·
4 columns
A list of outlet group configuration entries.
An entry containing configuration objects for outlet groups.
Indexes
outletGroupId
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
outletGroupId
A unique value for each outlet group.
|
Integer32 Constraints: range: 1-128 |
.1.3.6.1.4.1.13742.6.3.12.2.1.1 |
||||||||
|
outletGroupName
The user-defined name.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.12.2.1.2 |
||||||||
|
outletGroupCapabilities
A bit string indicating which sensors are available for the outlet group.
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.12.2.1.3 |
||||||||
|
outletGroupMembers
The list of member outlets of this group.
String must consist of a comma separated sequence of the outlet identifiers in the format PDUID-OUTLETID. Example: 1-1,1-5,2-2. |
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.3.12.2.1.4 |
.1.3.6.1.4.1.13742.6.3.12.3
·
1 row entry
·
19 columns
A list of outlet group sensor configuration entries.
An entry containing outlet group sensor configuration objects.
Indexes
outletGroupId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outletGroupSensorLogAvailable
Is data logging enabled for this sensor?
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.12.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorUnits
The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.3.12.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorResolution
The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorMaximum
The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorMinimum
The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actua… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorHysteresis
The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigit… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorStateChangeDelay
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive… |
Unsigned32r/w Constraints: range: 0-300 |
.1.3.6.1.4.1.13742.6.3.12.3.1.14 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorLowerCriticalThreshold
The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.21 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorLowerWarningThreshold
The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.22 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorUpperCriticalThreshold
The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.23 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorUpperWarningThreshold
The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.3.12.3.1.24 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorEnabledThresholds
A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.6.3.12.3.1.25 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorSignedMaximum
The largest possible reading as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.12.3.1.26 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorSignedMinimum
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual v… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.12.3.1.27 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorSignedLowerCriticalThreshold
The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.12.3.1.28 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorSignedLowerWarningThreshold
The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.12.3.1.29 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorSignedUpperCriticalThreshold
The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual va… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.12.3.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletGroupSensorSignedUpperWarningThreshold
The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.3.12.3.1.31 |
outletSwitchControlTable
table.1.3.6.1.4.1.13742.6.4.1.2
·
1 row entry
·
4 columns
A list of outlets for a PDU. The number of entries is given by the value of outletCount.
An entry for implementing switching operations on an outlet.
Indexes
pduId outletId
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
switchingOperation
The switching operation: switch on, switch off or power-cycle.
|
OutletSwitchingOperationsEnumerationr/w Textual Convention: OutletSwitchingOperationsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.1.2.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSwitchingState
The outlet state at present
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.1.2.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSwitchingTimeStamp
The timestamp indicating when the outlet was last switched
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.4.1.2.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
outletSuspendedState
Whether the outlet is currently off because it was suspected to have caused an OCP trip event
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.1.2.1.5 |
.1.3.6.1.4.1.13742.6.4.2.1
·
1 row entry
·
1 columns
A list of control entries for the external sensors. The set of valid indices is defined by the value of externalCount and the externalDeviceCapabilities entry for the selected external.
An entry used for controlling an external sensor.
Indexes
pduId sensorID
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
externalSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.2.1.1.2 |
.1.3.6.1.4.1.13742.6.4.3.1
·
1 row entry
·
4 columns
A list of transfer switches for a PDU. The number of entries is given by the value of transferSwitchCount.
An entry for implementing switching operations on a transfer switch.
