measurementsInletSensorMinValue
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.5.2.3.1.8
Object
column
SNMPv2-SMIUnsigned32
The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.5.2.3.1.8- Type
- column
- Access
- readonly
- Status
- current
- Parent
- inletSensorMeasurementsEntry
- Table
- inletSensorMeasurementsTable
- Siblings
- 12
Syntax
SNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| measurementsInletSensorMinTimeStamp The timestamp of last change of the minimum value of sensor reading
provided as measurementInletSensor[Signed]MinValue | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.2.3.1.10 |
| measurementsInletSensorMaxValue The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value … | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.2.3.1.11 |
| measurementsInletSensorSignedMaxValue The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.5.2.3.1.12 |
| measurementsInletSensorMaxTimeStamp The timestamp of last change of the maximum value of sensor reading
provided as measurementInletSensor[Signed]MaxValue | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.2.3.1.13 |
| measurementsInletSensorMinMaxResetTimeStamp The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsInletSensor[Signed]{Min|Max}{Value|TimeStamp}
a… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.2.3.1.14 |
| measurementsInletSensorIsAvailable The sensor is present. | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.5.2.3.1.2 |
| measurementsInletSensorState The sensor state. | column | SensorStateEnumeration | .1.3.6.1.4.1.13742.6.5.2.3.1.3 |
| measurementsInletSensorValue The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDecimalDigits… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.2.3.1.4 |
| measurementsInletSensorTimeStamp The timestamp for reading. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.2.3.1.5 |
| measurementsInletSensorSignedValue The sensor reading as a signed integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDecimalDigits is… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.5.2.3.1.6 |
| measurementsInletSensorMinMaxValid The minimum and maximum values of sensor reading and their timestamps
provided as measurementsInletSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.5.2.3.1.7 |
| measurementsInletSensorSignedMinValue The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.5.2.3.1.9 |