transferSwitchSensorLogEntry
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.6.7.3.1
Object
row
An entry containing log objects for a transfer switch sensor.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.6.7.3.1- Type
- row
- Status
- current
- Parent
- transferSwitchSensorLogTable
- Table
- transferSwitchSensorLogTable
- Children
- 8
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| logTransferSwitchSensorDataAvailable Is data available for this sensor during this measurement period? | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.6.7.3.1.2 |
| logTransferSwitchSensorState The most critical sensor state during this measurement period. | column | SensorStateEnumeration | .1.3.6.1.4.1.13742.6.6.7.3.1.3 |
| logTransferSwitchSensorAvgValue The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by
transferSwitchSensorDecimalDigits. For example, if the val… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.6.7.3.1.4 |
| logTransferSwitchSensorMaxValue The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by
transferSwitchSensorDecimalDigits. For example, if the val… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.6.7.3.1.5 |
| logTransferSwitchSensorMinValue The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by
transferSwitchSensorDecimalDigits. For example, if the val… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.6.7.3.1.6 |
| logTransferSwitchSensorSignedAvgValue The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by
transferSwitchSensorDecimalDigits. For example, if the value … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.6.7.3.1.7 |
| logTransferSwitchSensorSignedMaxValue The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by
transferSwitchSensorDecimalDigits. For example, if the value … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.6.7.3.1.8 |
| logTransferSwitchSensorSignedMinValue The minimum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by
transferSwitchSensorDecimalDigits. For example, if the value … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.6.7.3.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduId A unique value for each PDU or power meter.
For BCM2 and PMC, pduId can be:
- 0 for the main controller
- The meter ID (rotary switch) for power meter
For a… | column | Integer32 | .1.3.6.1.4.1.13742.6.3.2.1.1.1 |
| transferSwitchId A unique value for each transfer switch. Its value
ranges between 1 and the value of transferSwitchCount. | column | Integer32 | .1.3.6.1.4.1.13742.6.3.9.3.1.1 |
| sensorType The type of sensor. | column | SensorTypeEnumeration | .1.3.6.1.4.1.13742.6.3.2.5.1.1 |
| logIndex A unique value for each entry in the log. Its value
ranges between 1 and the value of logSize. | column | Integer32 | .1.3.6.1.4.1.13742.6.6.1.2.1.1 |