Indexes
pduId transferSwitchId
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
transferSwitchActiveInlet
The index of the currently active inlet. The value normally ranges
between 1 and the value of inletCount, but can be 0 in case no inlet is active (e.g. overload alarm). |
Integer32 Constraints: range: 0-64 |
.1.3.6.1.4.1.13742.6.4.3.1.1.1 |
||||||||||||||||||
|
transferSwitchTransferToInlet
Select the active inlet. The written value must be between 1 and the
value of inletCount. If the selected inlet is available it will become both active and preferred, otherwise an inconsistentValue error will be returne… |
Integer32r/w Constraints: range: 0-64 |
.1.3.6.1.4.1.13742.6.4.3.1.1.2 |
||||||||||||||||||
|
transferSwitchAlarmOverride
Force transfer even if the phase difference between the inlets is too
large. This may only be written together with transferSwitchTransferToInlet, otherwise an inconsistentValue error will be returned. Always reads as f… |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.3.1.1.3 |
||||||||||||||||||
|
transferSwitchLastTransferReason
The reason for the most recent transfer
|
TransferSwitchTransferReasonEnumeration Textual Convention: TransferSwitchTransferReasonEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.3.1.1.4 |
actuatorControlTable
table.1.3.6.1.4.1.13742.6.4.4.2
·
1 row entry
·
1 columns
A list of actuators for a PDU.
An entry for implementing user-initiated state changes for an actuator.
Indexes
pduId sensorID
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
actuatorState
The actuator state.
A get operation retrieves the state of the actuator. A set operation changes the state of the sensor. The valid states depend on the actuator type. See the comment for SensorStateEnumeration. Attempt… |
SensorStateEnumerationr/w Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.4.2.1.2 |
rcmSelfTestTable
table.1.3.6.1.4.1.13742.6.4.5.2
·
1 row entry
·
1 columns
A list of inlet RCMs.
An entry for initiating the self test of an inlet RCM.
Indexes
pduId inletId
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
rcmState
The rcm state.
A Get operation retrieves the state of the RCM State Sensor. A Set operation changes the state of the sensor. The only valid state for set operations is selfTest(29). When rcmState is set to selfTest, sel… |
SensorStateEnumerationr/w Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.5.2.1.2 |
.1.3.6.1.4.1.13742.6.4.5.3
·
1 row entry
·
1 columns
A list of overcurrent protector RCMs.
An entry for initiating the self test of an overcurrent protector RCM.
Indexes
pduId overCurrentProtectorIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
overCurrentProtectorRcmState
The rcm state.
A Get operation retrieves the state of the RCM State Sensor. A Set operation changes the state of the sensor. The only valid state for set operations is selfTest(29). When rcmState is set to selfTest, sel… |
SensorStateEnumerationr/w Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.5.3.1.2 |
inletSensorControlTable
table.1.3.6.1.4.1.13742.6.4.6.1
·
1 row entry
·
2 columns
A list of control entries for the inlet sensors. The set of valid indices is defined by the value of inletCount and the inletDeviceCapabilities entry for the selected inlet.
An entry used for controlling an inlet sensor.
Indexes
pduId inletId sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
inletSensorResetValue
Writing to this variable sets a new value for the addressed sensor. Only
accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. T… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.4.6.1.1.1 |
||||
|
inletSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.6.1.1.2 |
.1.3.6.1.4.1.13742.6.4.6.2
·
1 row entry
·
1 columns
A list of control entries for the inlet pole sensors. The set of valid indices is defined by the value of inletPoleCount and the inletPoleDeviceCapabilities entry for the selected inlet pole.
An entry used for controlling an inlet pole sensor.
Indexes
pduId inletId inletPoleIndex sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
inletPoleSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.6.2.1.2 |
.1.3.6.1.4.1.13742.6.4.6.3
·
1 row entry
·
1 columns
A list of control entries for the inlet line pair sensors. The set of valid indices is defined by the value of inletLinePairCount and the inletLinePairDeviceCapabilities entry for the selected inlet line pair.
An entry used for controlling an inlet line pair sensor.
Indexes
pduId inletId inletLinePairIndex sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
inletLinePairSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.6.3.1.2 |
outletSensorControlTable
table.1.3.6.1.4.1.13742.6.4.7.1
·
1 row entry
·
2 columns
A list of control entries for the outlet sensors. The set of valid indices is defined by the value of outletCount and the outletDeviceCapabilities entry for the selected outlet.
An entry used for controlling an outlet sensor.
Indexes
pduId outletId sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
outletSensorResetValue
Writing to this variable sets a new value for the addressed sensor. Only
accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. T… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.4.7.1.1.1 |
||||
|
outletSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.7.1.1.2 |
.1.3.6.1.4.1.13742.6.4.7.2
·
1 row entry
·
1 columns
A list of control entries for the outlet pole sensors. The set of valid indices is defined by the value of outletPoleCount and the outletPoleDeviceCapabilities entry for the selected outlet pole.
