inletSensorStateChangeDelay
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.3.3.4.1.14
Object
column
r/w
Unsigned32
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.3.3.4.1.14- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- inletSensorConfigurationEntry
- Table
- inletSensorConfigurationTable
- Siblings
- 20
Syntax
Unsigned32
Values & Constraints
Object Constraints
range: 0-300
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| inletSensorTolerance deprecated The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by
(inletSensorDecimalDigits + 1). For example, if … | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.10 |
| inletSensorMaximum The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDec… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.11 |
| inletSensorMinimum The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDe… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.12 |
| inletSensorHysteresis The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.13 |
| inletSensorLowerCriticalThreshold The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDec… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.21 |
| inletSensorLowerWarningThreshold The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDeci… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.22 |
| inletSensorUpperCriticalThreshold The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDec… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.23 |
| inletSensorUpperWarningThreshold The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDeci… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.24 |
| inletSensorEnabledThresholds A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. | column | Bits | .1.3.6.1.4.1.13742.6.3.3.4.1.25 |
| inletSensorSignedMaximum The largest possible reading as a signed integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDecima… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.4.1.26 |
| inletSensorSignedMinimum The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDecim… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.4.1.27 |
| inletSensorSignedLowerCriticalThreshold The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDecima… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.4.1.28 |
| inletSensorSignedLowerWarningThreshold The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDecimal… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.4.1.29 |
| inletSensorSignedUpperCriticalThreshold The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDecima… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.4.1.30 |
| inletSensorSignedUpperWarningThreshold The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 and
inletSensorDecimal… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.4.1.31 |
| inletSensorLogAvailable Is data logging enabled for this sensor? | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.3.3.4.1.4 |
| inletSensorUnits The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. | column | SensorUnitsEnumeration | .1.3.6.1.4.1.13742.6.3.3.4.1.6 |
| inletSensorDecimalDigits The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.7 |
| inletSensorAccuracy deprecated The accuracy: the maximum relative difference (in percent) between
measurement and the actual value.
This parameter does not apply to sensors without numerical reading. | column | HundredthsOfAPercentage | .1.3.6.1.4.1.13742.6.3.3.4.1.8 |
| inletSensorResolution The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by
inletSensorDecimalDigits. For example, if the value is 1 … | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.4.1.9 |