An entry used for controlling an outlet pole sensor.
Indexes
pduId outletId outletPoleIndex sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
outletPoleSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.7.2.1.2 |
unitSensorControlTable
table.1.3.6.1.4.1.13742.6.4.8.1
·
1 row entry
·
2 columns
A list of control entries for the unit sensors. The set of valid indices is defined by the value of unitCount and the unitDeviceCapabilities entry for the selected unit.
An entry used for controlling an unit sensor.
Indexes
pduId sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
unitSensorResetValue
Writing to this variable sets a new value for the addressed sensor. Only
accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. T… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.4.8.1.1.1 |
||||
|
unitSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.8.1.1.2 |
.1.3.6.1.4.1.13742.6.4.9.1
·
1 row entry
·
2 columns
A list of control entries for the circuit sensors. The set of valid indices is defined by the value of circuitCount
An entry used for controlling an circuit sensor.
Indexes
pduId circuitId sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
circuitSensorResetValue
Writing to this variable sets a new value for the addressed sensor. Only
accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. T… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.4.9.1.1.1 |
||||
|
circuitSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.9.1.1.2 |
.1.3.6.1.4.1.13742.6.4.9.2
·
1 row entry
·
1 columns
A list of control entries for the circuit pole sensors. The set of valid indices is defined by the value of circuitPoleCount and the circuitPoleDeviceCapabilities entry for the selected circuit pole.
An entry used for controlling an circuit pole sensor.
Indexes
pduId circuitId circuitPoleId sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
circuitPoleSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.9.2.1.2 |
.1.3.6.1.4.1.13742.6.4.10.2
·
1 row entry
·
1 columns
A list of outlet groups. The number of entries is given by the value of outletGroupCount.
An entry for implementing switching operations on an outlet group.
Indexes
outletGroupId
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
outletGroupSwitchingOperation
The switching operation: switch on, switch off or power-cycle.
|
OutletSwitchingOperationsEnumerationr/w Textual Convention: OutletSwitchingOperationsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.10.2.1.2 |
.1.3.6.1.4.1.13742.6.4.11.1
·
1 row entry
·
2 columns
A list of control entries for the outlet group sensors. The set of valid indices is defined by the value of outletGroupCount and the outletGroupDeviceCapabilities entry for the selected outlet group.
An entry used for controlling an outlet group sensor.
Indexes
outletGroupId sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
outletGroupSensorResetValue
Writing to this variable sets a new value for the addressed sensor. Only
accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. T… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.4.11.1.1.1 |
||||
|
outletGroupSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.11.1.1.2 |
serverPowerControlTable
table.1.3.6.1.4.1.13742.6.4.12.1
·
1 row entry
·
1 columns
A list of server entries. The number of entries is given by the value of serverCount for the PDU.
An entry for implementing power control operations on a server.
Indexes
pduId serverID
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
serverPowerControlOperation
Reading the variable returns the current power state of the server. Writing
on(1) or off(2) results in a power control operation, switching the configured power target on or initiating a graceful shutdown. Writing any o… |
ServerPowerStateEnumerationr/w Textual Convention: ServerPowerStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.12.1.1.1 |
.1.3.6.1.4.1.13742.6.4.13.1
·
1 row entry
·
1 columns
A list of control entries for the over current protector sensors. The set of valid indices is defined by the value of overCurrentProtectorCount and the overCurrentProtectorDeviceCapabilities entry for the selected over current protector.
An entry used for controlling an over current protector sensor.
Indexes
pduId overCurrentProtectorIndex sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
overCurrentProtectorSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.13.1.1.2 |
.1.3.6.1.4.1.13742.6.4.14.1
·
1 row entry
·
1 columns
A list of control entries for the transfer switch sensors. The set of valid indices is defined by the value of transferSwitchCount and the transferSwitchDeviceCapabilities entry for the selected transfer switch.
An entry used for controlling an transfer switch sensor.
Indexes
pduId transferSwitchId sensorType
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
transferSwitchSensorResetMinMax
Writing True to this variable resets minimum / maximum values and their timestamps.
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.4.14.1.1.2 |
.1.3.6.1.4.1.13742.6.5.1.3
·
1 row entry
·
13 columns
A list of unit sensor entries.
An entry containing unit sensor measurement objects.
Indexes
pduId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsUnitSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.1.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.1.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This val… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.1.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.1.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.1.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsUnitSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.1.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, th… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.1.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.1.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementUnitSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.1.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, th… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.1.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.1.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementUnitSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.1.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsUnitSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsUnitSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsUnitSensorMinMaxValid. The… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.1.3.1.14 |
.1.3.6.1.4.1.13742.6.5.2.3
·
1 row entry
·
13 columns
A list of inlet sensor entries.
An entry containing inlet sensor measurement objects.
Indexes
pduId inletId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsInletSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This v… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This valu… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsInletSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, the… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementInletSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, the… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementInletSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsInletSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsInletSensorMinMaxValid. T… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.3.1.14 |
.1.3.6.1.4.1.13742.6.5.2.4
·
1 row entry
·
13 columns
A list of inlet pole sensor entries.
An entry containing inlet pole sensor measurement objects.
Indexes
pduId inletId inletPoleIndex sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsInletPoleSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.4.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.4.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.4.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. T… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsInletPoleSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigit… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits i… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementInletPoleSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigit… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits i… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementInletPoleSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletPoleSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsInletPoleSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsInletPoleSensorMinMax… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.4.1.14 |
.1.3.6.1.4.1.13742.6.5.2.5
·
1 row entry
·
13 columns
A list of inlet line pair sensor entries.
An entry containing inlet line pair sensor measurement objects.
Indexes
pduId inletId inletLinePairIndex sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsInletLinePairSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.5.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.5.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.5.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.5.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.5.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsInletLinePairSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.2.5.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDeci… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.5.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimal… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.5.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementInletLinePairSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.5.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDeci… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.5.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimal… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.2.5.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementInletLinePairSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.5.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsInletLinePairSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsInletLinePairSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsInletLinePairSens… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.2.5.1.14 |
.1.3.6.1.4.1.13742.6.5.3.3
·
1 row entry
·
13 columns
A list of over current protector sensor entries.
An entry containing over current protector sensor measurement objects.
Indexes
pduId overCurrentProtectorIndex sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsOverCurrentProtectorSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.3.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.3.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, the… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.3.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.3.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then a… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.3.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOverCurrentProtectorSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.3.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProte… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.3.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtecto… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.3.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementOverCurrentProtectorSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.3.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProte… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.3.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtecto… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.3.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementOverCurrentProtectorSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.3.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOverCurrentProtectorSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOverCurrentProtectorSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsOverCurren… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.3.3.1.14 |
.1.3.6.1.4.1.13742.6.5.4.3
·
1 row entry
·
13 columns
A list of outlet sensor entries.
An entry containing outlet sensor measurement objects.
Indexes
pduId outletId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsOutletSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.4.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.4.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This va… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.4.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOutletSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.4.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, t… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.4.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementOutletSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, t… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.4.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementOutletSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOutletSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsOutletSensorMinMaxValid.… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.3.1.14 |
.1.3.6.1.4.1.13742.6.5.4.4
·
1 row entry
·
13 columns
A list of outlet pole sensor entries.
An entry containing outlet pole sensor measurement objects.
Indexes
pduId outletId outletPoleIndex sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsOutletPoleSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.4.4.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.4.4.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.4.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01.… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.4.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOutletPoleSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.4.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDig… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.4.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementOutletPoleSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDig… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.4.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementOutletPoleSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletPoleSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOutletPoleSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsOutletPoleSensorMinM… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.4.4.1.14 |
.1.3.6.1.4.1.13742.6.5.5.3
·
1 row entry
·
10 columns
A list of external sensor entries. The number of entries is given by the value of externalSensorCount for the PDU.
An entry containing external sensor measurement objects.
Indexes
pduId sensorID
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsExternalSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.5.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.5.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. Thi… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.5.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.5.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsExternalSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.5.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.5.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementExternalSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.5.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.5.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementExternalSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.5.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsExternalSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsExternalSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsExternalSensorMinMaxVa… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.5.3.1.14 |
.1.3.6.1.4.1.13742.6.5.6.3
·
1 row entry
·
4 columns
A list of wire sensor entries. Note: This feature is no longer used, the table is always empty
An entry containing wire sensor measurement objects.
Indexes
pduId wireId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsWireSensorIsAvailable
obsolete
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.6.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsWireSensorState
obsolete
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.6.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsWireSensorValue
obsolete
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This val… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.6.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsWireSensorTimeStamp
obsolete
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.6.3.1.5 |
.1.3.6.1.4.1.13742.6.5.7.3
·
1 row entry
·
13 columns
A list of transfer switch sensor entries.
An entry containing transfer switch sensor measurement objects.
Indexes
pduId transferSwitchId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsTransferSwitchSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.7.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.7.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual val… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.7.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.7.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.7.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsTransferSwitchSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.7.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDe… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.7.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecim… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.7.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementTransferSwitchSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.7.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDe… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.7.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecim… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.7.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementTransferSwitchSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.7.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsTransferSwitchSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsTransferSwitchSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsTransferSwitchSe… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.7.3.1.14 |
.1.3.6.1.4.1.13742.6.5.8.3
·
1 row entry
·
13 columns
A list of circuit sensor entries.
An entry containing circuit sensor measurement objects.
Indexes
pduId circuitId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsCircuitSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.8.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.8.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. Th… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.8.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsCircuitSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.8.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2,… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.8.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementCircuitSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2,… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.8.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementCircuitSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsCircuitSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsCircuitSensorMinMaxVali… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.3.1.14 |
.1.3.6.1.4.1.13742.6.5.8.4
·
1 row entry
·
13 columns
A list of circuit pole sensor entries.
An entry containing circuit pole sensor measurement objects.
Indexes
pduId circuitId circuitPoleId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsCircuitPoleSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.8.4.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.8.4.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.4.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.8.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsCircuitPoleSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.8.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalD… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigi… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.8.4.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementCircuitPoleSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.4.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalD… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.4.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigi… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.8.4.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementCircuitPoleSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.4.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsCircuitPoleSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsCircuitPoleSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsCircuitPoleSensorMi… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.8.4.1.14 |
.1.3.6.1.4.1.13742.6.5.9.3
·
1 row entry
·
13 columns
A list of outlet group sensor entries.
An entry containing outlet group sensor measurement objects.
Indexes
outletGroupId sensorType
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsOutletGroupSensorIsAvailable
The sensor is present.
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.9.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.9.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorValue
The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.9.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorTimeStamp
The timestamp for reading.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.9.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorSignedValue
The sensor reading as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.0… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.9.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorMinMaxValid
The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOutletGroupSensor[Signed]{Min|Max}{Value|TimeStamp} are valid |
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.5.9.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorMinValue
The minimum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalD… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.9.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorSignedMinValue
The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigi… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.9.3.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorMinTimeStamp
The timestamp of last change of the minimum value of sensor reading
provided as measurementOutletGroupSensor[Signed]MinValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.9.3.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorMaxValue
The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalD… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.9.3.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorSignedMaxValue
The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigi… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.5.9.3.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorMaxTimeStamp
The timestamp of last change of the maximum value of sensor reading
provided as measurementOutletGroupSensor[Signed]MaxValue |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.9.3.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
measurementsOutletGroupSensorMinMaxResetTimeStamp
The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOutletGroupSensor[Signed]{Min|Max}{Value|TimeStamp} and measurementsOutletGroupSensorMi… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.5.9.3.1.14 |
logIndexTable
table.1.3.6.1.4.1.13742.6.6.1.1
·
1 row entry
·
2 columns
A table containing current indices for the data log buffer.
An entry containing the current indices for a PDU's data log buffer.
Indexes
pduId
| Column | Syntax | OID |
|---|---|---|
|
oldestLogID
The index of the oldest data in the buffer for this PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.1.1.1.2 |
|
newestLogID
The index of the newest data in the buffer for this PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.1.1.1.3 |
logTimeStampTable
table.1.3.6.1.4.1.13742.6.6.1.2
·
1 row entry
·
2 columns
A list of entries containing the timestamps of the entries in the log.
An entry containing the timestamp for log entries.
Indexes
pduId logIndex
| Column | Syntax | OID |
|---|---|---|
|
logIndex
A unique value for each entry in the log. Its value
ranges between 1 and the value of logSize. |
Integer32 Constraints: range: 1-20000 |
.1.3.6.1.4.1.13742.6.6.1.2.1.1 |
|
logTimeStamp
The time when the data was collected. It is measured in seconds since
January 1, 1970 (midnight UTC/GMT). |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.1.2.1.2 |
unitSensorLogTable
table.1.3.6.1.4.1.13742.6.6.1.3
·
1 row entry
·
8 columns
A list of unit sensor entries in the log.
An entry containing log objects for a unit sensor.
Indexes
pduId sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logUnitSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.1.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logUnitSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.1.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logUnitSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then act… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.1.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logUnitSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then act… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.1.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logUnitSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then act… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.1.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logUnitSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.1.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logUnitSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.1.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logUnitSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.1.3.1.9 |
inletSensorLogTable
table.1.3.6.1.4.1.13742.6.6.2.3
·
1 row entry
·
8 columns
A list of inlet sensor entries in the log.
An entry containing log objects for a inlet sensor.
Indexes
pduId inletId sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logInletSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.2.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.2.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then a… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then a… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then a… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actu… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actu… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actu… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.3.1.9 |
inletPoleSensorLogTable
table.1.3.6.1.4.1.13742.6.6.2.4
·
1 row entry
·
8 columns
A list of inlet pole sensor entries in the log.
An entry containing log objects for a inlet pole sensor.
Indexes
pduId inletId inletPoleIndex sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logInletPoleSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.2.4.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletPoleSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.2.4.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletPoleSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletPoleSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.4.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletPoleSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletPoleSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, t… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletPoleSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, t… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletPoleSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, t… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.4.1.9 |
.1.3.6.1.4.1.13742.6.6.2.5
·
1 row entry
·
8 columns
A list of inlet line pair sensor entries in the log.
An entry containing log objects for a inlet line pair sensor.
Indexes
pduId inletId inletLinePairIndex sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logInletLinePairSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.2.5.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletLinePairSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.2.5.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletLinePairSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDig… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.5.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletLinePairSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDig… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.5.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletLinePairSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDig… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.2.5.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletLinePairSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.5.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletLinePairSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.5.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logInletLinePairSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.2.5.1.9 |
.1.3.6.1.4.1.13742.6.6.3.3
·
1 row entry
·
8 columns
A list of over current protector sensor entries in the log.
An entry containing log objects for a over current protector sensor.
Indexes
pduId overCurrentProtectorIndex sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logOverCurrentProtectorSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.3.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOverCurrentProtectorSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.3.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOverCurrentProtectorSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSe… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.3.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOverCurrentProtectorSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSe… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.3.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOverCurrentProtectorSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSe… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.3.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOverCurrentProtectorSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSenso… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.3.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOverCurrentProtectorSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSenso… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.3.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOverCurrentProtectorSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSenso… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.3.3.1.9 |
outletSensorLogTable
table.1.3.6.1.4.1.13742.6.6.4.3
·
1 row entry
·
8 columns
A list of outlet sensor entries in the log.
An entry containing log objects for a outlet sensor.
Indexes
pduId outletId sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logOutletSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.4.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.4.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.4.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.4.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.4.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.4.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.4.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then ac… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.4.3.1.9 |
outletPoleSensorLogTable
table.1.3.6.1.4.1.13742.6.6.4.4
·
1 row entry
·
8 columns
A list of outlet pole sensor entries in the log.
An entry containing log objects for a outlet pole sensor.
Indexes
pduId outletId outletPoleIndex sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logOutletPoleSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.4.4.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletPoleSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.4.4.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletPoleSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.4.4.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletPoleSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.4.4.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletPoleSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.4.4.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletPoleSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2,… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.4.4.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletPoleSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2,… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.4.4.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletPoleSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2,… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.4.4.1.9 |
externalSensorLogTable
table.1.3.6.1.4.1.13742.6.6.5.3
·
1 row entry
·
5 columns
A list of external sensor entries in the log.
An entry containing log objects for a external sensor.
Indexes
pduId sensorID logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logExternalSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.5.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logExternalSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.5.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logExternalSensorAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, the… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.5.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logExternalSensorMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, the… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.5.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logExternalSensorMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, the… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.5.3.1.6 |
.1.3.6.1.4.1.13742.6.6.6.3
·
1 row entry
·
5 columns
A list of wire sensor entries in the log. Note: This feature is no longer used, the table is always empty
An entry containing log objects for a wire sensor.
Indexes
pduId wireId sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logWireSensorDataAvailable
obsolete
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.6.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logWireSensorState
obsolete
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.6.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logWireSensorAvgValue
obsolete
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then act… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.6.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logWireSensorMaxValue
obsolete
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then act… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.6.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logWireSensorMinValue
obsolete
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then act… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.6.3.1.6 |
.1.3.6.1.4.1.13742.6.6.7.3
·
1 row entry
·
8 columns
A list of transfer switch sensor entries in the log.
An entry containing log objects for a transfer switch sensor.
Indexes
pduId transferSwitchId sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logTransferSwitchSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.7.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logTransferSwitchSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.7.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logTransferSwitchSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalD… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.7.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logTransferSwitchSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalD… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.7.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logTransferSwitchSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalD… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.7.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logTransferSwitchSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigi… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.7.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logTransferSwitchSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigi… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.7.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logTransferSwitchSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigi… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.7.3.1.9 |
circuitSensorLogTable
table.1.3.6.1.4.1.13742.6.6.8.3
·
1 row entry
·
8 columns
A list of circuit sensor entries in the log.
An entry containing log objects for a circuit sensor.
Indexes
pduId circuitId sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logCircuitSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.8.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.8.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, th… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.8.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, th… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.8.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, th… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.8.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.8.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.8.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.8.3.1.9 |
.1.3.6.1.4.1.13742.6.6.8.5
·
1 row entry
·
8 columns
A list of circuit pole sensor entries in the log.
An entry containing log objects for a circuit pole sensor.
Indexes
pduId circuitId circuitPoleId sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logCircuitPoleSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.8.5.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitPoleSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.8.5.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitPoleSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.8.5.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitPoleSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.8.5.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitPoleSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.8.5.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitPoleSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.8.5.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitPoleSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.8.5.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logCircuitPoleSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.8.5.1.9 |
.1.3.6.1.4.1.13742.6.6.9.3
·
1 row entry
·
8 columns
A list of outlet group sensor entries in the log.
An entry containing log objects for a outlet group sensor.
Indexes
outletGroupId sensorType logIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logOutletGroupSensorDataAvailable
Is data available for this sensor during this measurement period?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.9.3.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletGroupSensorState
The most critical sensor state during this measurement period.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.6.9.3.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletGroupSensorAvgValue
The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.9.3.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletGroupSensorMaxValue
The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.9.3.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletGroupSensorMinValue
The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits … |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.6.9.3.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletGroupSensorSignedAvgValue
The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.9.3.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletGroupSensorSignedMaxValue
The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.9.3.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
logOutletGroupSensorSignedMinValue
The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.6.6.9.3.1.9 |
reliabilityDataTable
table.1.3.6.1.4.1.13742.6.10.1.2
·
1 row entry
·
9 columns
A list of PDU reliability data entries.
An entry containing reliability data for a particular PDU.
Indexes
reliabilityIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
reliabilityIndex
Index of the entry in the reliability data table.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.13742.6.10.1.2.1.1 |
||||||
|
reliabilityId
Unique ID of the entry.
POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MAIN.CSUMERRLASTHOUR Number of checksum error… |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.10.1.2.1.2 |
||||||
|
reliabilityDataValue
The normalized value
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.1.2.1.3 |
||||||
|
reliabilityDataMaxPossible
The maximum possible normalized value
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.1.2.1.4 |
||||||
|
reliabilityDataWorstValue
The worst normalized value seen so far
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.1.2.1.5 |
||||||
|
reliabilityDataThreshold
The normalized Threshold value
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.1.2.1.6 |
||||||
|
reliabilityDataRawUpperBytes
The upper 4 bytes of the raw (not normalized) data.
reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.1.2.1.7 |
||||||
|
reliabilityDataRawLowerBytes
The lower 4 bytes of the raw (not normalized) data.
reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.1.2.1.8 |
||||||
|
reliabilityDataFlags
Flags
|
Bits Enumerated Values:
|
.1.3.6.1.4.1.13742.6.10.1.2.1.9 |
reliabilityErrorLogTable
table.1.3.6.1.4.1.13742.6.10.2.2
·
1 row entry
·
8 columns
A list of PDU reliability error log entries.
An entry containing reliability error log data for a particular PDU.
Indexes
reliabilityErrorLogIndex
| Column | Syntax | OID |
|---|---|---|
|
reliabilityErrorLogIndex
Index of the entry in the reliability error log table.
|
Integer32 Constraints: range: 1-2147483647 |
.1.3.6.1.4.1.13742.6.10.2.2.1.1 |
|
reliabilityErrorLogId
Unique ID of the entry.
POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MAIN.CSUMERRLASTHOUR Number of checksum error… |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.10.2.2.1.2 |
|
reliabilityErrorLogValue
The normalized value
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.2.2.1.3 |
|
reliabilityErrorLogThreshold
The normalized threshold value
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.2.2.1.6 |
|
reliabilityErrorLogRawUpperBytes
The upper 4 bytes of the raw (not normalized) data.
reliabilityErrorLogRawUpperBytes and reliabilityErrorLogRawLowerBytes should be combined and interpreted as a signed 64-bit value |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.2.2.1.7 |
|
reliabilityErrorLogRawLowerBytes
The lower 4 bytes of the raw (not normalized) data.
reliabilityErrorLogRawUpperBytes and reliabilityErrorLogRawLowerBytes should be combined and interpreted as a signed 64-bit value |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.2.2.1.8 |
|
reliabilityErrorLogPOH
The time of occurrence of the event measured from the last
time the PDU was powered on |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.2.2.1.9 |
|
reliabilityErrorLogTime
The UTC time of occurrence of the event
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.2.2.1.10 |
hwFailureTable
table.1.3.6.1.4.1.13742.6.10.3.1
·
1 row entry
·
7 columns
A list of hardware failure entries.
A hardware failure entry.
Indexes
pduId hwFailureIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwFailureIndex
Index of the entry in the hardware failure table.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.13742.6.10.3.1.1.1 |
||||||||||
|
hwFailureComponentId
The id of the affected hardware component.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.6.10.3.1.1.2 |
||||||||||
|
hwFailureType
The hardware failure type.
|
HwFailureTypeEnumeration Textual Convention: HwFailureTypeEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.10.3.1.1.3 |
||||||||||
|
hwFailureAsserted
Reflects whether the failure state is asserted(true) or not(false).
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.6.10.3.1.1.4 |
||||||||||
|
hwFailureLastAssertTimeStamp
The timestamp indicating when the failure was last asserted.
It is measured in seconds since January 1, 1970 UTC. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.3.1.1.5 |
||||||||||
|
hwFailureLastDeassertTimeStamp
The timestamp indicating when the failure was last deasserted.
It is measured in seconds since January 1, 1970 UTC. If the failure is currently asserted then this has no meaning and is reported as 0. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.3.1.1.6 |
||||||||||
|
hwFailureAssertCount
The number of times the failure was asserted.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.6.10.3.1.1.7 |